Fig. 4. Condensate drainage
3
2
1
4
5
3
2
1
4
5
A condensate drainage system is used in premises with above-zero temperatures. To enable
operation at subzero temperatures the condensate drainage system must be equipped with heat
insulation and pre-heating facilities.
The units are intended for connection to 230 V / 50 (60) Hz single-phase alternating current mains.
The power mains connection is via a Euro plug cable pre-wired at the factory.
Connect the unit to power mains through the external automatic circuit breaker with magnetic trip
integrated into the fi xed wiring system with the rated current not below the rated current consumption
(refer to Table 1).
Disconnect the unit from the power supply prior to any operations on the unit! The
unit must be plugged into a properly installed power socket with an earthed terminal.
The rated electrical parameters of the unit are stated on the rating plate. Any tampering
with the internal connections is prohibited and will void the warranty.
Connection to power mains