Main technical specifications of Belimo electric actuators with a return spring and a thermal breaker
Technical data
Basic models
Models with increased torque
Models with the highest torque
Rated operation voltage
AC/DC 24 V
AC 230 V
AC/DC 24 V
AC 230 V
AC/DC 24 V
AC 230 V
Permissible operating voltage tolerance
AC 19.2…28.8 V
DC 21.6…28.8 V
AC 198…264 V
AC 19.2…28.8 V
DC 21.6…28.8 V
AC 198…264 V
AC 19.2…28.8 V
DC 21.6…28.8 V
AC 198…264 V
AC mains frequency
50/60 Hz
Power consumption at rest [W]
0.8
1.1
1.4
2.1
2
3
Power consumption in operation [W]
2.5
3.5
4
5
7
8.5
Maximum design capacity [VA]
4
6.5
6
10
10
11
Motor torque [Nm]
4
9
18
Spring torque [Nm]
3
7
12
Protection class
III
II
III
II
III
II
Ingress protection rating
IP54
Auxiliary switches
2 pcs., single-pole, reversible
1 mA…3 (0.5) A, AC 250 V
2 pcs., single-pole, reversible,
1 mA…6(3)A, AC 250 V
Electric motor connection cable
1 m, 2 x 0.75 mm² (halogen-free)
Auxiliary switch connection cable
1 m, 6 x 0.75 mm² (halogen-free)
Running time spring
20 seconds at -10…+55 °C
< 60 seconds at -30…-10 °C
16 seconds at +20 °C
Running time motor
< 60 s/90°
< 120 s/90°
Response temperature of thermal breaker sensors
Duct sensor 72 °C
Outdoor sensor 72 °C
Service life
Min. 60 000 emergency positions
Technical maintenance
Not required
Main technical specifications of Zern electric actuators with a return spring and a thermal breaker
Technical data
Basic models
Models with increased torque
Rated operation voltage
AC/DC 24 V
AC 100-240 V
AC/DC 24 V
AC 100-240 V
Permissible operating voltage tolerance
AC/DC 19.2…28.8 V
AC 85…265 V
AC/DC 19.2…28.8 V
AC 85…265 V
AC mains frequency
50/60 Hz
Power consumption at rest [W]
3
Power consumption in operation [W]
5
Motor torque [Nm]
5
8
Spring torque [Nm]
Protection class
III
II
III
II
Ingress protection rating
IP54
Auxiliary switches
2 pcs., single-pole, reversible,
1 mA…3(0.5)A, AC 220 V
Electric motor connection cable
1 m, 2 x 0.5 mm² (halogen-free)
Auxiliary switch connection cable
1 m, 6 x 0.5 mm² (halogen-free)
Running time spring
<20 seconds
< 60 seconds at -30…-10 °C
<25 seconds
< 60 seconds at -30…-10 °C
Running time motor
< 70 s/95°
< 100 s/95°
Response temperature of thermal breaker sensors
Duct sensor 72 °C
Outdoor sensor 72 °C