7
VUE2 150 P ЕС Comfo
The unit design and operating logic are stated on fig. 2:
The warm stale air from the premises enters the unit through air ducts where it is stripped of impurities and then extracted through
the heat exchangers by means of the exhaust fan further outside via the air ducts. The cool fresh air from the outside enters the unit
through air ducts where it is stripped of impurities in the supply filter and then extracted through the heat exchangers by means of the
supply fan further into the premises via the air ducts.
The heat exchangers ensure energy exchange between the warm stale air extracted from indoors with the cool fresh air supplied
from outdoors. The air streams remain completely separated in the process. Sensible and latent heat energy recovery reduces heat energy
losses and, consequently, heating costs in the cold season and the air conditioning costs in the warm season.
The units are offered in the left-hand and right-hand variants for installation convenience.
The polymerized cellulose heat exchangers are used to recover both sensible and latent energy contained in the extract air and
transfer it to the cold intake air flow from outside.
The polymerized cellulose heat exchangers act as air moisture accumulators when the ambient air humidity is too low or as supply
air dehumidifiers if the ambient humidity is high. Due to the excellent water-absorbing properties of the heat exchanger material the
unit drainage is not required. The heat exchangers are used to minimise heat energy losses and, consequently, heating costs in the cold
season.
The unit design is shown on Fig. 2.
The units are equipped with a quick-release access panel on special gaskets for easy repair and maintenance.
DESIGN AND OPERATING LOGIC
Table 2. Control panel parameters
Ambient temperature [°C]
from 0 up to +40
Relative humidity [%]
from 5 up to 90 (no condensation)
Cable cross section [mm2]
from 0.18 to 0.35
Material
ABS plastic
Dimensions (WхHхD) [mm] 86х86х14
Cable length [m]
up to 10
IP rating
IP30
Exhaust air
Intake air
Extract air
Supply air
Extract filter
Supply filter
Control unit
Heat exchanger
Supply fan
Heat exchanger
Exhaust fan
Right-hand modification
Left-hand modification
Intake air
Exhaust air
Extract air
Supply air
Heat exchanger
Exhaust fan
Fig. 2. Design and operating logic