16
Encore
®
FlexBurn
®
2040 Non-Catalytic / Catalytic Wood Burning Stove
30005295
Mobile Home Installation
You must use an Vermont Castings Group Vermont Cast-
ings Kit #0336 for installation into a mobile home.
1. An outside air inlet must be provided for combustion
and must remain clear of leaves, debris, ice and/or
snow. It must be unrestricted while stove is in use to
prevent room air starvation which can cause smoke
spillage and an inability to maintain a fire. Smoke
spillage can also set off smoke alarms.
2. Stove must be secured to the mobile home structure
using the fasteners provided in the Mobile Home Kit.
3. Stove must be grounded with #8 solid copper ground-
ing wire or equivalent and terminated at each end with
N.E.C. approved grounding device.
4. Stove must be installed with an approved UL103 HT
ventilated chimney connector, UL103 HT chimney and
terminal cap with spark arrestor. Never use a single
wall connector (stove pipe) in a mobile home installa-
tion. Use only double-wall connector pipe, Dura-Vent
DVL, Selkirk metalbestos DS, Security DL double wall
connector or any listed double wall pipe connector.
5. Refer to the clearance charts in this manual or the
serial number label on the back of the stove for clear-
ances to combustibles.
6. Floor protection requirements on Page 9 must be fol-
lowed precisely.
7. In Canada, this appliance must be connected to a 6
inch (152 mm) factory-built chimney conforming to
CAN/ULC 629M, STANDARD FOR FACTORY BUILT
CHIMNEYS. Floor protection referenced on Page 10
must be followed.
8. Use silicone to create an effective vapor barrier at the
location where the chimney or other component pen-
etrates to the exterior of the structure.
9. Follow the chimney and chimney connector manufac-
turer’s instructions when installing the flue system for
use in a mobile home.
NOTE:
Offsets from the vertical, not exceeding 45°, are
allowed per Section 905(a) of the Uniform Mechanical
Code (UMC). Offsets greater than 45° are considered
horizontal and are also allowed, providing the hori-
zontal run does not exceed 75% of the vertical height
of the vent. Construction, clearance and termination
must be in compliance with the UMC Table 9C. This
installation also complies with NFPA 211.
NOTE:
Top sections of the chimney must be removable
to allow maximum clearance of 13.5 ft. (411 cm) from
ground level for transportation purposes.
10. Burn wood only. Other types of fuels may generate
poisonous gases (e.g. carbon monoxide).
11. If unit burns poorly while exhaust blower is on in home,
(i.e. kitchen range hood) increase combustion air.
WARNING: NEVER DRAW COMBUSTIBLE AIR
FROM A WALL, FLOOR OR CEILING CAVITY OR
FORM ANY ENCLOSED SPACE SUCH AS AN ATTIC
OR GARAGE.
CAUTION: THE STRUCTURAL INTEGRITY OF
THE MOBILE HOME FLOOR, WALL AND CEILING/
ROOF MUST BE MAINTAINED. (i.e., DO NOT CUT
THROUGH FLOOR JOIST, WALL STUD, CEILING
TRUSS, etc.).
WARNING:
DO NOT INSTALL IN SLEEPING ROOM
ST1190
mobile home install
Spark
Arrestor
Cap
Roof
Flashing
Storm Collar
Joint
Shield/
Firestop
Listed Chimney
Connector
Floor
Protection
Outside Air Kit
Connector
Outside Air Floor Vent
KT1190
Fig. 18
Mobile home installation.