8
78D0011
WDV Series Gas Fireplace
clearances
Mantel clearances
nOte:
The combustible area above the facing must
not protrude more than 3/4" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
6
”
5
”
3
”
4
56O
”
45°
1
”
3
56O
”
FP2423
mantel leg
1
56O
”
2
56O
”
FP2423
Side of Fire-
place Opening
Figure 5 -
Mantel clearances
top View
clearances tO cOMBustIBles
Follow these instructions carefully to
ensure safe installation. Failure to follow
instructions exactly can create a fire
hazard.
the appliance cannot be installed on a carpet,
tile or other combustible material other than
wood flooring. If installed on carpet or vinyl
flooring, the appliance shall be installed on
a metal, wood or noncombustible material
panel extending full width and depth of the
appliance.
W
arn
In
G
54” Minimum
Ceiling
12” Max.
Depth
2
1
/
2
” Max
Depth
6” Min.
From Opening
12” Min.
From Opening
6” Min.
FP2421
mantel clearances
5
6M
”
Min. to Combustibles
Figure 4 -
Ceiling and Sidewall Clearances
FP2421
9"
12"
6"
12"
6"
2
1
/
2
"
FP2422
mantel clearances
Wall
Stud
Insulation
Board
Standoff
Top of Fireplace
Opening
FP2422
side View