H623-10 Installation Guide

TM

Wiring Example

Calibration

Troubleshooting

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center hole and around the sensor body to produce multiple turns through the 
“window.” This increases the current measured by the transducer.

Controller must be programmed to account for the extra turns. e.g., if four turns pass through the sensor (as shown) the normal 
controller reading must be divided by 4.

4x

0.5A

0.3 A

Scale the controller software to match the current transducer’s output (0 to 10 Vdc).

SENSED AMPS

10 A

0 Vdc

0 A

5 Vdc

SENSOR OUTPUT

Issue

Solution

No reading at controller

• Check for control voltage at sensor (<10 Vdc).
• Check for amperage in monitored conductor (>1 A).
• Assure that sensor core mating surfaces are clean.

Motor

Fan

CONTROLLER

AI

CONTACTOR

Insulated Conductor ONLY

0 to 10 Vdc+

COMM