Advanced instructions

EN

VTS reserves the right to implement changes without prior notice

7

 5. DESCRIPTION OF EAHU AUTOMATICS

 5.1. Interaction of EAHU with CO Detection Modules

The CO detection modules should be connected in parallel from the power supply side and alarm contacts side. If a detector detects 

concentration of CO exceeding a threshold, then EAHU will start operating.

!

   

Rated parameters of the protection unit mounted on the VTS-E-0006 electric module PWB have to be taken into account (see 
page 3.3).

 5.2. Connecting control components

!

   

Control components should be connected as shown on the Electric Diagram

No

Location of cable connection

Unit (group)

Diagram ref no.

Conductor 

type

Cross-section

[mm

2

]

1.

Joint terminal of converter control

[2] converter

[2] / COM

[2]

1

1

2.

Initiating signal for frequency converter

[2] / START

1

1

3.

Speed I signal for frequency converter

[2] / FC I

1

1

4.

Speed II signal for frequency converter

[2] / FC II

1

1

5.

Speed III signal for frequency converter

[2] / FC III

1

1

6.

Frequency converter alarm contact

FC ALARM

2

1

7.

Joint terminal for CO detector

CO detector

N1F / 24V DC

1

1

8.

CO detector contact indicating exceeding of the first 

threshold of CO concentration

N1F / CO I

1

1

9.

CO detector contact indicating exceeding of the second 

threshold of CO concentration

N1F / CO II

1

1

10.

CO detector contact indicating exceeding of the third 

threshold of CO concentration

N1F / CO III

1

1

11.

CO detector contact indicating unit's failure

N1F / CO ALARM

1

1

12.

Joint terminal for remote control

Remote 

control 

adjuster

Q2 / 24V DC

1

1

13.

Remote control contact – speed I

Q2 / RC I

1

1

14.

Remote control contact – speed II

Q2 / RC II

1

1

15.

Remote control contact – speed III

Q2 / RC III

1

1

16.

Alarm contact of fire protection control

ALARM

2

1

17.

EAHU lighting

E1

2

1

18.

Damper actuator

2Y1

3

1

19.

Operation confirmation voltage-free contact NO type

X3:23 – X3:22

2

1

20.

Operation confirmation voltage-free contact NC type

X3:23 – X3:22

2

1

21.

External initiating signal

ESP

2

1

22.

Pressure control contact of initial filter

2S1H

2

1

23.

Pressure control contact of secondary filter

2S2H

2

1

 5.3. Required Conductors

Conductor 

type

Figure

Description

Parameters

[1]

Control cables with copper conductors, 

shielded with copper wires, PCV insulated.

Rated voltage: 300/500 V Operating temperature: 

-40 up to 70°C

[2]

Multi-conductor cables, single- or multi-wire 

copper conductors, PCV insulated.

Rated voltage: 450/750V Operating temperature: 

-40 up to 70°C

Содержание VS 180-300 CG 0-1

Страница 1: ...EN Control gear for Exhaust Air Handling Units EAHU VS 21 150 CG 0 1 VS 180 300 CG 0 1 VS 400 650 CG 0 1 Operation and Maintenance Manual DTR CG ver 1 7 09 2021...

Страница 2: ...www vtsgroup com The control gear complies with European Standard IEC EN 60439 1 AC Standard Switchboards and low voltage control gears EN...

Страница 3: ...trol 4 3 2 EAHU Start Control Signals 5 3 3 Order of Control Channels 5 3 4 Damper Control 5 3 5 EAHU Start Confirmation for Remote Equipment 5 3 6 Filter Check 5 4 TECHNICAL SPECIFICATION 6 4 1 Const...

Страница 4: ...n Power of the Control Gear Element Function 24V DC Control circuits supply LED 24V READY Ext start permission LED REMOTE Remote control LED 1 4 Detailed description of signal lamps CO Control LED ind...

Страница 5: ...witch of the control gear Function Condition Operation EAHU Start up Local fan speed adjuster I II III setting I II or III Each of the three control signals local remote from the CO detector may indep...

Страница 6: ...control LOC channel 1 connection J12 Exhaust fan speed can be controlled from the front of the control gear Remote control RC channel 2 X3 13 X3 16 Exhaust fan speed can be controlled through remote c...

Страница 7: ...h memory module The exhaust unit start up after converter alarm event requires fixing the cause of the alarm and turning off and switching on again the Q1 mains switch of the control gear 3 3 Order of...

Страница 8: ...voltage of control circuits 24 V AC EMC environment 1 4 3 Parameters of protection elements of the VTS E 0006 electric module F11 Protection module of power supply circuit of the CO detection module P...

Страница 9: ...ct indicating exceeding of the first threshold of CO concentration N1F CO I 1 1 9 CO detector contact indicating exceeding of the second threshold of CO concentration N1F CO II 1 1 10 CO detector cont...

Страница 10: ...er 2 Motor feeder 1 Control gear feeder 2 Control gear rated current kW A 1x230V 50Hz 3x230V 50Hz MicroDrv VLT mm2 mm 2 mm 2 A 0 75 3 gG16 1 3x1 5 4x1 5 3x2 5 4 5 1 1 4 5 gG16 1 3x1 5 4x1 5 3x2 5 6 1...

Страница 11: ...prior notice 9 0 1 8 7 69 1 5 4 3 2 I I I I I I I I I I I I O C E T O M E R Y D A E R C D V 4 2 1 M 2 1 N L PE GND 0 10V IN1 COM IN2 24V AC DC 1 2 1209 0062 GND 0 10V 10V AN1 GND OR 1x230V 3x400V 1 2...

Страница 12: ...otice 10 0 1 8 7 69 1 5 4 3 2 I I I I I I I I I I I I O C E T O M E R Y D A E R C D V 4 2 1 M 2 1 N L PE GND 0 10V IN1 COM IN2 24V AC DC 1 2 1209 0062 GND 0 10V 10V AN1 GND 3x400V 2 M 2 1 N L PE AN1 G...

Страница 13: ...E R C D V 4 2 1 M 2 1 N L PE GND 0 10V IN1 COM IN2 24V AC DC 1 2 1209 0062 GND 0 10V 10V B GND OR 1x230V 3x400V 1 2 1203 1002 A B GND A For VVS005s MOTOR EC072 25E3G01 B190 Cable1 power Brown L Cable2...

Страница 14: ...A E R C D V 4 2 1 M 2 1 N L PE GND 0 10V IN1 COM IN2 24V AC DC 1 2 1209 0062 GND 0 10V 10V 3x400V 2 M 2 1 N L PE 1 2 1203 1002 For MOTOR EC072 25E3G01 B190 Cable1 power Brown L Cable2 communication Y...

Страница 15: ...ns EN VTS reserves the right to implement changes without prior notice 13 0 1 8 7 6 9 1 5 4 3 2 1 M 2 3 1 U 2 I I I I I I I I I I I I O C E T O M E R Y D A E R C D V 4 2 Electric scheme of VS 21 150 C...

Страница 16: ...4 5 Q1 1L1 1L1 1L2 1L2 1L3 1L3 PE N L1 L2 L3 1L1 1L2 1L3 2M1 3 2U1 1 2 3 4 5 6 2F1M N N PE PE H1 T1 24V 230V F1 1 N 1L3 2 N1 1L3 12 11 10 13 15 14 16 17 18 VTS E 0006 J12 3 2 1 4 6 5 7 8 9 21 20 19 2...

Страница 17: ...650 CG 0 1 control gear 6 7 8 10 9 1 2 3 4 5 Q1 1L1 1 1 L L 1 1 1L2 1 1 L L 2 2 1L3 1 1 L L 3 3 PE N L1 L2 L3 1L1 1L2 1L3 2M1 2M3 3 3 2U1 1 1 2 2 3 3 4 4 5 5 6 6 2F1M N N N PE PE PE N 1 1 L L 1 1 1 1...

Страница 18: ...Advanced instructions EN VTS reserves the right to implement changes without prior notice 16 AE 0 2S2H 2M1 2U1 2S1H 2Y1 CO...

Отзывы: