Table 6: ZEC510-1 - controller wiring diagram

Number Description

Name on the

Verasys user

interface

Terminal

label

Object name Signal type

1

24 V HOT power transformer

2

24 V COM power transformer

3

Electric heat safeties

n/a

4

Optional. Heating stage command 1

HEATING STAGE

COMMAND 1

OUT1

HTG1-C

24 VAC on/off,

internally sourced

5

Optional. Heating stage command 2

HEATING STAGE

COMMAND 2

OUT2

HTG2-C

24 VAC on/off,

internally sourced

6

Optional. Supply fan command

SUPPLY FAN

COMMAND

OUT3

SF-C

24 VAC on/off,

internally sourced

7

Optional. Supplemental heating stage

command

SUPPLEMENTAL

HEATING STAGE

COMMAND

OUT4

SUPHTG1-C 24 VAC on/off,

externally sourced

8

Optional. Heating stage command 3

HEATING STAGE

COMMAND 3

OUT5

HTG3-C

24 VAC on/off,

externally sourced

9

Pressure ports. No polarity

10

Manual override

n/a

11

Optional. Supply air temperature

sensor TE-631GV-2.

SUPPLY AIR

TEMPERATURE

IN3

SA-T

Nickel 1K RTD

12

Optional. Relay: RIBU1C

13

Occupancy sensor OLS-2100-1. To red

wire occupancy switch

14

Occupancy sensor OLS-2100-1. To

neutral occupancy switch

OCCUPANCY

STATUS

IN2

OCC-S

Dry Contact, Normally

Open
Normally Closed is

configurable
through the interface

15

Optional. Discharge air temperature

sensor TE-631GV-2.

DISCHARGE AIR

TEMPERATURE

IN1

DA-T

Nickel 1K RTD

16

To next device

17

From last device

18

See riser schedule to determine the EOL

device. You must set the EOL switch to

the 

ON

 position on the EOL device.

n/a

19

Zone temperature sensor

NSB8BTN240-0. The connector is

located on the back of the sensor.

ZONE

TEMPERATURE

SENSOR BUS

ZN-T

20

Optional. Zone CO

2

 sensor NS-

BCN7004-0. The connector is located on

the back of the sensor.

ZONE AIR QUALITY

or ZONE CO2

SENSOR BUS

ZN-CO2

Sensor Actuator

(SA) bus

Note:

• Heating or fan contactors are in the VAV box. The VAV controller binary outputs switch the

common. OUT1, OUT2, and OUT3 are 24 V HOT continuously.

• You can average up to five NS sensors. Connect the NS sensors in a daisy-chain

configuration using the addresses in the 

Configuring the NS sensors

 section. The fifth

sensor must have the fixed address 199.

• If you install CO

2

 Net sensors, in addition to the 24 VAC power for the controller, you must

also supply 24 VAC power to the 

HOT

 and 

COM

 terminals.

Verasys ZEC510 VAV Controllers Installation Guide

14

Содержание ZEC510

Страница 1: ...barcode for factory use only LC ZEC510 3 Building Technologies Solutions www johnsoncontrols com 2021 04 08 241014301485B Verasys ZEC510 VAV Controllers Installation Guide Part No 24 10143 01485 Rev B...

Страница 2: ...2 Verasys ZEC510 VAV Controllers Installation Guide...

Страница 3: ...17 ZEC510 terminal functions ratings requirements and wiring guidelines 19 Input and output wiring guidelines 19 System and zone bus supply power wiring guidelines 19 Sequence of operation 24 Occupie...

Страница 4: ...th American emissions compliance 31 United States 31 Canada 32 Product warranty 32 Software terms 32 Single point of contact 32 Contact information 33 Verasys ZEC510 VAV Controllers Installation Guide...

Страница 5: ...VAV controller Important Utiliser ce ZEC510 VAV controller uniquement en tant que dispositif de contr le de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du controller risque de provo...

Страница 6: ...he top bottom sides and front of the controller for cable and wire connections and adequate ventilation through the controller Do not mount the ZEC510 in areas where electromagnetic emissions from oth...

Страница 7: ...box using a 5 16 in drill bit 10 Insert the mounting screw and tighten it against the spacer Important Do not over tighten the screw Over tightening can cause the threads to strip If you mount the ZE...

Страница 8: ...r 45 and 60 boxes The closed damper seal provides the full closed stop 15 Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point socket Tighten to 10 5 N m...

Страница 9: ...nly Make all wiring in accordance with local national and regional regulations To wire the ZEC510 complete the following steps 1 Use the appropriate figures according to your particular configuration...

Страница 10: ...ensor bus 2 Sensor bus terminal block plug on the terminating device 3 Daisy chained device on a sensor bus segment 4 Sensor bus terminal block plug on the daisy chained device 5 Cable shield connecti...

Страница 11: ...d device 5 Cable shield connection 6 Connects to the next device on the zone bus Connects to all ZECs and the zoning roof top unit RTU of the VZC100 Modular ports The modular sensor and zone bus ports...

Страница 12: ...ts into a board mounted jack on the upper left of the ZEC controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in the following...

Страница 13: ...ise interference and ground loop problems You may damage the controller by sharing power with other devices Wiring diagrams ZEC510 1 controller VAV with staged reheat control wiring example Figure 9 Z...

Страница 14: ...eutral occupancy switch OCCUPANCY STATUS IN2 OCC S Dry Contact Normally Open Normally Closed is configurable through the interface 15 Optional Discharge air temperature sensor TE 631GV 2 DISCHARGE AIR...

Страница 15: ...ZEC510 2 controller VAV with incremental reheat control wiring example Figure 11 ZEC510 2 flow diagrams Figure 12 ZEC510 2 wiring diagram 15 Verasys ZEC510 VAV Controllers Installation Guide...

Страница 16: ...y switch OCCUPANCY STATUS IN2 OCC S Dry Contact Normally Open Normally Closed is configurable through the interface 13 Optional Discharge air temperature sensor TE 631GV 2 DISCHARGE AIR TEMPERATURE IN...

Страница 17: ...Figure 13 Piping details ZEC510 3 controller Multizone unit VAV with proportional reheat control wiring example Figure 14 ZEC510 3 Flow diagrams 17 Verasys ZEC510 VAV Controllers Installation Guide...

Страница 18: ...OUTPUT OUT4 HTG O 0 VDC to 10 VDC 6 Optional Heating stage command HEATING STAGE COMMAND OUT5 HTG C 24 VAC on off externally sourced 7 Pressure ports No polarity 8 Manual override n a 9 Optional Suppl...

Страница 19: ...resses in the Configuring the NS sensors section The fifth sensor must have the fixed address 199 If you install CO2 Net sensors in addition to the 24 VAC power for the controller you must also supply...

Страница 20: ...ts OCOM2 to 24 COM when activated Internal power source 30 VAC maximum voltage to load 0 5 A maximum output current 40 mA minimum load current See guideline C in Table 10 OUT3 Provides a BO connection...

Страница 21: ...fan Internal power source 24 VAC power 24 HOT See guideline C in Table 10 OCOM3 Provides a BO connection for box fan Connects OCOM3 to 24 COM when activated Internal power source 30 VAC maximum volta...

Страница 22: ...AC maximum voltage to load 0 5 A maximum output current 40 mA minimum load current See guideline C in Table 10 OUT4 Provides an AO connection for box heat Outputs 0 VDC to 10 VDC signal 10mA maximum o...

Страница 23: ...p software for the input or output point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG strande...

Страница 24: ...he bias the primary air damper is at the minimum cfm and no mechanical heating runs When the zone temperature rises above the unoccupied cooling setpoint the primary air damper increases the cfm and n...

Страница 25: ...ables to address the NS sensors Figure 17 CO2 net stat with terminals addressable Table 11 CO2 NS sensors with terminals addressable A Address switch B To next device on the sensor bus if required C F...

Страница 26: ...4 Switch 2 Switch 1 199 Off Off Off 200 Off Off On 201 Off On Off 202 Off On On 203 On Off Off Note Addresses 204 to 206 are not supported Setup and adjustments Setting the ZEC510 device address Befor...

Страница 27: ...he highest address that you can set is 127 so ensure that DIP switch 128 is OFF 3 Continue setting lower numbered switches until the total equals the intended address 4 Write each field controller s d...

Страница 28: ...lighting switch OLS 2100 1 Occupancy sensing light switch for control of indoor incandescent and fluorescent lights RIBU1C Enclosed relay for OLS 2100 1 sensor Balancing tool NS ATV7003 0 Handheld VAV...

Страница 29: ...eady EOL is active Off steady EOL is not active Communication bus problems Communication problems include cases when devices fail to connect or connect intermittently One of the following factors can...

Страница 30: ...ing and exiting each terminal Note Devices at the ends of the trunk have one wire entering and exiting each terminal Check EOL switch settings Verify that the zone bus EOL switch on the Zone Coordinat...

Страница 31: ...nimum shaft length 44 mm 1 3 4 in Dimensions Height x width x depth 140 mm x 140 mm x 25 mm 5 1 2 in x 5 1 2 in x 1 in Shipping weight 0 30 lb 0 14 kg United States UL Listed File E107041 CCN PAZX UL...

Страница 32: ...deux conditions suivantes 1 L appareil ne doit pas produire de brouillage et 2 L utilisateur de l appareil doit accepter tout brouillage radio lectrique subi m me si le brouillage est susceptible d e...

Страница 33: ...Contact information Contact your local branch office www johnsoncontrols com locations Contact Johnson Controls www johnsoncontrols com contact us 33 Verasys ZEC510 VAV Controllers Installation Guide...

Страница 34: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice...

Отзывы: