12 – TEMPERATURE SETBACK DELAY - HEAT
00-120
(20* default setting) Select the time delay (in minutes) for
which the room that is in the guest occupancy mode needs to
be unoccupied before the temperature setback is initiated.
This feature prevents initiating temperature setback
prematurely while the guest is still in the room but in an area
where occupancy cannot be detected by the occupancy sensor.
Setting the “Temperature Setback Delay - Heat” to “00”, disables
the setback in the heat mode. Set to “00” to disable EMS.
Custom Energy Savings Settings