background image

6

WMC Series Woodburning Fireplace

20000583

Planning Information

Preplanning  an  installation  is  very  important  to  ensure 

safety  and  to  save  time  and  money.   An  installer  must 

predetermine where a fireplace will be set and how the 

chimney system will be run.

Mounting the Fireplace

A fireplace may be mounted on the following surfaces:
1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed beneath 

each of the four (4) corners of the fireplace.

The fireplace 

must

 be spaced 1/2" (13 mm) from a com-

bustible back wall and 1/2" (13 mm) from a combustible 

side wall or support. Refer to Page 14, Figure 18.

Planning the Chimney Run

Determine how the chimney will be run, length of run and 

chimney components required to complete the job. (Fig. 4)  

Never

 install a chimney below minimum heights.

The Ten Foot Rule

Major  U.S.  building  codes  specify  a  minimum  chimney 

height above the roof top. The “Ten Foot Rule” is a fire 

safety rule and not a draft rule.  It is recommended that 

you always meet or exceed the “Ten Foot Rule,” especially 

when installing a termination on a high pitch roof.  (Fig. 

6)
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the peak of 

the roof is 10' (3 m) or less, the top of the chimney must 

be at least 2' (609 mm) above the peak of the roof, but 

never less than 3' (914 mm) in height above the highest 

point where it passes through the roof.

2. If a horizontal distance from the chimney to the peak of 

the roof is more than 10' (3 m), a chimney height refer-

ence point is established that is on the surface of the roof 

a distance of 10' (3 m) from the chimney in a horizontal 

plane. The top of the chimney must be at least 2' (609 

mm) above the reference point, but never less than 3' 

(914  mm)  in  height  above  the  highest  point  where  it 

passes through the roof.

In planning a chimney system, it is important to know:
1.  The height of a chimney is measured from the hearth 

to the exit point on the termination.

2.  A chimney cannot be offset more than 30° from a vertical 

plane.

3.  A chimney may run straight up or it may be necessary 

to offset it to avoid obstructions.

4.  The maximum length of an angled run (total chimney 

system) is 20' (6 m).  

5.  No more than 2 offsets (4 total 30° elbows in U.S./or 

2  total  45°  elbows  in  Canada)  per  fireplace  may  be 

used.

6.  A  guy  wire  stabilizer  (not  provided)  is  required  for 

chimneys extending more than 6' (1.8 m) above a roof 

line.

L1

L1

LT

MODEL SK

2 WALL 

CHIMNEY

TOTAL

LENGTH 

(LT)

INSTALLED

LENGTH 

(L1)

SK81

SK818

SK83

SK84

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

FP288A

MBUF-INSTALLED LENGTH

Triple wall

1/28/99   djt

TRIPLE

WALL

81

818

83

84

FP288A

Fig. 5 

 Installed lengths of chimney sections.

2' Min.

2' Min.

3'

Min.

0 To 10'

3'

Min.

0 To 10'

AC246

4/1/96

Reference

Point

AC246

Fig. 6 

  Ten Foot Rule illustration.

Содержание Royal Collection WMC36

Страница 1: ...se in U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 20000583 1 13 Rev 31 FP583A WMC 12 18 98 WMC Series Woodburning Fireplaces Homeowner s Installation and Operating Manual ...

Страница 2: ...t part not manufactured or approved by Vermont Cast ings Group in combination or assembly with a Vermont Castings Group fireplace system not withstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a fire hazard Consult local building codes to ensure that you are in compliance before installing the firepla...

Страница 3: ...ia 203mm 3 6 9 1 4 m m Fig 2 WMC42 Series specifications and framing FP592A WMC42 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt B 1 6 m m Z x 13mm Z x 36 914mm 35Z v 895mm 40 1016mm B 16mm 19C v 502mm 1C v 45mm 35Z x 902mm 21 7C v 197mm 7Z x 191mm Recessed Nailing Flange 11 Dia 279mm Rough Opening Width 41 Rough Opening Height Rough Opening Depth Gas Line Access 47 ...

Страница 4: ...d Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both sides Nailing Flange Standoff Batt Insulation cut out around firestop Firestop Ceiling Level A B C FP1531 hearth dimensions 9 04 djt Front Width Back Width Depth A B C WMC36 33Z x 20Z v 18Z v 851 mm 514 mm 4...

Страница 5: ... 1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0 1 2 1 68 124 0 1 2 1 1 70 128 0 0 0 3 1 74 134 0 1 1 2 2 78 140 0 0 3 1 2 81 146 0 1 0 3 2 84 151 0 0 2 2 2 87 156 0 1 3 1 2 89 160 0 0 1 3 2 93 166 0 1 2 2 2 95 170 0 0 0 4 2 99 177 0 1 1 3 2 101 18...

Страница 6: ...t 2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak of the roof is more than 10 3 m a chimney height refer ence point is established that is on the surface of the roof a distance of 10 3 m from the chimney in a horizontal plane The top of the chimney must be at ...

Страница 7: ...mates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncombustible insula tion rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If fireplace is installed on a platform insulation should b...

Страница 8: ...uctions Read all instructions before beginning installation Follow instruc tions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V switch described in the fan or fireplace installation instruc tions Installation Instructions For mounting the speed control a 2 deep standard electri cal box should be used Using wire nuts supplied ...

Страница 9: ...t Castings Group elbows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to install the second elbow in each offset as close to the ceiling or support as possible so the elbow straps can be secured to framing members to help support the weight of the chimney ...

Страница 10: ...installing firestop spacer Size of Chimney Vertical 30 8 Flue SKFS2A SKFS6A SK Series 14 x 14 14 x 25 368mm x 368mm 368mm x 648mm 8 Flue FS2A FS6A S Series 3 Wall 17 x 17 17 x 29 445mm x 445mm 454mm x 753mm Angle of Chimney at Ceiling The inside dimension of the frame must be the same as the hole size selected from Figure 13 in order to provide required air space between the outside diameter of th...

Страница 11: ... collar on top of the fireplace Install the pipe as pictured in Figure 17 When you get a good lock you will hear the pipe clearly snap together Once sections are snap locked in place it is extremely difficult to get them apart Make sure the pipe is firmly snapped and locked together as each pipe section is mounted When installing elbows only outer pipe will snap lock Middle pipes simply slide into...

Страница 12: ...ld with the flanges on its base extending down into the framing hole Nail each corner of attic insulation shield to the framing members of the ceil ing hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run Continue attaching pipe sections to complete system to next level always being careful that the pipe is firmly snapped locked in place before pr...

Страница 13: ...ing Top Housing or Termination Follow the installation instructions provided with the chim ney termination you have selected Installing Chimney In a Chase Refer to Page 4 Figure 3 for an illustration of a typical chase installation CAUTION Treatment of firestop spacers and construc tion of chase may vary with type of building These instructions are not a substitute for local building codes You mus...

Страница 14: ...otected with a specifically built wall shield as described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls Rt must 1 85 minimum FP531b Fig 22 Mantel clearance FP531b mantel clearances 9 03 djt Z x 12 305mm Max 12 305mm Min 1Z x 38mm 6 159mm Min Combustible Mantel and Trim Finished Wall Header Standoff Noncombustible Material Gri...

Страница 15: ...d from manufacturer of the material Factors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is sufficiently greater to maintain an equivalent total thermal resistance Rt Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Non...

Страница 16: ...doffs Safety Strips Must be overlapped Z x minimum Hearth Extension Insulation Side View FP550 Fig 26 Sealing gaps How to Operate Your Fireplace Your fireplace can provide countless hours of pleasure and security However use your fireplace carefully because any time you build a fire inside a house a problem may develop Open Flue Damper The flue damper is meant to be closed only when the fire is co...

Страница 17: ...to totally seal between the pipe and tube Note Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from fireplace side NOTE When installing an ANSI Z21 11 2 ventless appli ance the finishing materials used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in fireplace should be rated less than 100 ...

Страница 18: ...replace 26D0131 26D0131 5 Damper Knob Wood 7536177 7536177 6 Firebrick Left Side 3041104 3034102 7 Firebrick Back 3030102 3034104 8 Firebrick Right Side 3041105 3034103 9 Firebrick Hearth 3041103 3034105 10 Screen Rod two per fireplace 26D0138 61D0500 11 Top Brick Retainers three per fireplace 3030172 3030172 12 Cable Clips four per fireplace 7512135 7512135 13 O S A Assy 20003076 20003076 14a Doo...

Страница 19: ...se an unapproved component to make any modifications you may create a possible fire hazard and will void the Vermont Castings Group warranty In ad dition such action may void the coverage provided by the owner s insurance Accessories Contact your Vermont Castings Group distributor or dealer for finishing Mantels available in a wide selection of styles Glass Door Optional Bi Fold door set Pewter fi...

Страница 20: ...le chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Includes adapter Flashing not included SK8 Chimney Sections Pipe used to build 8 SK8 flue systems SK81 1 Long SK818 1 Long SK83 3 Long SK84 4 Long SK8 Chimney Elbows Elbow used to create an offset in an ...

Страница 21: ...rom the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclosure Installs on the over the chimney collar of the CCE SK SK8 fireplace provides outside air to assist in cooling the chimney system Attic Insulation Shield Used to prevent insulation from coming i...

Страница 22: ...22 WMC Series Woodburning Fireplace 20000583 ...

Страница 23: ...ure dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local building code Building codes vary greatly throughout the country and you should determine whether your local building code contains restrictions on the use of this fireplace before you purchase it Blo...

Страница 24: ...Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup com ...

Отзывы: