6
WMC Series Woodburning Fireplace
20000583
Planning Information
Preplanning an installation is very important to ensure
safety and to save time and money. An installer must
predetermine where a fireplace will be set and how the
chimney system will be run.
Mounting the Fireplace
A fireplace may be mounted on the following surfaces:
1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed beneath
each of the four (4) corners of the fireplace.
The fireplace
must
be spaced 1/2" (13 mm) from a com-
bustible back wall and 1/2" (13 mm) from a combustible
side wall or support. Refer to Page 14, Figure 18.
Planning the Chimney Run
Determine how the chimney will be run, length of run and
chimney components required to complete the job. (Fig. 4)
Never
install a chimney below minimum heights.
The Ten Foot Rule
Major U.S. building codes specify a minimum chimney
height above the roof top. The “Ten Foot Rule” is a fire
safety rule and not a draft rule. It is recommended that
you always meet or exceed the “Ten Foot Rule,” especially
when installing a termination on a high pitch roof. (Fig.
6)
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the peak of
the roof is 10' (3 m) or less, the top of the chimney must
be at least 2' (609 mm) above the peak of the roof, but
never less than 3' (914 mm) in height above the highest
point where it passes through the roof.
2. If a horizontal distance from the chimney to the peak of
the roof is more than 10' (3 m), a chimney height refer-
ence point is established that is on the surface of the roof
a distance of 10' (3 m) from the chimney in a horizontal
plane. The top of the chimney must be at least 2' (609
mm) above the reference point, but never less than 3'
(914 mm) in height above the highest point where it
passes through the roof.
In planning a chimney system, it is important to know:
1. The height of a chimney is measured from the hearth
to the exit point on the termination.
2. A chimney cannot be offset more than 30° from a vertical
plane.
3. A chimney may run straight up or it may be necessary
to offset it to avoid obstructions.
4. The maximum length of an angled run (total chimney
system) is 20' (6 m).
5. No more than 2 offsets (4 total 30° elbows in U.S./or
2 total 45° elbows in Canada) per fireplace may be
used.
6. A guy wire stabilizer (not provided) is required for
chimneys extending more than 6' (1.8 m) above a roof
line.
L1
L1
LT
MODEL SK
2 WALL
CHIMNEY
TOTAL
LENGTH
(LT)
INSTALLED
LENGTH
(L1)
SK81
SK818
SK83
SK84
56O
"
56O
"
56O
"
56O
"
56O
"
56O
"
56O
"
56O
"
FP288A
MBUF-INSTALLED LENGTH
Triple wall
1/28/99 djt
TRIPLE
WALL
81
818
83
84
FP288A
Fig. 5
Installed lengths of chimney sections.
2' Min.
2' Min.
3'
Min.
0 To 10'
3'
Min.
0 To 10'
AC246
4/1/96
Reference
Point
AC246
Fig. 6
Ten Foot Rule illustration.