Vertiv | Liebert EXS 80kVA UPS | User Manual
7
Overview
1.3.1. Parallel System Features
1. The hardware and software of parallel system are completely identical to that of the single module. Parallel
system configuration can be achieved through configuration software settings.
2. Parallel cables are connected in a ring, offering system reliability and redundancy.
3. The total load of the parallel system can be queried from the LCD of each UPS.
1.3.2. Parallel System Requirements
A group of paralleled modules act as if they were one large UPS with the benefit of greater reliability. The
following requirements apply to ensure that all modules are utilised equally and that they comply with relevant
wiring rules:
1. All UPS modules must be of the same series, and connect to the same bypass source.
2. The N line of bypass and rectifier input sources must be connected to the same neutral line terminal.
3.
Any
RCD
, if
installed, must be of an appropriate setting and located upstream of the common
neutral line
input terminal
. Alternatively, the device must monitor the protective earth current of the system. Refer to
Warning: High earth leakage current
before
Table of
Contents
.
4. Parallel system consists of two or more UPS modules, the bypass load sharing inductors (optional) should be
selected.
Содержание EXS 0080kTK16FN01000
Страница 1: ...Liebert EXS 80kVA UPS User Manual...
Страница 8: ...This page is intentionally left blank...
Страница 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Страница 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Страница 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Страница 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Страница 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Страница 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Страница 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Страница 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Страница 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...