Program Example
The following sequence of entries creates and runs the program shown graphically
below.
1. Press scroll
until the display shows RAMP.U <SP RAMP UNITS>. Select MIN.
2. Press scroll
until the display shows DWELL.U <DWELL UNITS>. Select MIN.
3. Press scroll
until the display shows RMP.1 <RAMP RATE 1>. Select 5
4. Press scroll
until the display shows T.SP1 <TARGET SP 1>. Select 600
5. Press scroll
until the display shows DWEL.1 <DWELL TIME 1>. Select 30
6. Press scroll
until the display shows RMP.2 <RAMP RATE 2>. Select 4
7. Press scroll
until the display shows T.SP2 <TARGET SP 2>. Select 400
8. Press scroll
until the display shows DWEL.2 <DWELL TIME 2>. Select 30
9. Press scroll
until the display shows RMP.3 <RAMP RATE 3>. Select OFF
10. Press scroll
until the display shows T.SP3 <TARGET SP 3>. Select 600
11. Press scroll
until the display shows DWEL.3 <DWELL TIME 3>. Select 60
12. Press scroll
until the display shows RMP.4 <RAMP RATE 4>. Select 3
13. Press scroll
until the display shows T.SP4 <TARGET SP 4>. Select 800
14. Press scroll
until the display shows DWEL.4 <DWELL TIME 4>. Select OFF
15. Press scroll
until the display shows RMP.5 <RAMP RATE 5>. Select 5
16. Press scroll
until the display shows T.SP5 <TARGET SP 5>. Select 400
17. Press scroll
until the display shows DWEL.5 <DWELL TIME 5>. Select 480
18. Press the ACK function to return to the home display.
19. Press the up
and down
keys together, to operate the program.
Segment
23
4.0 3216 Controller
Содержание CARBOLITE GERO TZF 15/90/610
Страница 6: ...1 0 Symbols and Warnings Caution Double Pole Neutral Fusing 6 ...
Страница 50: ......
Страница 51: ...Notes Service Record Engineer Name Date Record of Work ...