background image

18

Vermont Castings EWF36A

20005167

Operation

Attach Handles

The fallaway handles are used to open and close the 
front doors. Remove after each use so they will not get 
hot. Keep in convenient location for each use. (Fig. 27)
Assemble the primary air control and damper handles 
by passing the 3

³⁄₈

” screw through the ceramic shaft 

and into the bright metal hub. Tighten carefully until 
snug. Do not overtighten. Ceramic handle could crack. 
(Fig. 28) 

5167

EPA36

cover

3/02

FP1397

Fig. 27

  Insert fallaway handles into door handle stubs.

Steel Handle

Fallaway Handle

EWF36A Controls 

Three controls regulate the performance of the 
EWF36A fireplace:  A primary air control supplies oxy-
gen for the fire, the damper directs air flow within the 
fireplace and a variable-speed fan control, or rheostat, 
regulates the warm air flow into the room. (Fig. 29)

Primary Air Control

A single air control regulates the amount of heat the fire 
will produce and how long it will burn.

FP1396
EWF handles
8/14/03   djt

FP1396

Fig. 28

  Assemble primary air control and damper handles.

Screw

Ceramic Shaft

Metal Hub

The 

primary air control

 is located in the upper left 

corner of the unit.  (Fig. 27) It is the primary source of 
air for starting, maintaining, and reviving the fire.
Generally, more air entering the fireplace makes the fire 
burn hotter and faster, while less air prolongs the burn.
The air supply is open to the maximum when the control 
lever is rotated clockwise, and closed when rotated 
counterclockwise. To vary the burn rate, adjust the con-
trol to the desired position in between these extremes; 
opening the primary air control makes the unit burn 
hotter. Closing the control slows the unit down. You may 
adjust to any position you desire.

The Damper

The damper directs air flow within the fireplace.

The 

damper

 is operated by moving the lever located 

in the upper right corner of the unit. It has two posi-
tions: Open to start or revive the fire and closed, for 
normal operation and to control burn rate. The damper 
is open when the lever is fully rotated counterclockwise 
and pulled out and closed when pushed in. When the 
damper is in the open position, with the lever pulled out, 
and rotated fully in the clockwise direction, the handle 
can ‘telescope’ back without closing the damper or any 
damper movement. There are no intermediate settings 
for the damper.

NOTE:

 Full clockwise or counterclockwise movement of 

the damper handle is approximately 50°.

NOTE:

 Always open the damper before opening the 

doors. Close damper to set burn rate.

FP1204
EPA36
controls
3/20/02   djt

Primary Air Control

FP1203

Fig. 29 

 EWF36A controls.

Damper

Содержание EWF36

Страница 1: ...TY NOTICE IF THIS APPLIANCE IS NOT PROPERLY INSTALLED OPERATED AND MAIN TAINED A HOUSE FIRE MAY RESULT TO REDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH CONTACT LOCAL BUILDING OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA ...

Страница 2: ...mplete details on the EWF36A performance and specifications please refer to Page 3 The EWF36A is designed tested and listed for burning wood Do not burn other fuels Installation or service of this woodburning firep should only be completed by a qualified installer preferably NFI or WETT Canada certified Please read the appropriate sections of this manual before you install and use your EWF36A For info...

Страница 3: ...ings as detailed in CFM Corporation Chimney Top installation instructions Installation other than as instructed by CFM Corporation or Installation and or use of any component part not manufactured or approved by CFM Corpo ration in combination or assembly with a CFM Corporation fireplace system notwithstand ing any independent testing laboratory or other third party approval of such component parts...

Страница 4: ...nditions and on average efficiencies These values are based on operation in building code conforming homes under typical winter climate conditions If your home is of nonstandard construction e g unusually well insulated not insulated built under ground etc or if you live in a more severe or more temperate climate these figures may not apply Since so many variables affect performance consult your Ver...

Страница 5: ...00 djt Chase Installation Insulation methods shown are optional for cold climate not a requirement for unit operation Termination Cap Storm Collar Pan Flashing Draftstop Batt Insulation cut out around fire stop Firestop Ceiling Level Standoff Metal Safety Strips 1 2 or 3 pieces Batt Insula tion MUST be used in the Chase Outside Air Cover Plate Andiron Brick Ledge ...

Страница 6: ... of angled run of chimney Chimney supports are required for every 30 feet and 60 feet of vertical chimney height above the hearth Determine the offset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling NOTE This offset distance may not be your full offset distance See Examples 2 and 3 Fig 3 Chimney ...

Страница 7: ...of is more than 10 3m a chimney height reference point is established that is on the surface of the roof a distance of 10 3m from the chimney in a horizontal plane The top of the chimney must be at least 2 610mm above the reference point but never less than 3 914mm in height above the high est point where it passes through the roof 2 Min 2 Min 3 Min 0 To 10 3 Min 0 To 10 AC246 4 1 96 Reference Poi...

Страница 8: ... assistance Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncombustible insulation rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If firep...

Страница 9: ...arts damaged in shipment specifically check the end connection of chimney sections and elbows NOTE The EWF36A fireplace must use CFM Corpora tion model triple wall 8 chimney components only The installation procedure described in this manual applies only to this system Straight Up Chimney Installation To mark the centerline of the flue put the fireplace in final position and measure out from the wall 9...

Страница 10: ...ty Strips Securing the Fireplace Slide fireplace into position Safety strips are used to ensure that any combustible materials in front of the fireplace are protected even though a noncombustible hearth extension is required When the finished extended hearth is added the top of the finished hearth must be flush with the bottom of the fireplace Z shaped metal safety strips have been supplied with the fire...

Страница 11: ...ctice to protect your hands and eyes during installation by wearing work gloves and safety glasses CAUTION Do not install termination into a garage or other area that could contain flammable liquids or fumes or into an attic space Installation Instructions Determine the location of the fireplace as described in the fireplace Installation Manual Then plan location of the duct termination and the route...

Страница 12: ...ide of the unit Fig 14 3 Attach the air duct assemblies to the inside panel with four 4 screws removed in Step 1 fig 14 FP1061 AKMST rain cap Caulking Wall Duct Termination Rain Cap FP1061 Fig 15 Caulk and install duct termination rain cap in place UP FP1198 EPA Pipe install Circulating models 3 20 02 djt Pipe Section Pipe Rim Hem Lance Pipe Hem FP1198 Fig 16 Install pipe listening for the snap loc...

Страница 13: ...ions Canadian Requirements for Insulation Shield In Canada an attic insulation shield is required to prevent attic insulaiton from contacxting the chimney section NOTE If the attic insulation shield is used the firestop is not required in the attic installation Framing dimensions fr the chimney hole should measure 17 x 17 445 x 445 mm An attic shield MUST be installed on top of attic joists above t...

Страница 14: ...Install the frame securely because the chimney top and flash ing anchored to the frame must be able to withstand heavy winds Install Remainder of Chimney Sections Since you have already preplanned the height of your termination according to the Ten Foot Rule continue to install pipe to the predetermined height Check the chimney top installation instructions for details on how high above the roof to...

Страница 15: ...mbustible mantel is fitted above the fireplace is dependent on the depth of the mantel This also applies to the distance between the mantel leg if fitted and the fireplace For the correct mounting heights and widths refer to Figures 22 and 23 When using paint or lacquer to finish the mantel such paint or lacquer must be heat resistant to prevent discoloration FP1398 Fig 22 Combustible mantel minimum op...

Страница 16: ... Rt value of the alternate material employed is greater than or equal to R 1 09 Thermal resistance R or thermal conductivity K may be obtained from manufacturer of the material Factors are related by the formula K 1 R Fig 24 T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material i...

Страница 17: ...nce to combustible perpendicular wall B Min clearance to combustible perpendicular wall when using noncombustible wall shield Side Wall Side Wall F C E E D 4 Brick Example material Combustible material permitted within shaded area Noncombustible wall shield requires 1 EH2416 insulation minimum R Value 1 85 between decorative noncombustible rigid covering and combustible wall Minimum height and wid...

Страница 18: ...ting maintaining and reviving the fire Generally more air entering the fireplace makes the fire burn hotter and faster while less air prolongs the burn The air supply is open to the maximum when the control lever is rotated clockwise and closed when rotated counterclockwise To vary the burn rate adjust the con trol to the desired position in between these extremes opening the primary air control make...

Страница 19: ...ontrol Settings that Work Best for You No single air control setting will fit every situation Each installation will differ depending on the quality of the fuel the amount of heat desired and how long you wish the fire to burn The control setting also depends on your particular installation s draft or the force that moves air from the stove up through the chimney Draft is affected by such things as ...

Страница 20: ... light the main bed of fuel until the chimney begins drawing and repeat the procedure as often as necessary if the initial attempt is unsuccessful 5 Once a good ember bed of at least 2 3 51 76 mm has formed let the fire burn hot for an additional ten to fifteen minutes 6 Close the damper and the primary air control to a medium low setting as described on Page 18 The fire volume will diminish immediat...

Страница 21: ...t too far before the cover engages the slot Ash may contain hot coals and must be treated with extreme care Hold the covered ash pan with both hands to avoid dropping or spilling the ashes Take the pans outdoors and empty the ash into an ash container Before replacing the ash pan clear away any ash that has spilled over the sides and back of the pan Replace the ash pans and front door Empty the as...

Страница 22: ...llen wrench 3 Retighten the lock nut while at the same time hold ing the striker screw with the Allen wrench to prevent its turning Test the door seal Close the door on a dollar bill and attempt to pull it free If the bill is freed with little resis Maintenance ST531 Door Pawl 11 00 Pawl Small Lock ing Nut Large Locking Nut Set Screw Striker Screw Handle Stub ST531 Fig 31 Turn the striker screw to...

Страница 23: ...lace and out of the retaining brackets 4 Check the combustor s honeycomb like element for a buildup of fly ash If any is evident take the combustor outside and clean it by blowing air gently through it Do not push anything through the honey comb do not use compressed air to clear the pas FP1324 Catalyst 2 27 03 djt Wedge In Place Wedge Catalyst Catalyst As sembly FP1324 Fig 32 Carefully tap out the...

Страница 24: ...he glass is firmly seated against the gasket Replace door The Chimney System A Clean Chimney System is Safer and Works Better Although the combustion system in the EWF36A can re duce creosote formation dramatically it is not a substi tute for regular inspection and cleaning of the chimney and chimney connector Learn to Recognize and Avoid Creosote The EWF36A has been designed to reduce creosote bui...

Страница 25: ...cleaning the chimney reinstall the chimney cap according to the manufacturer s directions Maintenance Schedule Fireplace Daily Ash should be removed before the level reaches the top of the pan Check each time you re load or at least once a day Keep the area around the fireplace clear of any com bustible material Yearly Spring Cleaning Remove ash from the fire box and replace with a moisture absorbin...

Страница 26: ...nsion Extends Traditional Top Housing on 202036 steep pitched roofs single flue Contemporary Chase Top Used to terminate chimney at the top of a SLTS8 Termination chase Flashing is not included Contemporary Flashing 8 6 12 with 8 flue Required for Contemporary Round Top 0 to 6 12 pitch termination to prevent rain entry 8 12 12 with 8 flue 6 12 to 12 12 pitch Chimney Sections 8 flue 81 1 long Used to b...

Страница 27: ...mper rod Clamp 20005985 5 CS Hex hd 3 8 16 x 1 Full Thd 1201443 6 375 Washer 20005980 7 Damper Clamp 20005990 9 Damper Link Assy 20006057 10 Right Hinge Painted 20006302 11 Left Hinge Painted 20006303 Ref Description EWF36A 12 Left Door Assy 20005212 13 Pin Hinge 1201836 14 Left Door Handle Assy Vert Nickel 5004265 15 Gasket 5 16 Adhesive Backed 1203591 16 Glass Clip 30001716 17 Pan Hd PH 1 4 20 x...

Страница 28: ...FP Front 20005160 52 Lattice EPA FP Front 20005162 53 Door Rt EPA FP Front 20004742 54 Door Lt EPA FP Front 20004741 EWF36A Fireplace continued Ref Description EWF36A Ref Description EWF36A 55 Air Wash Rt Painted 20006296 56 Air Wash Lt Painted 20006297 57 Basic Upper Rt not shown 20006024 58 Basic Upper Lt not shown 20006025 59 Basic Lower Rt not shown 20006026 60 Basic Lower Lt not shown 2000602...

Страница 29: ...t ZA1200 was cor rectly connected when the unit was installed the fan lead can be directly plugged into the EB 1 plug socket The fireplace when installed must be electrically connected and grounded in ac cordance with local codes with the current CSA C22 1 Canadian Electrical Code or for US installations follow local codes and the National Electrical Code ANSI NFPA No 70 Any electrical rewiring of ...

Страница 30: ...30 Vermont Castings EWF36A 20005167 ...

Страница 31: ...oduct must be installed or serviced by a qualified installer preferably NFI or WETT Canada certified as prescribed by the local jurisdiction It must be installed and operated at all times in accordance with the Installation and Operating instructions furnished with the product Any alteration willful abuse accident or misuse of the product shall nullify this warranty 2 This warranty is transferable h...

Страница 32: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Отзывы: