Vermont Castings Dutchwest 2478 Скачать руководство пользователя страница 10

10

Dutchwest Non-Catalytic Convection Heater

30002278

Procedure:

1.  Convert specifications to R-value:

i.  R-value given - no conversion needed.
ii.  k-factor is given with a required thickness (T) in 

inches:  

iii. K-factor is given with a required thickness (T) in 

inches:

iv. r-factor is given with a required thickness (T) in 

inches:  R = r x T 

2.  Determine the R-value of the proposed alternate 

floor protector:
i.  Use the formula in Step 1 to convert values not 

expressed as R.

ii.  For multiple layers, add R-values of each layer to 

determine overall R-value.

3.  If the overall R-value of the system is greater than 

the R-value of the specified floor protector, the alter-
nate is acceptable.

EXAMPLE:

 The specified floor protector should be 5/8-

inch thick material with k-factor of 0.84. The proposed 
alternate is 4” brick with an r-factor of 0.2 over 1/8” 
mineral board with a k-factor of 0.29
Step a: Use formula above to convert specification to 

R-value:

Step b: Calculate R of proposed system. 
  4” brick of r = 0.2, therefore:
   R

brick

 = 0.2 x 4 = 0.8

  1/8” mineral board of k = 0.29, therefore
   R

mineralboard

 =         x 0.125 = 0.431 

   R

total

 = R

brick

 + R

mineralboard

 = 0.8 + 0.431 = 1.231

Step c: Compare proposed system Rtotal of 1.231 to 

specified R of 0.744. Since proposed system Rtotal 
is greater than required, the system is acceptable.

Definitions

To install the heater without legs as a fireplace insert, 
the floor must be completely noncombustible, such as 
an unpainted concrete floor over earth.
Many fireplaces do not satisfy the “completely non-
combustible” requirement because the brick or con-
crete hearth in front of the fireplace opening usually is 
supported by heavy wooden framing as in Figure 13.  
Because heat passes readily through brick or concrete, 
it can easily pass through to the wood. As a result, such 
fireplace hearths are considered a combustible floor. 
You may not install a heater on a combustible hearth 
without legs. Standard leg installations must include the 
bottom heat shield.  The  floor protector must also meet 
standard requirements for freestanding installations.

Floor Protection for Fireplace 

Installations with Standard Legs 

Fireplace installations with the standard legs and the 
bottom heat shield must have a floor protector of the 
same construction as that specified for freestanding 
installations: use an approved 5/8” (16mm) noncom-
bustible hearth pad with K = 0.84 BTU/in ft

2

 hr °F or an 

equivalent material with an R-value of at least 0.744 
(that may be covered with a decorative noncombustible 
material if you desire).  (Refer to “How to Determine if 
Alternate Floor Protection Materials are Acceptable” 
section) The floor protector must extend at least 16” 
(406 mm) [18” / 457 mm in Canada] from the front of 
the stove and from the left (loading door) side, and at 
least 8” (203 mm) from the right side and rear.  It must 
also provide protection beneath any horizontal runs of 
the chimney connector, including 2” to either side.
Many raised hearths will extend less than the required 
distance from the front of the heater when it is installed.  
In such cases, sufficient floor protection, as described 
above, must be added to extend the hearth 16” (406 
mm) [18” (457 mm) in Canada].
Hearth rugs do not satisfy the requirements for floor 
protection.  
Fireplace insert installations also have specific clear-
ance requirements to the side walls, side decorative 
trim, and fireplace mantel.  This information is found in 
“Fireplace Installation Clearances” in this section. 

REMINDER- FIREPLACE INSERT INSTALLATIONS 
WITHOUT LEGS ARE PERMISSIBLE ONLY IF THE 
HEARTH IS COMPLETELY NONCOMBUSTIBLE, 
SUCH AS UNPAINTED CONCRETE OVER EARTH.

R =             x T

1

K x 12

R =    x T  =          x 0.625 = 0.744

1

k

1

0.84

1

0.29

(Btu)(ft)

(ft

2

)(hr)(°F)

 

K =                

 

k =                   = K x 12

(Btu)(in)

(ft

2

)(hr)(°F)

 

R = 

(ft

2

)(hr)(°F)

Btu

Fireplace Installations

The Dutchwest Model 2478 has a reversible flue collar 
to allow for either top exit or rear exit installations.
You may install your Dutchwest Model 2478 in an exist-
ing fireplace as a fireplace insert with no legs, or with 
the standard legs attached.

R =   x T

1

k

(ft

2

)(hr)(°F)

(Btu)(in)

1

k

=

r =

Содержание Dutchwest 2478

Страница 1: ...erating Manual If this heater is not properly installed operated and maintained a house re may result For safety follow all installation operation and maintenance directions Contact local building of...

Страница 2: ...to cause cancer birth de fects and other reproductive harm California Health Safety Code Sec 25249 6 Table of Contents Speci cations 3 Installation 4 Clearances 10 Assembly 16 Operation 18 Maintenanc...

Страница 3: ...in a more severe or more temper ate climate these gures may not apply Since so many variables affect performance consult your Dutchwest Authorized Dealer to determine realistic expectations for your...

Страница 4: ...ed to 1 a chimney complying with the requirements for Type HT chimneys in the standard for Chimneys Fac tory Built Residential Type and Building Heating Appli ance UL 103 or 2 a code approved masonry...

Страница 5: ...nector The chimney connector is the single wall pipe or listed and approved double wall pipe that connects the stove to the chimney The chimney itself is a masonry or prefabricated structure that encl...

Страница 6: ...elescoping joints with at least three sheet metal screws 3 Secure the chimney connector to the chimney In structions for various installations follow below 4 Con rm that the installed stove and chimne...

Страница 7: ...back into the replace chimney The liner of the replace chimney should extend at least to the point at which the chimney connector enters the chimney Follow all the guidelines for installing a chimney...

Страница 8: ...gle wall connector to provide the required 12 305 mm clearance for the connector Any material used to close up the opening must be non combustible The following wall pass through methods may be ap pro...

Страница 9: ...t 0 744 Refer to How to Deter mine if Alternate Floor Protection Materials are Accept able section The oor protector may be covered with a decorative noncombustible material if desired Do not obstruct...

Страница 10: ...installations must include the bottom heat shield The oor protector must also meet standard requirements for freestanding installations Floor Protection for Fireplace Installations with Standard Legs...

Страница 11: ...ombustible surface Keep furnish ings and other combustible materials away from the stove as well In general a distance of 48 1220 mm must be maintained between the stove and moveable combustible items...

Страница 12: ...himney Connector Clearance Chart that follows For example the letter A gives the minimum side clear ance for installations in which the stove is not equipped with any heat shield and the wall beside t...

Страница 13: ...7 heat shield 432 mm 381 mm 191 mm 178 mm 368 mm 178 mm Double wall connector Chimney Connector Clearance Single wall connector 20 14 No connector heat shield 508 mm 356 mm Single wall2 connector 10 6...

Страница 14: ...dutchwest flue centerline 6 30 00 djt A B C E D F C F Chimney Connector Side Rear Corner Side Rear Corner Listed Approved A 30 B 13 C 18 D 21 E 12 F 18 Double wall with 762 mm 330 mm 470 mm 533 mm 318...

Страница 15: ...1220 mm 60 1525 mm Spaced 1 25 mm from Floor ST802 Fig 17 Sidewall protection ST803 corner wall protection 5 04 60 1525 mm 48 1220 mm Spaced 1 25 mm from Floor ST803 Fig 18 Corner wall protection Wall...

Страница 16: ...ottom Heat Shield is required in many instal lations Refer to the oor protection information found in the Installation Section of this manual Attach the Legs and Heat Shield NOTE To avoid damaging the...

Страница 17: ...ssen the effort of moving the stove over smooth ooring is to slide it on a piece of inverted carpet Move it slowly to ensure the oor is not scratched Retighten all leg fastening hardware ST815 back le...

Страница 18: ...Opening the inlet shutters provides air for primary combustion To open the shutters turn the lever clockwise The shutters are all the way open when the lever points to ward the rear at a 9 00 positio...

Страница 19: ...ulting in short burn time and dimin ished stove performance If you must burn it mix it in with greener wood to slow the burn Store your rewood under cover to keep it dry Even for short term storage ke...

Страница 20: ...ase the ring rate of your heater by altering the air control adjustment range outlined in these directions In some newer homes that are well insulated and weather tight poor draft may result from insu...

Страница 21: ...RT THE FIRE DO NOT BURN GARBAGE OR FLAM MABLE FLUIDS SUCH AS GASOLINE NAPTHA OR ENGINE OIL Also never use gasoline type lantern fuel kerosene charcoal lighter uid or similar liquids to start or freshe...

Страница 22: ...ace in a metal container with a tight tting lid ST438 ash pail 7 6 00 djt ST438 ST805 remove ashes 5 04 ST805 Fig 28 Check the ash compartment before reloading the stove Safe Ash Handling Ashes may co...

Страница 23: ...sen the small locking nut with an open end wrench 2 Use the allen wrench included with the stove to turn the striker screw clockwise one quarter turn and close the door to test the engagement The door...

Страница 24: ...o 2 nuts on the threaded rods that secure the top plate to the inner top of the stove 2 Remove the top plate and open the damper 3 Loosen the adjusting bolt s lock nut Fig 32 4 Loosen the anchor bolt...

Страница 25: ...ve cool completely before you inspect the chimney Use a ash light and mirror to sight up the ue through the chimney clean out door or chimney connector inspection tee If no inspection access is availa...

Страница 26: ...or and the elbows Clean the system if nec essary ANNUAL SPRING CLEANING Disassemble the chimney connector and take it outdoors for inspection and cleaning Replace weak sections of connector Inspect th...

Страница 27: ...ure from the high ue temperatures Because the insulation is less dense than masonry the inner steel liner warms up more quickly than a masonry chimney this makes the steel chimney support a good draft...

Страница 28: ...y re All of the installation characteristics that adversely affect chimney draft also promote creosote condensation Consequently you can minimize creosote accumulation with an effective chim ney desig...

Страница 29: ...Conclusion Woodburning is more an art than a science Art in cludes technique and since installations homes and fuel vary the stove operator must also vary technique mostly timing to achieve satisfyin...

Страница 30: ...Convection Heater Model 2478 29 26 27 32 37 21 19 12 38 41 24 25 16 30 37 23 42 39 35 1 14 13 4 43 2 6 9 10 17 11 7 3 34 20 22 18 33 44 45 46 8 47 40 36 47 41 31 28 15 Ref Description 2478 1 Bottom 3...

Страница 31: ...oor Gasket Front Ash and Load Doors 1203589 26 Load Door Insulation 30002210 27 Load Door Refractory to June 2005 30002214 Load Door Refractory II replaces above 30002437 28 Ceramic Handle w Lifter Wo...

Страница 32: ...e to the stove caused by burning salt saturated wood chemically treated wood or any fuel not recommended in the Owners Guide 4 This warranty does not cover a stove repaired by someone other than a Dut...

Отзывы: