EP2 Series Installation Guide

Dimensions

1.   Mount the transducer using the screws provided. Avoid damaging the electronic components. 

2.   Wire the transducer and configure the jumpers for desired operation as shown in the Wiring and Configuration section below.

3.   Attach pressure tubing to the hose barbs. Observe MAIN and BRANCH port labels. Use flexible ¼” O.D. poly tubing for the main 

and branch pneumatic connections. Main supply pressure must not exceed 45 psig.

Installation

Wiring & Configuration

1.9"

(48 mm)

3.3"

(84 mm)

3.5"

(89 mm)

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

Jumper Configuration

Input

Current (4 to 20 mA) or Voltage (0 to 5 V or 0 to 10 V)

Voltage

For voltage mode of operation, select 0 to 5 V or 0 to 10 V

Pressure Range

Select 0 to 20 psi or 3 to 15 psi scaling

Operation Mode

Select AUTO for normal operation or MANUAL to adjust pressure using the pushbuttons

Options

Alarm Mode Relay

The alarm contacts open if the EP2 cannot obtain 80% of commanded pressure within two (2) minutes

Manual Mode Alarm Contacts open when manual mode is selected (auto mode contacts are closed)
Vent On Power Fail

The EP2 vents the branch line pressure on power failure

Terminal Block Connections

GND/Common

Power supply ground and signal common.

Input Signal

4 to 20 mA, 0 to 10 Vdc, or 0 to 5 Vdc input from the control system.

Power

22 to 30 Vdc, 20 to 30 Vac. From the control system or external power supply or transformer. 

Pressure Loss Alarm 

(optional)

Normally closed, solid-state contacts open if the main supply pressure fails or if the transducer is otherwise unable to 

produce the correct branch pressure. Connect to the digital input of the control system for alarm status indication. If 

commanded pressure does not reach 80% within 2 minutes, the alarm contacts open.

•   0 to 20 psi alarm contact does not change state when the commanded pressure is 4 psi or less
•   3 to 15 psi alarm contact does not change state when the commanded pressure is 5.4 psi or less

NOTE: In 24 Vac transformer applications, one side of the transformer secondary is connected to the signal common. Some control systems may require a 
dedicated power supply transformer or isolation transformer.