![Vents MPA 1200 E3 MPA Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/vents/mpa-1200-e3-mpa/mpa-1200-e3-mpa_user-manual_1002383009.webp)
9
www.ventilation-system.com
MOUNTING AND SET-UP
READ THE USER’S MANUAL PRIOR TO MOUNTING THE UNIT.
The unit should be mounted so that the arrow on the cover coincides with air flow direction in the system in order to provide access for
maintenance, servicing or replacement work.
Enough space must be provided for the cover to open all the way.
The unit can be mounted on flat surface or suspended on a threaded rod ensuring a secure fixation to prevent unit detachment or falling
down (in consideration of the unit weight and the mating surface material) using all the available L-shaped support brackets with an
antivibration damper attached to the unit base.
The unit is designed for mounting into rectangular air ducts.
• The duct should be connected via a flexible connection to eliminate transfer of noise and random vibrations.
• The dimensions of the connected air duct must be the same as the dimensions of the hole in the unit.
The recommended distance between the unit and other elements of the system must be not less than the diagonal of the unit spigot
(the distance from corner to corner of its air duct part).