EXS
User Manual 10H52260UM60 - Rev. 1 - 10/2017
101
10.4
Electrical Specifications (Input Rectifier)
Table 10-4 Rectifier AC input (mains)
Item
Unit
Rated power (kVA)
10kVA-20kVA
Rated AC input voltage
1
Vac
380/400/415, 3-phase 4-wire (+PE) TN/TT power distribution system
Input voltage range
2
Vac
305 - 499
Frequency
2
Hz
50/60 (range: 40 - 70)
Power factor
kW/kVA, full load
(half load)
0.99 (0.98)
Total current harmonic
distortion
%
Linear full load < 3% (battery float charge) (3-in 3-out)
Non-linear full load < 5% (battery float charge) (3-in 3-out)
Linear half load < 7% (battery float charge) (3-in 3-out)
Non-linear half load < 8% (battery float charge) (3-in 3-out)
Linear full load < 10% (battery float charge) (3-in 1-out)
1. The rectifiers will operate at any of the rated supply voltages and frequencies without the need for any further adjustment.
2. At 305V input mains, the UPS maintains the specified output voltage at rated load without discharging the battery.
10.5
Electrical Specifications (Intermediate DC Circuit)
Table 10-5 Battery
Item
Unit
Rated power (kVA)
10kVA-20kVA
Quantity of lead-acid batteries
1
Block
24, 32, 40 (12Vdc)
Float voltage
V/cell (VRLA)
2.27 (selectable from 2.2V/cell to 2.3V/cell)
Constant current and constant voltage charge mode
Temperature compensation
mV/°C/cl
-3.0 (selectable from 0 to -5.0 around 25°C or 30°C, or inhibit)
Ripple voltage (float charge)
%
≤ 3%
Boost voltage
V/cell (VRLA)
2.35 (selectable from 2.3 to 2.4)
Constant current and constant voltage charge mode
Boost control
Float-boost current trigger 0.05C
10
(selectable from 0.02 to 0.08)
Boost-float current trigger 0.02C
10
(selectable from 0.01 to 0.05)
12h safety time time-out (selectable from 5h to 24h)
Boost mode inhibit also selectable
EOD voltage
V/cell (VRLA)
1.60 - 1.85
Battery charger
V/cell
02:35
Constant current and constant voltage charge mode;
Boost charge mode automatic trigger or boost charge mode inhibit
also selectable
1. When the number of battery is 24-block, the maximum output capacity of the UPS is 70% of rated capacity.