Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
20
4.6
Expansion Shelf(s) Interconnections
Installing Output Paralleling Leads
Procedure
1.
Perform the procedure in Figure 4.5 for each expansion shelf.
Figure 4.5: DC Output Paralleling Interconnections
Cable, lugs (P/N 144511), and labels are
provided loose with the Expansion Shelf
to assemble a Return and a -48V
paralleling cable.
1. Cut the cables to the proper length.
2. Lug the cables
(use standard brown die for 2 ga. cable).
3. Connect cables between terminals
as indicated below. Torque to 58 in-lbs.
4. Re-Install Expansion Wiring Covers.
(refer to procedure in the
“Installing the System” chapter.)
Expansion
Wiring Covers
Hardware provided
on terminals.
RETURN
PARALLELING
CABLE
-48V
PARALLELING
CABLE
584622100 / 584622200 shown.
584622300 / 584622400 similar.