System Installation Considerations 

590-2172-501A/SL-29241/4200-136 
 

6-1 

 

 

 

 

6.  System Installation Considerations

 

 

This section describes items that should be considered before installing the UXIMe system. 

 

6.1   Disconnect Device

 

The Pulsed Load Lead harness which plugs into the Resistance Steps connector is the primary disconnect 
device. Unplug this connector to disconnect power from the UXIMe. 

 

6.2   Equipment Location

 

Consider the placement of the equipment in the event service is required. For example, access to the 
rear of the equipment or visual access to the status lights may be needed. The equipment is convection 
cooled and no cooling fans are used. To maintain proper operating temperature, the equipment must 
not be enclosed in another cabinet without proper ventilation. 

 

6.3   Rack Mounting

 

If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack 
environment may be greater than room ambient. Therefore consideration should be given to installing 
the equipment in an environment compatible with the maximum ambient temperature specified in the 
Product Description Guide. Installation of the equipment in a rack should be such that the amount of air 
flow required for safe operation of the equipment is not compromised. Mounting of the equipment in 
the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading. 

 

6.4   Mounting Options

 

The equipment can accommodate two types of mounting: 19

 rack mount or flush mount. Standard 

mounting is 19

 rack mounting. If the flush mount option is used, the optional flush mounting brackets 

will need to be installed. 

 

6.5   Wire Length

 

All harnesses lengths are standard 25

 or 50

 length and in most cases, should not require additional 

lengths. Distances between the battery, battery charger and the battery monitoring equipment should 
be considered. If longer harness lengths are required, harnesses are available in a maximum of 50

’ 

lengths. The resistance load test-wiring limits this length to the maximum distance the UXIMe can be 
mounted from the battery string. This manual describes all harnesses at the standard 25

 or 50

 length. 

 

6.6   Battery String Isolation

 

Isolate the battery string prior to installing the system. 

 

Important! 

Never attempt installation on a battery string that is in service and not fully isolated from 

the DC bus and load circuits. 

 

6.7   Cell Number 1 Identification

 

When referring to any material in this installation guide and reference is made to an actual cell number, 
always consider Cell 1 as the most positive end of the battery with respect to the battery charger. As the 
cells increment toward the negative end of the string, increment the cell numbers as well. 

Содержание Alber UXIMe

Страница 1: ...er Universal Xplorer Industrial Monitor UXIMe Battery Monitor Installation Guide Vertiv Corporation 1050 Dearborn Drive Columbus OH 43085 Tel 954 377 7101 www vertivco com 590 2172 501A SL 29241 4200...

Страница 2: ...o be used in performing procedures not specifically described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the property of V...

Страница 3: ...6 2 Vertiv Customer Service is available Monday to Friday 8 00AM to 4 30PM Eastern Time Telephone 954 377 7101 Email alber service vertivco com Website www vertivco com Corporate Office Address Vertiv...

Страница 4: ...iderations 6 1 6 1 Disconnect Device 6 1 6 2 Equipment Location 6 1 6 3 Rack Mounting 6 1 6 4 Mounting Options 6 1 6 5 Wire Length 6 1 6 6 Battery String Isolation 6 1 6 7 Cell Number 1 Identification...

Страница 5: ...c Communication Connection 16 1 17 Network Communication Connection 17 1 17 1 Network Protocols Supported 17 1 18 Parameter Alarm Connection 18 1 19 Hardware Alarm Connection 19 1 20 ELS2 Connections...

Страница 6: ...0 2 Figure 8 Exposed Dual or Multiple Posts Connections 10 3 Figure 9 Resistance Steps Connection to Battery 11 1 Figure 10 Charger Control Sense Lead Connection to Battery and Charger 12 1 Figure 11...

Страница 7: ...Installation Task List 4 1 Table 2 Model Number Description 5 1 Table 3 Inventory List 5 3 Table 4 Digital Input Modes 8 1 Table 5 Digital Input Jumper Settings 8 1 Table 6 Cell Measurement Specificat...

Страница 8: ...ings or capabilities 1 2 Document Symbols The symbols below appear in this manual or are affixed to the Vertiv device It is important to review these symbols and to understand the type of instructiona...

Страница 9: ...al slow blow fast blow or time delay must be used Equipment Access Operating personnel must not remove equipment covers shields or panels Component repair replacement and internal adjustments must be...

Страница 10: ...g For Wires Use only wire supplied with the installation kit Ventilation Never block equipment ventilation ports or openings The equipment must have adequate ventilation to prevent overheating Ensure...

Страница 11: ...m is disconnected and power to the units has been shut off You must disconnect the system components and the monitor system cabinet if a cabinet is being used from AC and or DC power sources 2 3 Sense...

Страница 12: ...ers active monitor status and state of active or latched alarms Embedded email clients for alarm notifications and data delivery of battery parameters XML format with priority handling of message sent...

Страница 13: ...System Overview 590 2172 501A SL 29241 4200 136 3 2 Figure 1 Typical System Connection...

Страница 14: ...Properly install the tab washers Installation of Tab Washers page 7 1 Configure the unit Unit Configuration page 8 1 Mount the equipment Equipment Mounting page 9 1 Connect the sense lead harnessing...

Страница 15: ...iv immediately The model number is in the format of PPPP COB where PPPP is 1010 and C O and B are described below PPPP C O B Description Choices 0 RS 485 Only 1 Network 1013 C Communications 2 Fiber O...

Страница 16: ...2 554 100 Optional 8 25 35 50 75 or 100 Double Ambient Temperature Sensor harness optional One ambient temperature sensor per system 1102 560 25 1102 560 50 1102 560 75 1102 560 100 25 50 75 or 100 Se...

Страница 17: ...shers per system other sizes available upon request 2027 029 UXIMe Configurator Software installation CD KIT 1400 531 Optional Flush mounting kit Optional 3703 006 Optional Fiber Optic Cable Optional...

Страница 18: ...t compromised Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading 6 4 Mounting Options The equipment can accommodate two ty...

Страница 19: ...and quantity depend on the system configuration The actual placement of these tab washers in relation to the battery post and existing hardware is critical In instances where a single load tab washer...

Страница 20: ...ssed Post Tab Washer Assembly To determine tab washer placement refer to the Configuration Connection Diagram in the back of this manual Locate the desired configuration that will be installed Using t...

Страница 21: ...d with the UXIMe for configuration There is a pair of 2 pin jumpers associated with each digital input which must be set according to the mode desired The cover of the unit must be removed to gain acc...

Страница 22: ...Unit Configuration 590 2172 501A SL 29241 4200 136 8 2 The location of the jumpers is shown in the figure below The factory does not have the jumpers inserted Figure 4 Digital Input Jumper Locations...

Страница 23: ...19200 bps default is 9600 RS 485 termination is recommended when intermittent communications occur RS 485 termination is enabled when the jumper is across Pins 1 and 2 of JP7 not the factory default s...

Страница 24: ...n each side of the unit To connect the flush mount brackets to the unit remove the two screws on each side that secure the rack mount brackets to the unit Install the supplied front spacer brackets us...

Страница 25: ...oper termination to each battery connection point 10 1Voltage Sense Lead Connection Preparation In order to prepare the sense lead harness connection follow these steps 1 Each voltage sense lead wire...

Страница 26: ...4200 136 10 2 Figure 7 Voltage Sense Lead Connections to Battery XX cable length Caution When a load lead wire connects to the same point as a voltage sense lead the load lead wire must be the closes...

Страница 27: ...negative sense lead wires white with colored stripe of the harness attach to the corresponding positive and negative terminals of the battery in a way that will monitor as many strap connections as po...

Страница 28: ...uish each resistance load step for proper termination at the battery From the UXIMe the Resistance Load cables are routed to the installation location and cut to the appropriate length For ease of fut...

Страница 29: ...washer verify that the fuse is not installed The fuse will be installed at time of startup Note It is very important that the load connection is the closest connection to the post if two tab washers...

Страница 30: ...g path and the required wire length from the equipment J0 to the connection points begin assembling the 10K resistor sense lead assembly to the charger sense lead harness as described in Section 10 1...

Страница 31: ...ess with 25 50 75 or 100 of cable Route the cable to the desired location to capture ambient room temperature and plug the connector into the rear of the unit Note The UXIMe device comes with one sing...

Страница 32: ...To connect the device monitored connect to one of the three inputs located on the rear of the unit If only a switch open close contact mode is being used then polarity is not important However if a v...

Страница 33: ...s BMS or accessory modules not currently supported Each of these ports is labeled 1 and 2 When connecting to a remote controller connect the A B connection of port 1 to the remote controller When mult...

Страница 34: ...TX of the UXCM to the RX of the UXIMe and then the TX of the UXIMe to the RX of the UXCM When cutting the fiber optic cable to length the ends must be properly cut and polished to achieve reliable co...

Страница 35: ...nector on the UXIMe Figure 15 Network Connection 17 1Network Protocols Supported There are several protocols supported by the network interface and will require specific ports to be opened up on the n...

Страница 36: ...the programmed thresholds This contact has three connections NC normally closed NO normally open COM common Connection can be made directly to the facility s alarm reporting system If multiple units a...

Страница 37: ...UXIMe and stays in this state during normal operation The relay changes state and the normally closed NC contact becomes active during any of the following fault conditions 1 Power fault 2 Application...

Страница 38: ...29241 4200 136 20 2 20 ELS2 Connections The ELS2 Power connections are made to the 5VDC connection using the optional harness 1108 164 XX Connect from the 5V ELS PWR port to the POWER jack on the ELSi...

Страница 39: ...ondensing at 5 C to 31 C 0 to 50 RH non condensing at 31 C to 40 C Indoor Use Only Measurement Category O 500V Transient Rating Pollution Degree 2 Altitude 0 to 2000 meters above sea level Alarms 2 Fo...

Страница 40: ...5 of reading 5 Cell Monobloc Temperature 0 C to 80 C 0 1 C 32 F to 176 F Table 6 Cell Measurement Specifications 21 3 System Measurements This section describes system measurement specifications Param...

Страница 41: ...UXIMe Drawings 590 2172 501A SL 29241 4200 136 22 1 22 UXIMe Drawings...

Страница 42: ...UXIMe Drawings 590 2172 501A SL 29241 4200 136 22 2 Figure 19 UXIMe Wiring Schematic Diagram...

Страница 43: ...Replacement 2 1 materials standard 5 3 Materials Received List 5 1 Mounting Options 6 1 Multiple Positive and Negative Posts 10 3 Network Protocols 17 1 Note 1 1 Operating Damaged Equipment 1 2 Operat...

Отзывы: