VUT .. WH ЕС
Heat exchanger adjustments
(Adjust-Recuper.)
Heat exchanger adjustment menu.
R-01
0
Minimum allowable exhaust air temperature downstream from
the heat exchanger that does not require exhaust temperature
regulation [ºC]. If actual exhaust air temperature drops down below
R-01 parameter, the bypass damper is partially opened to keep
exhaust air temperature within required parameters. After exhaust
air temperature increase above R-01 parameter, the bypass damper
is closed.
R-02
-5
Minimum allowable exhaust air temperature downstream from the
heat exchanger [ºC]. If exhaust air temperature remains below R-02
parameter longer than R-03 period, F1 alarm signal is generated.
R-03
600
Time period to check exhaust air temperature decrease [s].
R-04
1
Adjustment of the exhaust air temperature regulation parameters by
the bypass valve - PI-regulation proportionality constant.
R-05
100
Adjustment of the exhaust air temperature regulation parameters by
the bypass valve - PI-regulation integrating coefficient [s].
R-06
0,5
Adjustment of the exhaust air temperature regulation parameters by
the bypass valve - dead zone [°C]. If the discrepancy is below R-06, it
shall be disregarded.
R-07
1
Adjustment of the supply air temperature regulation parameters by
the bypass valve - PI-regulation proportionality constant.
R-08
100
Adjustment of the supply air temperature regulation parameters by
the bypass valve - PI-regulation integrating coefficient [s].
R-09
0,5
Adjustment of the supply air temperature regulation parameters by
the bypass valve - dead zone [°C]. If the discrepancy is below R-06, it
shall be disregarded.