B. WIRING.

 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / 
OR MAINTENANCE. 
 

IMPORTANT 

  The cross - sectional area of supply cord used should be ranged from 0.75 -1.5mm

2

  The extraction fan is suitable for connection to 220-240V 50Hz supply.  

  The fan is a class ll double insulated product and 

MUST NOT 

be earthed. 

 

 
 

1. 

Select and follow the appropriate wiring diagram. (Fig. 1, 2 or 3) 

2. 

Check all connections have been made correctly and ensure all terminal 
connections and supply wires are securely fastened using cable clamp provided. 

3. 

Ensure the impeller rotates and is free from obstructions once reassembled 

(Fig. 4 

and 5).

 

 
 

C. SETUP 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / 
OR MAINTENANCE. 

 

TIMER ADJUSTMENT – HTP AND T MODELS (FIG. 4 AND 5) 

BEFORE ADJUSTING THE TIMER, SWITCH OFF THE MAINS SUPPLY. TIMER SHOULD 
ONLY BE ADJUSTED BEFORE OR DURING INSTALLATION. 

1. 

Remove the fan grilles and PCB cover. The product is factory set at 15 minutes 
approx. The overrun period can be adjusted from 3-25 minutes by altering the pot 
on the control PCB. 

2. 

To REDUCE the operating time, use a small screwdriver to turn the pot 

ANTI-

CLOCKWISE

3. 

To INCREASE the operating time, use a small screwdriver to turn the pot 

CLOCKWISE.

 

4. 

Replace the PCB cover, impeller and fan covers. 

 

HUMIDITY SET-POINT ADJUSTMENT – HTP MODEL (FIG. 4 AND 5) 

BEFORE ADJUSTING THE CONTROLLER, SWITCH OFF THE MAINS SUPPLY. 
HUMIDISTAT SHOULD ONLY BE ADJUSTED BEFORE OR DURING INSTALLATION. 

 

1. 

Remove the fan grilles and PCB cover. The product is factory set to switch on at 
about 70% RH. The humidity set point can be adjusted from 40-95%RH by altering 
the pot on the control PCB. 

2. 

To LOWER the set-point use a small screwdriver to turn the pot 

ANTI-

CLOCKWISE

. This makes the controller MORE sensitive.  

3. 

To RAISE the set-point use a small screwdriver to turn the pot 

CLOCKWISE

. This 

makes the controller LESS sensitive.  

4. 

Replace the PCB cover, impeller and fan covers. 

Содержание Solo Pro HTP

Страница 1: ...ation and Wiring Instructions Stock Ref N Solo Pro P 409159 Solo Pro T 409160 Solo Pro HTP 409161 Solo Pro TM 409162 PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Solo Pro IPX4 220 240V 50Hz ...

Страница 2: ... Phase complies with the rating label D The Fan should only be used in conjunction with the appropriate Vent Axia products E The fan should only be used in conjunction with fixed wiring F When the Fan is used to remove air from a room containing a fuel burning appliance ensure that the air replacement is adequate for both the fan and the fuel burning appliance G The Fan should not be used where it...

Страница 3: ...re the fan as described in Section B Wiring Adjust any settings as required see Section C Setup 8 Replace the PCB and inner covers and impeller 9 After installation ensure impeller rotates freely Replace the front panel WALL MOUNTING FIG 4 1 For wall mounting cut a 117mm diameter hole through the wall and insert the wall sleeve Slope the sleeve slightly downwards away from the fan Where necessary ...

Страница 4: ... TIMER SHOULD ONLY BE ADJUSTED BEFORE OR DURING INSTALLATION 1 Remove the fan grilles and PCB cover The product is factory set at 15 minutes approx The overrun period can be adjusted from 3 25 minutes by altering the pot on the control PCB 2 To REDUCE the operating time use a small screwdriver to turn the pot ANTI CLOCKWISE 3 To INCREASE the operating time use a small screwdriver to turn the pot C...

Страница 5: ...RD is switched into the off position the fan will deactivate The HTP model will return to the Auto sensing mode D SERVICING AND MAINTENANCE WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTENANCE 1 At intervals appropriate to the installation the fan should be inspected and cleaned to ensure there is no build up of dirt or other deposits 2 Carefull...

Страница 6: ...r 2 Remove the two screws as shown 3 For P and HTP models remove the pull cord clip L Switched Fused Spur 1 Phase Supply 220 240V 50Hz N L FUSE N N L 5 4 3 5A Fig 3 Solo Pro TM Visionex PIR Controller Please follow the fitting and wiring instructions for the Visionex PIR Controller for full installation instructions Solo Pro TM ...

Страница 7: ... together to release the impeller 5 Remove two screws as shown Fig 5 Wiring and settings Supply cable via side or rear Supply cable connections Secure Supply cable with Cable Clamp Adjust Timer overrun or Humidistat set point model dependant as shown ...

Страница 8: ...ogy Control Factor CTRL 1 00 0 95 0 65 0 65 Control Typology Manual Control Clock Control Local Demand Control Local Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs N A N A N A N A Mixing Rate of Non Ducted BVUs not intended to be equipped with one duct connection on either supply or extract ...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ...lect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your original supplier or nearest Vent Axia Centre by post or personal visit Please ensure that it is adequately packed and accompanied by a letter clearly marked Guarantee Claim stating the nature of the fault and pro...

Отзывы: