background image

 
String Current Calibration 

 

 

590-2106-501A/SL-29421/4200-099 

 

 

 

Gain Level 

Input voltage 1 

Input voltage 2 

Gain 10B 

100.100 mV 

100 uV 

Gain 100B 

10.020 mV 

20 uV 

Gain 1000 

1.020 mV 

20 uV 

Table 1 - Calibration Input Voltages 

5.

 

Record the actual input value indicated by the DVM in the IC 1 input 1 box of the Gain 
Calibration tab. 

6.

 

Click 

Get Input 1 Counts

 and the Raw Counts value will update. 

7.

 

Click 

Get Input 1 Counts

 a second time after the raw counts have been updated and wait for a 

second raw counts update before moving on to the next step. 

8.

 

Adjust the Calibration source to the nominal Input Voltage 2 value for the selected gain level 
(100uV for Gain 10) shown in table 1. 

9.

 

Record the actual input value indicated by the DVM in the IC 1 input 2 box of the Gain 
Calibration tab. 

10.

 

Click 

Get Input 2 Counts

 and the Raw Counts value will update. 

11.

 

Click 

Get Input 2 Counts

 a second time after the raw counts have been updated and wait for a 

second raw counts update before moving on to the next step. 

12.

 

Click 

Update

 to send the calibration constants to the UXIM/UXTM. Typical raw count values 

are shown in table 2. 

Gain 

Input voltage 1 

Typical Counts 

Input voltage 2 

Typical Counts 

Gain 10B 

100.100 mV 

2541760 

100 uV 

2578 

Gain 100B 

10.020 mV 

2538220 

20 uV 

5096 

Gain 1000 

1.020 mV 

2584864 

20 uV 

51722 

Table 2 - Calibration Voltages and Typical Raw Count Values 

13.

 

Repeat steps 3 through 12 for the remaining gain levels in table 1. Choose each gain level from 
the Gain drop-down box and adjust the Calibration source to the corresponding nominal input 
voltage value shown in table 1. 

Содержание Alber Universal Xplorer Industrial Battery Monitor

Страница 1: ...r Industrial and Telecom Monitors UXIM and UXTM Battery Monitor Calibration Guide Vertiv Corporation 1050 Daerborn Drive Columbus OH 43085 Tel 954 377 7101 Fax 954 377 7042 www vertivco com 590 2106 5...

Страница 2: ...o be used in performing procedures not specifically described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the property of V...

Страница 3: ...rtiv Customer Service is available Monday to Friday 8 00AM to 4 30PM Eastern Time Telephone 954 377 7101 Fax 954 377 7042 Email alber service vertivco com Website www vertivco com Corporate Office Add...

Страница 4: ...00 099 iii Table of Contents 1 Safety Information 1 1 1 General 1 1 2 Document Symbols 1 1 3 Safety Symbols 2 1 4 Product Safety Practices 2 2 String Current Calibration 4 2 1 Equipment Required 4 2 2...

Страница 5: ...9 iv List of Figures Figure 1 UXIM Equipment Setup 4 Figure 2 UXTM Equipment Setup 5 Figure 3 Tools Gain Calibration 6 List of Tables Table 1 Calibration Input Voltages 7 Table 2 Calibration Voltages...

Страница 6: ...r energize the UXIM UXTM until after the installation is complete Never exceed equipment voltage power ratings or capabilities 1 2 Document Symbols The symbols below appear in this manual or are affix...

Страница 7: ...minimize shock hazard the system chassis must be connected to an electrical protective earth ground when required When AC mains are used for the power source the system must be connected to the AC po...

Страница 8: ...dify equipment Due to the possibility of introducing additional hazards do not substitute parts or perform any unauthorized modification to the product If necessary contact Vertiv to ensure the safety...

Страница 9: ...nt Calibration 2 1 Equipment Required for the UXIM 6 5 digit voltmeter DVM capable of measuring 10uV Keithley 2701 or equivalent Precision 10uV to 500mV DC Voltage Standard Calibration Source EDC MV10...

Страница 10: ...5 2 2 Equipment Required for the UXTM 6 5 digit voltmeter DVM capable of measuring 10uV Keithley 2701 or equivalent Precision 10uV to 500mV DC Voltage Standard Calibration Source EDC MV106 or equival...

Страница 11: ...rs using the method specific for the equipment being used If using Keithley 2701 short the inputs then press the REL button 2 Establish a USB connection between the UXIM UXTM Configurator software and...

Страница 12: ...tual input value indicated by the DVM in the IC 1 input 2 box of the Gain Calibration tab 10 Click Get Input 2 Counts and the Raw Counts value will update 11 Click Get Input 2 Counts a second time aft...

Отзывы: