System Application Guide
SAG582136800
Spec. No. 582136800 (Model 502
NGFB
)
Revision BA, April 8, 2020
Page 91 of 129
Input
Voltage
(VAC)
Ambient
Operating
Temp.
(1)
Max. Total
Output Curr.
(Amps)
Loop
Length (Ft.)
1.0 Volt Drop
(2)
Recm. 90°C
Wire Size
Recm.
Crimp Lug
(3)
120
40
157
76
(1) 2/0 AWG
(1) 245347200
96
(1) 3/0 AWG
(1) 245347300
121
(2) 1/0 AWG
(2) 245347100
65
126
120
(1) 3/0 AWG
(1) 245347300
151
(2) 1/0 AWG
(2) 245347100
190
(2) 2/0 AWG
(2) 245347200
76
(2) 1/0 AWG
(2) 245347100
95
(2) 2/0 AWG
(2) 245347200
65
200
119
(2) 2/0 AWG
(2) 245347200
151
(2) 3/0 AWG
(2) 245347300
Table 14C
Recommended DC Output Wire Size PER SHELF and Lug Selection
LIST 4
Input
Voltage
(VAC)
Ambient
Operating
Temp.
(1)
Max. Total
Output Curr.
(Amps)
Loop
Length (Ft.)
1.0 Volt Drop
(2)
Recm. 90°C
Wire Size
Recm.
Crimp Lug
(3)
120
40
236
50
(2) 2 AWG
(2) 245348200
76
(3) 2 AWG
(3) 245348200
80
(2) 1/0 AWG
(2) 245347100
65
189
94
(3) 2 AWG
(3) 245348200
100
(2) 1/0 AWG
(2) 245347100
126
(2) 2/0 AWG
(2) 245347200
240
40
374
80
(2) 3/0 AWG
(2) 245347300
96
(3) 2/0 AWG
(2) 245347200
121
(3) 3/0 AWG
(3) 245347300
65
299
120
(3) 2/0 AWG
(3) 245347200
151
(3) 3/0 AWG
(3) 245347300
160
(4) 2/0 AWG
(4) 245347200
Table 14D
Recommended DC Output Wire Size PER SYSTEM and Lug Selection
LIST 6