Vertiv

 

|

 

eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3)

 

|

 

Rev. J 

14 

Figure 5:  

Efficiency Curve 

 

Environmental Ratings 

 

Operating Ambient Temperature Range: 

a)

 

+55 °C (+131 °F) to +80 °C (+176 °F) with derating output. 

b)

 

-40 °C (-40 °F) to +55 °C (+131 °F) with full power performance. 

 

Temperature Coefficient:  0.02% per degrees Celsius. 

 

Storage Ambient Temperature Range:  -40 °C (-40 °F) to +70 °C (+158 °F). 

 

Relative Humidity:  This solar converter is capable of operating in an ambient relative humidity range of 
0% to 95%, non-condensing. 

 

Altitude:  2000 m (6560 ft) at full power (power limited for heights above 2000 m). 

 

Surge Protection:  Compliance with EN61000-4-5 (4 kV Line to Line, 4 kV Line to Earth).  Capable of 
withstanding surges per ANSI/IEEE C 62.41 1999 Category B3 across the input terminals. 

 

NOTE!  

This level of protection is a widely used standard for telecommunications power equipment.  As 

with all such equipment, it is the end user's responsibility to provide an adequately sized Surge 
Suppression Device at the commercial power service entrance of the building that reduces all incoming 
surges to levels below the classes/categories stated for the equipment. 

 

Ventilation Requirements:  The solar converters are fan cooled and utilize front to back forced 
ventilation.  A  solar converter must be mounted so ventilating openings are not blocked and 
temperature of the air entering the solar converter does not exceed the Operating Ambient 
Temperature Range stated above. 

 

Single Solar Converter Audible Noise:  At 25 °C ≤50 dB(A) with fan in high speed.  Measurement made at 
0.6 m distance in front of solar converter and at same horizontal line of the middle of solar converter. 

 

High Voltage Category:  II 

 

Power Distribution System:  TN/TT/IT 

 

NOTE!  

The solar converter module is recommended to be used in an environment with Pollution of 

Degree 2 or less.  Pollution Degree 2 applies where there is only non-conductive pollution that might 
temporarily become conductive due to occasional condensation (such as the office environment). 

Содержание eSure S48-2000e3

Страница 1: ...eSure MPPT Solar Converter Module User Manual UM1S482000E3 Revision J Specification Number 1S482000e3 Model Number S48 2000e3...

Страница 2: ...rect methods tools and materials to be used in performing procedures not specifically described in this document This document may contain confidential and or proprietary information of Vertiv Group C...

Страница 3: ...s 5 Personal Protective Equipment PPE 6 Hazardous Voltage 6 Handling Equipment Containing Static Sensitive Components 6 Static Warning 7 Introduction 9 Overview 9 Specifications 9 Operation 19 DC Inpu...

Страница 4: ...avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT...

Страница 5: ...oltages DC Input Voltages DANGER This system may operate from 400 VDC input voltage capable of producing fatal electrical shock DC input power must be completely disconnected from the branch circuits...

Страница 6: ...inspect operate or maintain the equipment Do not work on LIVE parts If required to work or operate live parts obtain appropriate Energized Work Permits as required by the local authority per NFPA 70E...

Страница 7: ...sistor is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive compone...

Страница 8: ...Vertiv eSure MPPT Solar Converter Module User Manual UM1S482000E3 Rev J 8 This page is intentionally blank...

Страница 9: ...operate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately 2000 W Constant Power Mode As load increases above approx...

Страница 10: ...pability is restored when the temperature decreases to below approximately 65 C 149 F Refer to Figure 3 to view the relationship between the output power and the ambient temperature with the input vol...

Страница 11: ...ut 50 VDC or 56 VDC Vout 58 VDC Regulation a Static Steady state regulation is 0 6 as controlled within the solar converter for any and all combinations of load from no load to full load input voltage...

Страница 12: ...omplies with Telcordia GR 947 CORE 1 Wideband noise emission is 250 mV peak to peak between 0 Hz to 100 MHz and 50 mV rms in any 3 kHz band 10 KHz to 20 MHz DC Input Ratings Nominal Input Voltage 140...

Страница 13: ...40 1 875 75 17 300 VDC 2114 8 53 450 37 790 95 51 1943 3 53 460 34 780 95 68 1772 6 53 470 31 760 95 80 1566 7 53 490 28 125 96 02 1433 3 53 490 25 746 96 08 1265 3 53 510 22 740 96 17 1098 3 53 530 1...

Страница 14: ...d user s responsibility to provide an adequately sized Surge Suppression Device at the commercial power service entrance of the building that reduces all incoming surges to levels below the classes ca...

Страница 15: ...t of load current and output voltage is approximately 2000 W Constant Power Mode As load increases above approximately 2000 W non adjustable output current continues to increase but output voltage dec...

Страница 16: ...tart timer expires the solar converter shuts down and locks out Manual restart is then required by turning power to the solar converter off or by removing the solar converter waiting until the LEDs on...

Страница 17: ...This feature can be disabled via the controller allowing the fan to run at full speed regardless of temperature Paralleling Up to 30 solar converters can be connected in parallel in one system Communi...

Страница 18: ...Voltage Regulation Input Voltage Output Voltage Output Current Current Limit Setting Temperature Over Voltage Setting On Off Status Fault Alarms such as HVSD Fan Fail Protection Alarms such as Input V...

Страница 19: ...e solar converter s front panel The functions of these indicators are as shown in Table 3 NOTE DC voltage must be present at the solar converter output terminals from battery or an operating solar con...

Страница 20: ...n DC input under over voltage PFC over voltage Moderate load sharing imbalance Solar converter not inserted into the slot completely Solar converter over temperature protection Flashing Loss of commun...

Страница 21: ...ving a solar converter module NEVER hold the handle in the closed position when installing a solar converter module into a shelf Procedure DANGER Refer to Figure 7 as this procedure is performed 1 Unp...

Страница 22: ...r converter is properly seated in the shelf If the current sharing imbalance still persists following the verification suggested above replace the solar converter exhibiting the current imbalance Sola...

Страница 23: ...ed remove any object that may be blocking the fan Ventilation blocked inlet or outlet remove any object that may be blocking the inlet or outlet Ambient temperature too high or solar converter inlet t...

Страница 24: ...be easily disabled notify the appropriate personnel to disregard any alarms associated with this system while this procedure is performed 2 Loosen the captive screw on the module s handle Pull the han...

Страница 25: ...s securing the front panel to the chassis 5 For proper orientation of the new fan observe the location of the fan wires and the fan rotation and air flow arrows on the old fan 6 Carefully remove the f...

Страница 26: ...Vertiv eSure MPPT Solar Converter Module User Manual UM1S482000E3 Rev J 26 Figure 8 Fan Replacement S48 2000e3 Fan Faceplate Mounting Screws 3 Faceplate Align holes in fan with tabs on faceplate...

Страница 27: ...Vertiv eSure MPPT Solar Converter Module User Manual UM1S482000E3 Rev J 27 This page is intentionally blank...

Страница 28: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1S482000E3 RJ 10 19...

Отзывы: