PU SENS 01

www.ventilation-system.com

10. Extra options

• 

Select the 

EXTRA OPTIONS

 item in the Engineering menu and press  

ENTER

 

.

•  HEATING CONTROL 

activates heater operation. 

Before activating the 

HEATING CONTROL MODE

 turn off the 

SUPPLY

FAN OFF MODE

 by selecting the 

OFF

 button.

• 

The 

SUPPLY FAN OFF MODE

 activates the heat exchanger freeze 

protection and can only be activated when the 

HEATING CONTROL

 

option is 

OFF

.

To activate the heat exchanger freezing protection function by means of 
the supply fan deactivation set the 

HEATING CONTROL

 parameter value 

to 

OFF

.

To proceed to the mode settings set the 

SUPPLY FAN OFF MODE

 

parameter to 

ON

.

•  HUMIDITY SENSOR SELECTION

 - selection of the humidity sensor for 

controlling the unit.
1 — the sensor is installed in the extract air duct.
2 — the sensor is installed indoors. 

•  BYPASS OPERATION MODES:

1 — automatic mode for set temperature maintenance and freeze 
protection.
2 — manual mode for positive air damper opening for natural ventilation.
The Summer Bypass only works for outdoor temperatures over 10°C

WARNING

: It is not recommended to use the manual bypass mode (2) 

during the winter period to prevent room overcooling. 
Only 

AUTO

 mode (1) should be used during the winter period.

• 

To save the changes and return to the Engineering menu press 

.

20

5

+3

• 

If the 

SUPPLY FAN OFF MODE

 parameter is set to 

ON

 the control panel 

switches to the 

SUPPLY FAN OFF MODE

 setting.

• 

Select an item by touching the respective field: 

WORKING HOURS

DOWNTIME

 and 

SWITCH-OFF TEMPERATURE

 (the temperature is set 

according to the outdoor temperature sensor readings defined in the range 
from +10 °C to -20 °C).

• 

Then use 

 and 

 to set the desired value.

• 

Press ENTER 

 to confirm the set parameters.

• 

To return to the Engineering menu without saving changes press 

 

EXIT

 

.

All manuals and user guides at all-guides.com

Содержание PU SENS 01 A11

Страница 1: ...PU SENS 01 A11 PU SENS 01 A19 Sensor Control Panel USER S MANUAL All manuals and user guides at all guides com a l l g u i d e s c o m...

Страница 2: ...ument intended for technical maintenance and operating staff The manual contains information about purpose technical details operating principle design and installation of the PU SENS 01 unit and all...

Страница 3: ...operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains...

Страница 4: ...OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLA...

Страница 5: ...Install the mounting box Remove the screws on the panel edge Disassemble the panel by separating the frontal part from the back part Pass the cable into the rectangular opening on the back part of the...

Страница 6: ...e the battery use a new battery only 1 Disconnect the unit from power supply 2 Remove two screws in the bottom part of the casing 3 Pull the top part of the casing aside to allow access to the upper c...

Страница 7: ...When the AUTO mode is active the unit switches to scheduled operation and ignores manual control settings of air flow and temperature provided that the timer is off 3 Manual control settings of air fl...

Страница 8: ...the set level the unit slowly increases the speed If the room humidity is lower than the set level the unit slowly decreases the speed In this way the humidity is maintained at the set level The humi...

Страница 9: ...ving changes press EXIT 5 User menu To enter the User menu press MENU in the control panel Main menu The User menu contains basic menu items and functions for parameters setting ENG MENU access to the...

Страница 10: ...to the Engineering menu press EXIT If you forgot the user defined password see para 11 Password Change press and hold RESET until you hear a long sound signal 20 clicks approximately 20 seconds The de...

Страница 11: ...the Engineering menu select the TEMPERATURE SENSOR submenu and press ENTER Select a desired sensor type Press ENTER to confirm To return to the Engineering menu without saving changes press EXIT The d...

Страница 12: ...indoors BYPASS OPERATION MODES 1 automatic mode for set temperature maintenance and freeze protection 2 manual mode for positive air damper opening for natural ventilation The Summer Bypass only works...

Страница 13: ...elect 0 deactivation of the unit 1 standby mode While in the Standby mode the ventilation unit runs at the first speed at the pre set temperature Press ENTER to confirm To return to the Engineering me...

Страница 14: ...rol panel is installed The control panel is equipped with a humidity sensor Then use or to set the desired humidity level Press ENTER to confirm To return to the Engineering menu without saving change...

Страница 15: ...enu without saving changes press EXIT The default settings are given in the table below 18 Current temperature review 6 15 20 OFF OFF Select the CURRENT TEMPERATURES item in the Engineering menu and p...

Страница 16: ...ctive When the AUTO mode is active the unit switches to scheduled operation and ignores manual control settings of air flow and temperature provided that the timer is off To set up the AUTO mode press...

Страница 17: ...00 12 00 1 20 2nd line 11 00 13 00 2 20 In the interval from 10 00 to 11 00 the unit will operate at the first speed and from 11 00 will switch to the second speed since the lower line has a higher p...

Страница 18: ...the timer is active the unit switches to the timer scheduled operation and ignores the schedule settings AUTO mode and manual control settings AIR FLOW and TEMPERATURE Activation of the TIMER function...

Страница 19: ...erval The OPERATING HOURS window shows the time elapsed from the filter installation Press RESET after replacement of the filter To save the changes and return to the Engineering menu press EXIT 23 Er...

Страница 20: ...stment Operation 50 Sleep 1 Humidity setting Duct 50 Room 50 Temperature sensor correction 4 Timer settings Hours 01 Hour Minutes 00 Minute Air flow rate 1 Temperature 20 Motor hours Air handling unit...

Страница 21: ...21 www ventilation system com All manuals and user guides at all guides com a l l g u i d e s c o m...

Страница 22: ...22 PU SENS 01 www ventilation system com All manuals and user guides at all guides com...

Страница 23: ...23 www ventilation system com All manuals and user guides at all guides com...

Страница 24: ...V55 6EN 10 All manuals and user guides at all guides com...

Отзывы: