Veris DC Current Transducer (CT) Connection Instructions
Page 3 of 3
Configuring the Data Logger for the CT, using HOBOware Pro Software:
HOBOware Pro software provides a configuration file for the CT. The table below lists the recommended configuration values that
this file contains. For information on loading configuration files, refer to the software documentation.
Note:
The CT requires 12-30VDC @ 35mA excitation power for 0-5 volts output option, which can be supplied by the FlexSmart
Analog Module (Onset Part No. S-FS-CVIA) with H22; by the Analog Sensor Port with U30; and by power adapter (Onset Part
No. AC-SENS-1) with ZW, U12, and UX120-006M. For the 4-20mA option, 15-30VDC @ 35mA will need to be provided.
Channel Name
Raw Value 1
Raw Value 2
Scaled Value 1
Scaled Value 2
Scaled Units
Min. Warm-up Time
Current
4mA
20mA
0
50 (or 100 or 200)
A
8-10 sec.
Current
0V
5V
0
50 (or 100 or 200)
A
8-10 sec.