MPA 3200, 3500 CONTROL UNIT
Contacts for connecting a signal from an automatic
Contacts for connecting a humidistat X5:3, X5:4
Contacts for connecting an air damper X5:5, X5:6, X5:7
к X5:5 (1)
к X5:6 (2)
к X5:7 (3)
Damper actuator
fire extinguishing circuit X5:1, X5:2
Additional options for external connections through the X5 terminal block are provided:
• connecting a contact of the automatic fire extinguishing system (inscription on the label - «PK1»)
• connecting a humidity sensor contact - humidistat (inscription on the label - «H1»)
• connecting a three-position air damper (inscription on the label - «1», «2», «3»).
When connecting the contact of the automatic fire extinguishing system, remove the jumper between the X5:1 and X5:2 terminals of the
X5 terminal block. In this case, a normally closed «dry contact» is used, which when triggered in case of fire, opens the unit control circuit
from the fire alarm panel and de-energizes it.
The humidistat is connected to the X5:3 and X5:4 terminals of the X5 terminal block. Normally open «dry contact» is used. When it is
closed, the unit switches to maximum speed.
The air damper actuator is connected to the X5:5, X5:6, and X5:7 terminals; «M» (1) contact of the damper actuator – to the X5:5 terminal
(inscription on the sticker «1»); «L» (2) contact – to the X5:6 terminal (inscription «2»); «L» (3) contact – to the Х5:7 terminal (inscription «3»).
The recommended type of damper is KRA (for round or rectangular air ducts) with an LM 230 A actuator (Belimo).
Содержание MPA 1200 E3 MPA
Страница 1: ...MPA E USER S MANUAL Single block air supply unit ...
Страница 16: ...16 MPA www ventilation system com MPA 800 CONTROL UNIT ...
Страница 17: ...17 www ventilation system com MPA 1200 2500 CONTROL UNIT ...
Страница 22: ...22 MPA www ventilation system com ...
Страница 23: ...23 www ventilation system com ...
Страница 24: ...V27EN 04 ...