ELECTRICAL CIRCULAR DUCT HEATERS
EKA
14
Heater type
Temperature control type
Setpoint range
EKA NV...
Potentiometer on the top of the heater casing
(0...30)
°C
*
EKA NI...
External wired remote panel with setpoint knob
(TR5K)
(0...30)
°C
EKA NIS...
External wired remote
(0...10) VDC
signal
(analog input)
P**×(0...100) %
EKA ESKM...
External wired remote PWM
(ON/OFF: ON (6…24) VDC)
signal
P**×(0...100) %
EKA MB...
External wired remote control via Modbus RTU protocol
(RS485)
(0...30)
°C
or
P**×(0...100) %
*
– other setpoint range on request
**
– power of the heater (kW)
Electrical duct heaters EKA NV
…
are designed with integrated temperature control, one
temperature sensor, potentiometer on the top of the heater casing for temperature setpoint.
When the heater power supply is switched on, LED 6 on the controller
(EKR-
KN…)
PCB
(see Fig.
11)
flashes once every 8 seconds if setpoint is 0
°C
and every second if setpoint is
higher than
0
°C.
If
controller turns on the heating depending on the demand, LED 5 lights
(see Fig. 11)
.
Heaters
EKA NV … operates
by the supply
(TJ-K10K)
air temperature sensor. Setpoint
temperature
(0…30)
°C.
There can be set the different desired
(setpoint)
air temperature by potentiometer on the top
of the heater casing.
If LED 6 lights continuously it means that there is a failure of: supply
(TJ-K10K)
air temperature
sensor or potentiometer on the top of the heater casing.
IMPORTANT:
If failure appears, power supply must be switched off and only then performed
fault elimination works.
Electrical duct heaters EKA NI
…
are designed with integrated temperature control, one
temperature sensor, wired remote control panel
(TR5K)
for temperature setpoint.
When the heater power supply is switched on, LED 6 on the controller
(EKR-
KN…)
PCB
(see Fig.
11)
flashes once every 8 seconds if setpoint is 0
°C
and every second if setpoint is
higher than
0
°C.
If
controller turns on the heating depending on the demand, LED 5 lights
(see Fig. 11)
.
Heaters
EKA NI … operates
by the supply
(TJ-K10K)
air temperature sensor. Setpoint
temperature
(0…30)
°C.
There can be set the different desired
(setpoint)
air temperature by wired remote control panel.
If LED 6 lights continuously it means that there is a failure of: supply
(TJ-K10K)
air temperature
sensor or wired remote control panel TR5K.
Description of control type
Description
of operating EKA NV …
2
Description
of operating EKA NI …
2
Содержание EKA 100