background image

Z203044-0V 

Page 1 of 3 

©2020 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0820 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  Read and understand the instructions before installing this product.

•  Turn off all power supplying equipment before working on it.

•  The installer is responsible for conformance to all applicable codes.

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

Installation Guide

Pressure

Product Identification

Product Overview

The EP2 electropneumatic pressure transducer uses micro-controlled poppet valve technology for highly accurate 
pressure sensing. The poppet valves consume no air, eliminating unnecessary air losses in the system and allowing 
for stable and reliable operation. The EP2 comes installed on standard SnapTrack, and an optional cover is available 
to protect from dust and other environmental factors. An LCD display and LED indicators make it easy to read 
system status at a glance. 

EP2 Series

Electropneumatic Transducer

Specifications

   Power Supply

Class 2, 22 to 30 Vdc, 20 to 30 Vac, 47 to 63 Hz, 150 mA max. 

Control Input

4 to 20 mA, 0 to 10 V, 0 to 5 V; jumper selectable

Input Impedance

4 to 20 mA, 250 Ω; 0 to 5/0 to 10V, 10 kΩ

Manual Override

Jumper selectable mode, digital pushbutton adjust

Alarm Contact

100 mA@30 Vac/dc (If equiped)

Accuracy

1% full scale; combined linearity, hysteresis, repeatability

Compensated Temperature Range

-4 to 60 °C (25 to 140 °F)

Temp Coefficient

±0.05%/°C

Operating Environment

10 to 90% RH, non-condensing; -4 to 60 °C (25 to 140 °F)

SCIM

523 in3/min.@45 psi; 8520 cm3/[email protected] kPA;  
333 in3/min@20 psi; 5407 cm3/[email protected] kPA

Supply Pressure

45 psig max

Control Range

0 to 20 psig or 3 to 15 psig jumper selectable

Pressure Differential

0.1 psig (supply to branch)

Pressure Indication

Electronic, 3-1/2 digit LCD

Minimum Tubing Length

15 feet*

Port Connection

1/8-in. i.d. poly tubing

Media Connection

Clean dry air or inert gas. Not for use with oxygen service.

WARRANTY

Limited Warranty

5 years

COMPLIANCE INFORMATION

Agency Approvals

EMC Conformance*:  EN 61000-6-3:2007 and A1:2011 Class B,  
EN 61000-6-1:2007

EP2

Output

= Selectable 3-15/0-20 psi

Feedback

0 = None

1 = Pressure Loss Alarm

2 = Manual Mode  Alarm 

EP2 

Failsafe

0 = None

1 = Vent on Power Fail

Option

Blank = none

2 = EP Cover Plate 

S

1

*For shorter tubing runs use AA45 Pneumatic Capacitor.
**EMC Special Note:  Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection  
(EN 61000-6-1:2007 specification requirements)

*CE mark applies to models with cover only.

*

Отзывы: