background image

11

BFC36 Balanced Flue Heat-Circulating Fireplace

7412647

FPC549a

BFC

Nail flange/standoff

circulating models

8/21/00   djt

Nail Top 

Standoffs

Nail Side-

Nailing 

Flanges

FPC549a

Fig. 12

  Fasten fireplace in position.

Installing the 

Chimney System

Start by attaching the first chimney section to the collar on 

top of the fireplace.

  

Install the pipe as pictured in Figure 13.  When  you get 

a good lock, you will hear the pipe clearly snap together. 

Once  sections  are  snap-locked  in  place,  it  is  extremely 

difficult to get them apart. 

Make sure the pipe is firmly 

snapped and locked together as each pipe section is 

mounted.

UP

FPC558a

BFC

Pipe install

Circulating models

8/21/00   djt

Pipe Section

Pipe 

Rim

Hem

Lance

Pipe 

Hem

FPC558a

Fig. 13

  Install pipe, listening for the snap-lock to fasten.

When  installing  elbows,  only  outer  pipe  will  snap-  lock.  

Middle pipes simply slide into position. Be sure to always 

attach straps on upper elbow to a structural framing mem-

ber. (Fig. 14)
Continue installing the pipe as required until pipe is installed 

up through the ceiling.  At this point, you must install a 

firestop spacer.

FP270/271

CR Series

2/19/99   djt

Support Structure

Ceiling Hole 

Framing

Elbow Strap

(must be tight)

Angled Firestop

Chimney Support Strap

(must be tight)

Elbow Strap

Angled Strap

FP270/271

Fig. 14

  Attach straps to a structural framing member.

Installing the Firestop Spacer 

in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly and 

required for safety.
Nail  the  firestop  spacer  (at  each  corner)  to  the  framing 

members of the ceiling hole. 

NOTE: 

 A firestop spacer is 

not required at the roof.
Hole sizes listed in Figure 10 for angled firestop spacers 

provide minimum required air space to chimney pipe for 

ceiling  thickness  up  to  8”  (203  mm).    When  combined 

thickness  of  ceiling  material,  ceiling  joists  and  flooring 

material exceeds 8” (203 mm), adjustments must be made 

in framing to assure that minimum air spaces to chimney 

are maintained.

Proper Firestop Spacer Installation

Figure 15 shows different installation procedures for  both 

an area that 

is

 an attic and  an area that 

is not

 an attic.

If the area above the ceiling

 is not 

an attic, position the 

firestop spacer with the flange on the ceiling side and the 

angled portion extending up into the hole.
If the area above the ceiling 

is

 an attic, position the firestop 

spacer with the flange on the top of the framed hole and 

the angled portion extending down into the hole.
Firestop spacers are not available for, nor are they required 

on vertical walls.

DO NOT 

put any sealant around the area where the outer 

pipe slides through the firestop spacer.  If you seal this 

area,

 it may cause a fire hazard.

Содержание Majestic BFC36

Страница 1: ...e Closed Combustion Heat Circulating Fireplace Model BFC36 For use in the U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 7412647 1 13 Rev 21 Homeowner s Installation and Operating Manual ...

Страница 2: ...ty Information 3 Specifications and Framing 4 Parts Identification 5 Chimney Requirements 6 Planning Information 7 Installation 8 Replacement Parts 18 Accessories 20 Warranty 23 Table of Contents BFC36 Listed UL127 ULC S610 Standard for Factory Built Fireplaces ...

Страница 3: ...replace or chimney component Modification of fireplace chimney assembly or any component parts thereof except for chase flashings as detailed in Vermont Castings Group Chimney Top installation instructions Installation other than as instructed by Vermont Castings Group or Installation and or use of any component part not manufactured or approved by Vermont Cast ings Group in combination or assembl...

Страница 4: ...FC36 specs 8 18 00 djt 1356O Dia 343mm Rough Opening Width 43 Rough Opening Height Rough Opening Depth Gas Line Access 5156QE 1297mm 5156QE 1297mm 6 Q E 1 8 3 4 m m 6M 197mm 23 584mm 610mm 6QE 624mm 3956M 997mm 556QE 246mm 35 889mm 279mm Gas Line Access 56O 902mm 36 914mm 1092mm 11 Dia 179mm 8 Dia 203mm 5 6 9 1 8 m m A B C FP1531 hearth dimensions 9 04 djt Front Width Back Width Depth A B C BFC36 ...

Страница 5: ...tstop Standoff Surround Trim Ledge Standoff Glass Door Romex Pigtail Gas Line Access Knock out Each Side Air Inlet Basket Grate Bottom Grille Metal Safety Strip s Shown not inplace 1 2 or 3 pieces Nailing Flange Top Grille and Air Outlet Gas Line Ac cess Hole Each Side Ceiling Level Firestop Batt Insulation Cut out around firestop FP554c Fig 2 Fireplace and chase parts identification ...

Страница 6: ...et of angled run of chimney Chimney supports are required for every 30 feet and 60 feet of vertical chimney height above the hearth Determine the offset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling Note This offset distance may not be your full offset distance See Examples 2 and 3 Fig 3 Chim...

Страница 7: ...ed the Ten Foot Rule especially when installing a termination on a high pitch roof Fig 5 The key points of the Ten Foot Rule are 1 If the horizontal distance from the chimney to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where it passes through the roof 2 If a horizon...

Страница 8: ... concrete slab If fireplace is installed on a platform insulation should be placed on top of the platform before fireplace is set Fig 7 When a fireplace is installed in a chase or on a outside wall enclosure should be treated like any outside wall in a home Insulation should be installed on the inside wall as well as the outside wall s In a chase it is also a good idea to install a firestop at the...

Страница 9: ...REPORT TO YOUR DEALERS ANY PARTS DAMAGED IN SHIPMENT SPECIFICALLY CHECK THE END CONNECTION OF CHIMNEY SECTIONS AND ELBOWS Note The BFC36 fireplace must use Vermont Castings Group Model triple wall 8 chimney components only The installation procedure described in this manual applies only to this system Straight Up Chimney Installation To mark the centerline of the flue put the fireplace in final po...

Страница 10: ...mney Vertical 30 FS2A FS6A 8 Flue 17 x 17 17 x 29 445 x 445mm 454 x 753mm The inside dimension of the frame must be the same as the hole size selected from Figure 10 in order to provide required the 2 51 mm air space between the outside diameter of the chimney and the edges of the framed ceiling hole Positioning Safety Strips Securing the Fireplace Slide fireplace into position Lift the fireplace ...

Страница 11: ...t Strap must be tight Elbow Strap Angled Strap FP270 271 Fig 14 Attach straps to a structural framing member Installing the Firestop Spacer in the Ceiling Hole A firestop spacer is used to keep pipe spaced properly and required for safety Nail the firestop spacer at each corner to the framing members of the ceiling hole Note A firestop spacer is not required at the roof Hole sizes listed in Figure...

Страница 12: ... you must use an approved Vermont Castings Group termination If a chase is used refer to the installation manual provided with the termination cap Locate Chimney Centerpoint On Roof Use same procedure detailed in locating center point of the flue system Drive a nail up through roof at the center point This will determine center point on outside of the roof Cut and Frame Roof Hole Size of roof hole...

Страница 13: ...e rafters Install the frame securely because the chimney top and flashing anchored to the frame must be able to withstand heavy winds Install Remainder of Chimney Sections Since you have already preplanned the height of your termination according to the Ten Foot Rule continue to install pipe to the predetermined height Check the chimney top installation instructions for details on how high above t...

Страница 14: ...antel clearances 12 from top of grille opening 6 from top of grille opening Face Plate FP531b mantel clearances 9 03 djt Z x 12 305mm Max 12 305mm Min 1Z x 38mm 6 159mm Min Fig 18 Mantel clearance Combustible Mantel Shelf and Trim Finished Wall Stud Standoff Circulating Front Noncombustible Material Fireplace Opening 2 x 4 Stud Finished Wall Must be sealed with noncom bustible material Fireplace F...

Страница 15: ...nt shift ing using trim molding or other similar means at three 3 outer edges Seal crack between the fireplace hearth and hearth extension with a non combustible material Figs 20 and 22 WARNING Hearth extension must be installed in ac Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Noncombustible Surround Facing Minimum Hearth Extension Dimensions for On Site Construction G H G...

Страница 16: ... IN Thickness of Listed Material FP533ADD Addendum 6 1 99 djt 8 4 99 changed 2 to 1 one inch to 1 2 inch djt FP533ADD Fig 21 Hearth extension material factors Example of Determining Hearth Extension Equiva lents To determine the thickness required for any new mate rial NEW K of new material per inch thickness required X of listed thickness K of listed material per inch material Example for Common ...

Страница 17: ...tion of the fireplace If the baffle is out of place the resulting improper air flow will cause dirty glass and improper combustion The baffle should be centered side to side between the refractory sidewalls and be pulled for ward toward the glass doors until it rests on the front sheet metal ledge Refer to the publication How to Enjoy Your Woodburning Fireplace for starting and maintaining a wood ...

Страница 18: ...scription BFC36 1 Top Grille Painted 3126160 2 Bottom Grille Painted 3126160 3 Grate Assembly 7579218 4 Left Door Assembly Complete 30004361 5 Right Door Assembly Complete 30004362 6 Rear Firebrick 2353145 7 Side Firebrick two per fireplace 2353146 8 Hearth Firebrick 2353140 9 Nailing Flange four per fireplace 2422198 10 Fiberglas Rope Gasket Outer Collar 7547137 11 Top Refractory 2353147 12 Front...

Страница 19: ...s Panel two per fireplace 30004352 21 Flat Gasket 3 4 Wide two per fireplace 20013997 22 Knob two per fireplace 1600657 23 Bushing four per fireplace 1201895 24 Pan Hd PH 1 4 20 x 1 Black two per fireplace 1200907 25 Spacer two per fireplace 1600070 26 Spring Clip 30004450 27 8 18 x 1 2 Decorative Screw 7521180 28 Hinge Spacer two per fireplace 30004360 29 BFC Door Assembly 20014006 Ref Descriptio...

Страница 20: ...with Vermont Castings Group approved components If you use an unapproved component to make any modifications you may create a possible fire hazard and will void the Vermont Castings Group warranty In addition such action may void the coverage provided by the owner s insurance Accessories Hearth Extension Insulation Provides hearth extension floor protection EH2416 Grate for BR BC36 42 Holds firewo...

Страница 21: ...ing is not included TT200C Adapter Kit TT8CB is required Chase Top Housing Used with chase terminations to prevent rain entry FL88 8 flue Contemporary Flashing 8 6 12 with 8 flue Required for Contemporary Round Top 0 to 6 12 pitch termination to prevent rain entry 8 12 12 with 8 flue 6 12 to 12 12 pitch Chimney Sections 8 flue 81 1 long Used to build chimney systems 818 1 long 83 3 long 84 4 long ...

Страница 22: ...22 BFC36 Balanced Flue Heat Circulating Fireplace 7412647 ...

Страница 23: ...r pressure dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local building code Building codes vary greatly throughout the country and you should determine whether your local building code contains restrictions on the use of this fireplace before you purchase...

Страница 24: ...24 BFC36 Balanced Flue Heat Circulating Fireplace 7412647 Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www Vermont Castings Group com ...

Отзывы: