Vermont Castings Vigilant II Скачать руководство пользователя страница 22

22

Vermont Castings Vigilant

2000898

Adjust the Chain Length

1.  Make the initial chain adjustment when the stove is 

cold. With the lever pointing straight up, connect the 
ball chain to the air intake shutter so the shutter is 
half open. This setting will work well for most instal-
lations.

2.  Replace the back heat shield if there was one in-

stalled originally.

3.  Check these three important points when the stove 

is hot:

• 

The chain should be long enough so the air in-
take shutter can close all the way.

• 

The chain should be short enough so that even 
at high temperatures the air intake shutter can be 
opened a little.

• 

The lever should always be accessible over the 
stove top.  

KT448

bend lever

3/18/04  djt

KT448

Fig. 28

  Hold the bar in place as you bend the new lever into 

position.

KT449

chain adjust

3/18/04  djt

KT449

Fig. 29

  On a cold stove, a properly adjusted thermostat 

assembly will draw the shutter half open when the lever is 
straight up.

The Chimney System 

For safety, good stove performance, and to protect your 
chimney and chimney connector, inspect your chimney 
and chimney connector on a regular schedule.  Clean 
the system if necessary.  Failure to keep the chimney 
and connector system clean can result in a serious 
chimney fire.  
When coal is burned, the products of combustion 
combine with moisture to form a soot residue which 
accumulates on the flue lining.  When ignited, this soot 
makes an extremely hot fire.  The chimney connector 
and chimney should be inspected at least once every 
two weeks during the heating season to determine if a 
soot buildup has occurred.  If soot has accumulated, it 
should be removed to reduce the risk of a chimney fire.  
Fly ash, carried from the fuel bed by draft in the chim-
ney, should also be removed from the chimney and 
chimney connector.  While these particles are non-com-
bustible, they may accumulate enough to reduce the 
size of the flue, and restrict draft.  This will affect stove 
performance, and is a potentially hazardous situation.  
(See Safety Tips).  Reduce the risk of restricting draft 
by keeping the system clean.  In addition, fly ash con-
tains an acid which, when combined with moisture, can 
cause rapid deterioration of metal or tile chimney walls.
To inspect the chimney, let the stove cool completely.  
Then, using a strong light, sight up through the flue col-
lar into the chimney flue. If it is not possible to inspect 
the flue system in this fashion, the stove must be dis-
connected to provide better viewing access. 
Clean the chimney using a specially designed brush 
the same size and shape as the flue liner.  Flexible 
fiberglass rods are used to run the brush up and down 
the liner, causing any deposits to fall to the bottom of 
the chimney where they can be removed.  The chimney 
connector should be cleaned by disconnecting the sec-
tions, taking them outside, and removing any deposits 
with a stiff wire brush.  Reinstall the connector sections 
after cleaning, being sure to secure the individual sec-
tions with sheetmetal screws.
If you feel any uncertainties about chimney inspection, 
contact your local Vermont Castings Authorized Dealer, 
or engage a professional chimney sweep in your area 
to perform the inspection and cleaning of the chimney.

Содержание Vigilant II

Страница 1: ...se SAFETY NOTICE IF THIS APPLIANCE IS NOT PROPERLY INSTALLED OPERATED AND MAINTAINED A HOUSE FIRE MAY RESULT TO REDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW INSTRUCTI...

Страница 2: ...ur Authorized Vermont Castings Dealer anytime you have a particular question about your stove or its performance Be assured that your cast iron Vermont Castings stove or replace has been made with the...

Страница 3: ...ption obtained under laboratory conditions and on average ef ciencies These values are based on operation in building code conforming homes under typical winter climate condi tions in New England If y...

Страница 4: ...eight due largely to a difference in temperature between the gases inside the chimney and gases out side the chimney Because gas expands when heated warm gases inside the chimney weigh less than cool...

Страница 5: ...necessary for this type of installation The chimney should extend at least 3 feet above the highest point where it passes through a roof and at least 2 feet higher than any portion of a building with...

Страница 6: ...VE OR INSERT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE Chimney Size When out tted with the standard 6 150 mm ue col lar The Vigilant II Coal Stove is designed to perform well when vented through ues...

Страница 7: ...ove will be in either a parallel or a corner instal lation not both Use only the part of the chart that ap plies to your installation Note Side clearances do not apply to corner installations Measure...

Страница 8: ...mum clearance parallel installation rear heat shield For rear exiting stoves both rear and side clearances are determined by the heat from the stove provided that the connector does not pass near a co...

Страница 9: ...ed to change an unprotected wall to a protected wall allow ing the clearances given in the right half of the Clear ance Chart Wall shields should be constructed of 24 gauge or heavier sheetmetal 1 2 n...

Страница 10: ...mm Clearance to Combustibles in Front of Stove 1 A ceiling heat shield 24 610 mm in diameter and suspended 1 25 mm from the ceiling must surround the chimney con nector in installations in which the...

Страница 11: ...mm D 16 406 mm E 12 305 mm F 2 51 mm to either side of connector Fig 12 Minimum oor protection requirements ST689 oor protector must meet the same requirements as for standard legs Floor Protection f...

Страница 12: ...market which have been tested and listed speci cally for use as wall pass throughs Use only these tested and listed accessories for wall pass throughs The National Fire Protection Association NFPA has...

Страница 13: ...cessories The Removable Handle The removable handle is inserted into the front door stub or the damper handle stub when you want to open or close the doors or change the position of the damp er The ha...

Страница 14: ...Coal Stove Freestanding If the chimney connector must pass through a combustible wall to reach the chimney follow the recommendations in the Wall Pass Through sec tion ST243 thinble connection 12 13...

Страница 15: ...e Watch these points If there is a combustible mantel or trim check the stove and chimney connector clearances in the Clearance Chart Use the necessary combination of mantel trim and connector heat sh...

Страница 16: ...nformation about the ash content of the coal he sells The Vigilant II Coal Stove is designed to burn anthracite hard coal or bituminous coal soft coal Do not burn other fuels As shipped from the facto...

Страница 17: ...is between 400 and 700 F although temperatures slightly outside of this range may be expected However if tempera tures go above 700 F for extended periods decrease the air supply move the thermostat...

Страница 18: ...smaller and draft problems can result Avoid draft problems when the outside temperature is 35 F or higher by operating your stove with the damper open to keep ue temperatures high If draft problems o...

Страница 19: ...striker screw one turn and re tight ening the small locking nut Keep making adjustments slowly until the setting is right The handle should resist slightly as it is turned to the closed position and t...

Страница 20: ...e plate and then slide it toward the front of the stove so the end with the shorter offset will be behind the iron The cover in the lower reback will be inserted into the opening and pushed to the lef...

Страница 21: ...side up on a level work sur face 2 Remove the two retainer clips Carefully remove the old glass 3 Examine the gasketing Worn gasketing should be replaced Remove the old gasketing Cut new gasket ing to...

Страница 22: ...y two weeks during the heating season to determine if a soot buildup has occurred If soot has accumulated it should be removed to reduce the risk of a chimney re Fly ash carried from the fuel bed by d...

Страница 23: ...if any appear to be corroded Is the door handle adjusted so the doors close tight ly Instructions for adjusting the handle are given in the Maintenance Section Draft Problems If the draft in the chim...

Страница 24: ...m Description Part Number Item Description Part Number CFM Corporation reserves the right to make changes in design materials speci cations prices and discontinue colors and products at any time witho...

Страница 25: ...n Cover w Handle 1601027 32 Shaker Handle 1600903 33 Ashpan 1400927 34 Ashdoor 1305045 35 Front Door Handle Assembly 5004237 36 Ashpan Bracket 1601039 37 Ashdoor Hinge 1305046 38 Ashdrop 1305044 39 Bo...

Страница 26: ...26 Vermont Castings Vigilant 2000898...

Страница 27: ...s 1 This warranty is transferable however proof of original purchase is required 2 CFM Corporation offers no warranty on chipping of enamel surfaces Inspect your Vigilant II Coal Stove prior to accept...

Страница 28: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: