3.0 301 Controller
3.9.6
Resetting Over-Temperature Activation
l
Start at the home display.
l
Press and hold the Over-Temperature key until
Ott
is dis-
played.
l
Repeatedly press the Page key until
Ot
is displayed and the
red indicator stops flashing.
l
Press the up or down Arrow key to check the over-tem-
perature limit value.
l
Press the up or down Arrow key to alter the value if neces-
sary.
l
Press the Page key to return to the over-temperature dis-
play.
The over-temperature has now been reset.
If the temperature is still above the over-temperature setpoint then over-temperature
indicator will be red but not flashing.
When the temperature falls below the over-temperature limit, the indicator changes
back to green.
When the current temperature falls below the over-temperature setpoint, the furnace/
oven starts to heat again.