18

Stardance Direct Vent/Natural Vent Gas Heater

20007065

9.  Install the storm collar and seal around the joints. 

(Fig. 31)

10. Add additional vent lengths to achieve the proper 

overall height.

11. Apply cement to the inner and outer termination col-

lars and install the terminal cap.

ST222

vent thru ceiling

12/99

#7DVAIS 

Attic Insulation 

Shield

#7DVFS 

Firestop in 

Upper Floor

#7DVFS

Firestop in 

Ceiling

Use Four 

8dNails

ST222

Fig. 30

  Install firestops and attic insulation shield.

ST221

vent thru roof

12/99

Sealant

Storm Collar

Use three #5 sheet 
metal screws at 
each joint

Upper 

edge of 

flange 

goes under 

upper 

shingles

Flashing

#7DVSKV

(A, B, or F)

RoofSupport

ST221

Fig. 31

  Roof support and flashing.

Venting System Assembly - Natural Vent

General Information

The Stardance Heater is shipped from the factory as a 
Direct Vent Heater.  It may be converted to a Natural 
Vent heater by installing the Vermont Castings Model 
Z31D00 FSDHAG Draft Hood Adapter.
The Stardance Heater is approved for installation as 
a Natural Vent. CFM Direct Vent pipe could be used 
directly after the Draft Hood Adapter up to the ceiling, 
then B-vent pipe must be used. Do not mix types of 
B-vent pipe; use components from one maker or the 
other. Follow the vent component maker’s instructions 
exactly. The heater will also accept standard or enam-
elled 7” (178mm) diameter pipe, around the Type B 
venting, for decorative purposes only. (Fig. 32)

NOTE: The restrictor plate supplied with the stove 
is not used for Natural Vent applications.

ST358

Decorative

pipe around b-vent

4/26/00   djt

CFM Direct Vent 

System may be 

used after Draft 

Hood up to the 

ceiling

Decorative 

7” Pipe

4” B-vent 

Pipe

Draft Hood 

Adapter

ST358

Fig. 32

  Decorative 7” pipe may be fitted around the B-vent 

pipe.

The Stardance stove, when installed as a Natural vent 
heater, includes a vent safety switch. (Page 36, Figure 
66) Operating the stove when it is not connected to a 
properly  installed and maintained venting system, or 
tampering with or disconnecting the vent safety switch, 
can result in carbon monoxide (CO) poisoning and pos-
sible death.

For U.S. installations:

 The venting system must con-

form with local codes and/or the current National Fuel 
Gas Code, ANSI Z22.1.

For Canadian installations:

 The venting system must 

conform to the current CSA B149.1 installation code.

Содержание 3900-3916

Страница 1: ...tructions If you cannot reach your gas supplier call the re department DO NOT STORE OR USE GASO LINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE This appliance...

Страница 2: ...Procedures Install the Optional Fan 13 Venting System Assembly Direct Vent 14 Install Vent Adapter Pipe 14 Side Wall Termination Assembly 15 Vent Termination Below Grade 17 Vertical Through the Roof V...

Страница 3: ...e air from the room for combustion and vent the exhaust vertically through the roof to the atmosphere This appliance is approved for bedroom installations in the U S and Canada This appliance may be i...

Страница 4: ...rect Vent Gas Heater This heater may be converted into a Natural Vent unit in the eld If a Natural Vent heater is desired the Vermont Castings Z31D00 FSDHAG Draft Hood must be directly installed to th...

Страница 5: ...ted out of traf c and away from fur niture and draperies The surface of the Heater Is hot when it is in use Young children should be watched carefully when they are in the same room when the Heater is...

Страница 6: ...ue centerline Wall Centerline from Floor ST131b Stardance wall thimble 9 28 00 djt A Direct Vent Only ST131b Effective Minimum Wall Thimble 56 1480 mm CFM Pipe Centerline 52 1378 mm Simpson Duravent...

Страница 7: ...ving jurisdiction In Canada please consult provincial and or local au thorities having jurisdiction for installations at eleva tions above 4 500 feet 1 370m WARNING Improper installation adjustment al...

Страница 8: ...anning the installation consider the location of the vent terminal and clearances Some of the most common clearances to keep in mind are shown in Fig ure 10 Important All vent clearances must be maint...

Страница 9: ...inals shall not be recessed into a wall or siding Horizontal venting must be installed on a level plane without an inclining or declining slope There must not be any obstruction such as bushes garden...

Страница 10: ...nt outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh...

Страница 11: ...Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors G Combustible 6 152 mm Noncombustible 2 51 mm F Combustible 6 15...

Страница 12: ...oal Gray paint Consult your dealer about other vent parts that may be appropriate to complete the installation Min Through the Wall Vent Kit 7TFSSK 1 90 Degree Elbow CG 1 24 Straight pipe CG 1 24 42 A...

Страница 13: ...the rheostat tightening with a wrench Do not over tighten Attach the control knob to the rheostat shaft Use the wire tie to secure the fan and rheostat wire harnesses together ST473 Fan parts 2767 FK2...

Страница 14: ...Inner Starter and secure the assembly with three sheet metal screws Fig 17 3 Dry t the Inner Pipe assembly to the stove for the purpose of determining the center line of the pipe on the wall Side Wall...

Страница 15: ...n Dura Vent install inner adapter pipe ST356 dura vent ST356a Fig 21 Simpson Dura Vent install outer adapter pipe Side Wall Termination Assembly 1 Locate the vent opening on the wall Refer to Fig ure...

Страница 16: ...required if installing a second 90 elbow Fig 25 8 Slip the wall plate and trim collar over the interior end of the horizontal pipe and install into the wall sleeve Seal the joint inside the wall plat...

Страница 17: ...Firestop Wall Screws and Anchors Snorkel Termination Cap Drain Window Well ST218a Fig 28 Snorkel kit installation ST219 snorkel detail 12 6 99 djt Recessed Wall Sheet Metal Screws and Bracket Wall Sc...

Страница 18: ...irectly after the Draft Hood Adapter up to the ceiling then B vent pipe must be used Do not mix types of B vent pipe use components from one maker or the other Follow the vent component maker s instru...

Страница 19: ...nstall the left log by engaging hole on bottom with pin on rear log Fig 34 Then set left bottom side on the burner so the edge of the log touches the left side of the rebox 5 Loosely sprinkle the lava...

Страница 20: ...ith the air shutter adjusted to the minimum allowed opening Refer to Table 1 Based on the altitude where the stove is located a shutter adjustment is acceptable to provide a mixed balance of ame color...

Страница 21: ...ri ces aligned with tubes on the inside of the burner Failure to do so could affect the ame appearance and performance of the unit 10 Refasten the right and left log bracket assembly 11 Refasten the r...

Страница 22: ...rs 2 Connect the thermostat wires to the valve Fig 42 Install the Front Plate Hold the front plate by the window bars and lift it into position engaging the two steel tabs on the top corners behind th...

Страница 23: ...u can open a window to provide fresh air to alleviate the condition Pilot and Burner Inspection Each time you light your heater check that the pilot ame and burner ame patterns are as shown in Figure...

Страница 24: ...these instruc tions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF Y...

Страница 25: ...e thermocouple operates the pilot ame Tighten the thermocouple The thermopile operates the main valve ON and OFF Clean and or adjust pilot for maximum ame impingement on thermocouple and thermopile Tu...

Страница 26: ...he transmitter will now control the main valve ame modulation level and fan control 7 If the manual switch is in the LOCAL position the valve will be at the highest xed pressure setting and the fan wi...

Страница 27: ...er for recognition process to occur between the receiver valve and transmitter 3 Use functions as described in TRANSMITTER sec tion Troubleshooting 1 Locate LED light on valve 2 LED will blink after e...

Страница 28: ...Yes Local Path If manual switch is set to LOCAL did main burner light and fan turn on Move switch from local to remote Press any key on transmitter Move switch back to local Turn pilotstat knob to PI...

Страница 29: ...dis play the room and tempera ture setting Auto Path Move switch from LOCAL to REMOTE Press any key within 30 seconds If the setting is above room temperature on the transmitter does the main valve an...

Страница 30: ...such as a coun ter protected by a towel 4 Remove the logset from the rebox 5 Remove the rear log bracket by unfastening the screw Fig 53 6 Remove the right and left log bracket assembly by unfastening...

Страница 31: ...Pilot 1 28 00 djt Pilot Hood Pilot Bracket CO105a Fig 57 Remove pilot hood CO106a DV360 580 Gas Conversion Pilot2 1 28 00 djt Index Tab Snap Ring CO106a Fig 58 Remove pilot ori ce Allen Wrench Pilot t...

Страница 32: ...to the base Lower the right hand side down in to place Make sure the burner is as far left as possible and the injector shoulders are inside the burner NOTE It is very critical to keep the left burner...

Страница 33: ...painted surfaces looking new Use high temperature stove paints available through your local dealer to touch up areas as needed Clean areas to be painted with a wire brush and be sure to cover the log...

Страница 34: ...ST179 Fig 65 Wrap the gasket material around the outside iedge of the glass Inspect the Vent System Annually Have the vent system inspected annually by a quali ed technician Shut off the main gas supp...

Страница 35: ...uit NOTE IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE SF 2 200 C WIRE OR ITS EQUIVALENT Thermocouple Safety Limit Switch Valve ST665 Safety...

Страница 36: ...4 10a 11 12 13 14 16 15 10b 10c 17 30 27 28 29 36 3 22 23 38 39 40 41 42 48a b 49 CFM Corporation reserves the right to make changes in design materials speci cations prices and discontinue colors and...

Страница 37: ...27 7533113 15 Nut Electrode SIT 0 974 144 57886 16 Tubing Pilot w Fittings 1 8 x 24 10001296 17 Thermopile PSE for RF Pilots 20002400 18 Burner Housing Assembly NG LP 20002214 19 Switch ON OFF RN RP M...

Страница 38: ...ting with 8738 20010645 49 Ignitor Piezo w Nut SIT 52464 50 Bracket Piezo Ignitor not shown 20010876 Fuel Conversion Kits Conversion Kit NG to LP JDV SDV30R Kit 000 5022 Conversion Kit NG to LP SDV30R...

Страница 39: ...OFF and Temperature IMTFK Wall mounted thermostat control Screen Kit An optional screen S30SK for use with the operable doors is available to allow the doors to be left in the open position Warming S...

Страница 40: ...40 Stardance Direct Vent Natural Vent Gas Heater 20007065...

Страница 41: ...41 Stardance Direct Vent Natural Vent Gas Heater 20007065...

Страница 42: ...If upon inspection the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the prov...

Страница 43: ...nstate que les dommages sont la faute du fabricant les r parations les pi ces et la main d uvre seront autoris es sans frais pour le client Toute pi ce et ou tout composant remplac en vertu des dispo...

Страница 44: ...ncy Ratings Model EnerGuide Ratings Fireplace Ef ciency SDV30RN 63 0 SDV30RP 63 0 SDV30RFN 63 0 SDV30RFP 63 0 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corpo...

Отзывы: