CONNECTION TO POWER MAINS

POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.

THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.

THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE 

MANUFACTURER’S LABEL.

ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED  

AND WILL VOID THE WARRANTY.

X

N

L

QF

X

S

N

L

QF

N

L

N

L

WIRING DIAGRAM

•  The unit is rated for connection to power mains with the parameters specified in the "Technical specifications” section, according to 

the wiring diagram.

•  The connection must be made using durable, insulated and heat-resistant conductors (cables, wires). 
•  The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending 

on the wire type, insulation, length and installation method.

•  The external power input must be equipped with an automatic circuit breaker QF built into the stationary wiring to open the circuit 

in the event of overload or short-circuit. 

•  The position of the external automatic circuit breaker must ensure free access for quick power-off of the unit. 
•  The trip current of the automatic circuit breaker must exceed the maximum current consumption of the unit (refer to the “Technical 

data” section or to the unit label). 

•  The recommended trip current of the circuit breaker is the next current in the standard trip current row following the maximum 

current of the connected unit. 

•  The circuit breaker is not included in the delivery set and can be ordered separately.

Designation:

– line;

 N

 – neutral;

 QF 

– automatic circuit breaker;

 S 

– external switch (Diagrams 1, 2);

 

– switch (Diagram 3);

 X 

– input terminal block

Diagram 1

Connection of the fan 

to power mains

Diagram 2

Connection of the fan to power mains with an 

external switch

WARNING! The fan is equipped with a thermal switch without self-resetting function.

To avoid a random restart of the thermal switch, the unit must not be powered through an external switching device, such as 

a timer, or connected to power mains usually turned on/off by public services.

QF

N

L

N

L1

L2

X

S

Diagram 3

Connection of the Duo fan 

to power mains

Содержание VKS 200

Страница 1: ...VK Centrifugal fan USER S MANUAL...

Страница 2: ...VK unit and all its modifications Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workpla...

Страница 3: ...operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation operations Unpack the unit with care The unit must be grounded While installi...

Страница 4: ...es in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open the unit during operation Do not direct...

Страница 5: ...ogenic germs Name Number Fan 1 pc Screws and dowels 4 pc Mounting bracket 2 pc User s manual 1 pc Packing box 1 pc VK S 100 X Additional options Q low power motor Duo double speed motor U speed contro...

Страница 6: ...250 VK 315 VKS 315 Voltage V 50 Hz 1 230 Power W 107 173 108 173 200 310 Current A 0 47 0 76 0 47 0 76 0 88 1 36 Maximum air flow m3 h 780 930 865 1080 1340 1700 RPM min 1 2660 2125 2560 2090 2655 25...

Страница 7: ...speed as the room air temperature exceeds the set point As the air temperature drops 2 C below the set point or if the initial temperature is below the set point the TSI goes out and the fan operates...

Страница 8: ...n is suitable both for horizontal or vertical mounting on the floor on the wall or on the ceiling Air motion in the system must be in compliance with the direction of the arrow on the fan casing Insta...

Страница 9: ...in the event of overload or short circuit The position of the external automatic circuit breaker must ensure free access for quick power off of the unit The trip current of the automatic circuit break...

Страница 10: ...d only in the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transportation at low temperatures allow the unit to warm...

Страница 11: ...ler for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including s...

Страница 12: ...cceptance of the complete unit delivery with the user s manual The warranty terms are acknowledged and accepted Customer s Signature INSTALLATION CERTIFICATE The VK __________ unit is installed pursua...

Страница 13: ...13 www ventilation system com...

Страница 14: ...14 VK www ventilation system com...

Страница 15: ...15 www ventilation system com...

Страница 16: ...V02EN 12...

Отзывы: