Ducting Do’s and Don’ts

YES

NO

Smooth Duct

Smooth Gradual Turn

Proper Combining

of Two Ducts

Flexible Duct

Sharp Angled Turns

Improper Combining 

of Two Ducts

General Requirements

• 

Observe local codes regarding special duct requirements and placement of duct against combustibles.

•  Using Vent-A-Hood transitions (back page) will ensure proper efficiency.

•  Using Vent-A-Hood roof jacks or wall louvers (back page) will ensure proper efficiency.

• 

Where possible, seal joints with duct tape.

• 

The hood must be ducted to the outdoors without restrictions.

Blower Requirements

• 

The single blower unit (B100) requires 6” round duct or equivalent (28 square inches), and the dual 

blower unit (B200) requires 8” round duct or equivalent (50 square inches).

Blower

Combined Duct Dize

Sq. Inch Area

Vent-A-Hood Transition

Single (B100)

6" round or equivalent

28 sq. in.

N/A

Dual (B200)

8" round or equivalent

50 sq. in.

N/A

Single and Dual (B100 & B200)

10" round or equivalent

79 sq. in.

VP562 (Optional)

Two Duals (Two B200s)

12" round or equivalent

113 sq. in.

VP563 (Optional)

Ducting Requirements

• 

NEVER reduce the duct size.

•  When combining ducts together, the square inch area must reflect the total square inch area of the 

ducts being combined.

•  Do not use flexible or corrugated duct. This type of duct will restrict airflow and reduce performance.

•  Only use smooth, galvanized, metal duct.

• 

Make the duct run as short and as straight as possible with as few turns as possible.

• 

Avoid sharp-angled turns. Instead, use smooth, gradual turns such as adjustable elbows or 45 degree 

angled turns.

•  For duct runs over 20 feet, increase the duct diameter by one inch for every ten feet of duct.

• 

A 90 degree elbow is equal to 5 feet of duct.

Termination Requirements

•  Airflow must not be restricted at the end of the duct run.

• 

A wall louver or roof jack is required for each duct run.

•  Every wall louver or roof jack must include a gravity damper to prevent back drafts.

• 

Do not use screen wire or spring-loaded doors on wall louvers or roof jacks.

•  Do not terminate venting into an attic or chimney.

Содержание VP526

Страница 1: ...nto wall or ceiling do not damage electrical wiring and other hidden utilities C Ducted fans must always be vented to the outdoors D Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire ...

Страница 2: ...00 B200 10 round or equivalent 79 sq in VP562 Optional Two Duals Two B200s 12 round or equivalent 113 sq in VP563 Optional Ducting Requirements NEVER reduce the duct size When combining ducts together the square inch area must reflect the total square inch area of the ducts being combined Do not use flexible or corrugated duct This type of duct will restrict airflow and reduce performance Only use...

Страница 3: ...of the liner allowing room for the transition if applicable If back venting the elbow s should be installed so that the non crimped end s are on the inside the collar s of the exhaust outlet s If a transition is used install duct down to the location of the transition outlet plus 1 This will allow the transition to engage 1 inside of duct Consult the connection diagrams next page for further detai...

Страница 4: ... for step 10 5 Remove the shipping tape that is securing the E Z Clean shield s inside the hood Remove the E Z Clean shield s by lightly pulling it toward the front of the hood Gently close the back draft damper s from the top side of the hood To remove the blower housing s unsnap the suitcase latches one on each side of the housing The housing s should be pulled forward and gently tipped to clear...

Страница 5: ...sly removed from the packaging in Step 4 11 Install the trim piece for the back side of the liner provided in the liner trim kit by hooking one side under the bottom edges of the back countersunk washers Snap the trim piece over the top of the countersunk washers by applying pressure upward and toward the liner wall Repeat this process for the side trim pieces provided in the liner trim kit Note I...

Страница 6: ... 23 VP563 30 3 x 10 TO 7 TRANSITION MODEL DIM VP521 3 x 10 to 7 7 7 3 10 LOW PROFILE ROOF JACK MAXIMUM 4 12 PITCH MODEL DIM 6 VP539 VP540 VP541 6 Round 7 Round 8 Round 16 16 LOW PROFILE ROOF JACK MAXIMUM 4 12 PITCH MODEL DIM 10 VP552 VP553 10 Round 12 Round 22 20 ADJUSTABLE ELBOW MODEL DIM VP513 VP514 VP515 6 Round 7 Round 8 Round 6 7 8 VP513 8 VP514 9 9 16 VP515 10 5 8 BACK SIDE VENT ELBOW MODEL ...

Отзывы: