GEIST™ POWER FAILURE SENSOR

Quick Installation Guide

VM1055/590-2254-501A

   

 1

Part Number: 

PFS

Description

The Power Failure Sensor (PFS) is 

used to monitor voltage presence 

(grid/city power) on a circuit 

through the I/O ports of a remote 

environmental or power + 

environmental monitor. If voltage 

drops to zero, the monitored I/O 

reading drops below 10. 

NOTE: 

To monitor the loss of ‘grid-

supplied’ power, connect the 

PFS-100 directly to that power 

source 

before

 any UPS systems.  

NOTE: 

In order to monitor and 

report the PFS signal state during a 

power loss, the remote monitoring 

unit itself, as well as any switches 

or routers within the data path of 

the unit, 

must 

be backed up by 

UPS power.  If any of these units 

lose power during a power outage, 

appropriate remote alarm reporting 

cannot take place.

Installation

1. Using only an approved AC 

adaptor, plug the adaptor into 

the desired ‘grid-supplied’ 

power location. Do not plug the 

adaptor into the PFS-100 

sensor body yet.

2. Route the sensor body wire 

with the two stripped ends to 

the remote monitoring unit.

Connect the ends to the I/O 

port on the remote monitoring 

unit. The solid black wire 

connects to Common (-) and 

the striped black wire connects 

to the desired Input (1, 2 or 3).  

3. Plug the approved AC adaptor 

into the PFS-100.

NOTE: 

During initial setup, one 

PFS-100 LED turns on and one 

flashes for approximately 35 

seconds. After that time, a third 

Power Failure Sensor

Geist

TM

 Power Failure Sensor

SPECIFICATIONS

Sensor

Input

Output

PFS-100

4.5-6 VDC

3.4-5 VDC

Power Adaptor

Input

Output

PFS-100 US, PFS-100 UK, 

PFS-100 UN

100-240 VAC 50/60 Hz

6 VDC

Geist

TM

 Power Adaptor Options

PFS-100 US

PFS-100 UK

PFS-100 UN