Installation and Wiring Instructions for the Tempra SELV Range of Heat Recovery Fans. 

 

  IMPORTANT: 
  READ THESE INSTRUCTIONS 
  BEFORE COMMENCING THE  
  INSTALLATION 

 

DO NOT install this product in areas where the following may be present or occur: 
 

  Excessive oil or a grease laden atmosphere. 

  Corrosive or flammable gases, liquids or vapours. 

• 

Ambient temperatures higher than 40°C or less than – 5°C. 

• 

Possible obstructions which would hinder the access or removal of the Fan. 

 

SAFETY AND GUIDANCE NOTES 

 

A. 

All wiring to be in accordance with the current I.E.E. Regulations, or the appropriate standards of           
your country and 

MUST 

be installed by a suitably qualified person. 

B. 

The Fan should be provided with a local isolator switch capable of disconnecting all poles, having a 
contact separation of at least 3mm. 

C. 

Ensure that the mains supply (Voltage, Frequency, and Phase) complies with the rating label. 

D. 

The electrical supply to this fan is 24v DC SELV from the transformer/controller. This means the fan 
may be installed within reach of a person using a fixed bath or shower, i.e. in a nearby wall. 
However, the fan must not be placed where it could be submerged in water or regularly exposed to 
direct water spray, e.g. from a shower head whether permanently fixed or movable. 

E. 

ONLY CONNECT TOGETHER THE PRODUCTS FROM THE Lo-CARBON TEMPRA SELV 
RANGE SINCE THE FANS ARE SPECIALLY DESIGNED TO WORK ON 24v DC AND ARE NOT 
COMPATIBLE WITH OTHER VENT-AXIA CONTROLLERS. DO NOT CONNECT MORE THAN 
ONE FAN TO THE CONTROLLER. 

F. 

The controller must not be installed in a shower cubicle or enclosure. It must be away from direct 
sources of water spray and out of reach of a person using a fixed bath or shower. Site away from 
direct sources of heat. 

G. 

The controller needs free air circulation and must not be covered with any insulating material such 
as might be in a ceiling or roof void. 

H. 

The Fan should only be used in conjunction with the appropriate Vent-Axia products. 

I. 

The fan should only be used in conjunction with fixed wiring. 

J. 

When the Fan is used to remove air from a room containing a fuel-burning appliance, 
precautions must be taken to avoid back-flow of gases into the room from the open flue of 
gas or other appliance. Ensure that the air replacement is adequate for both the fan and the 
fuel-burning appliance. 

K. 

  The Fan should not be used where it is liable to be subject to direct water spray for prolonged 

periods of time. 

L. 

The horizontal duct should be arranged to slope slightly downwards away from the Fan. 

M. 

This appliance is not intended for use by young children or infirm persons without supervision. 

N. 

Young children should be supervised to ensure that they do not play with the appliance. 

 

Disposal

  

This product should not be disposed of with household waste.  
Please recycle where facilities exist.  
Check with your local authority for recycling advice.

 

 
 

 
 

Содержание Lo-Carbon Tempra SELV HTP

Страница 1: ...ell LT 444370 Humidistat Timer Pullcord HTP 403837 Humidistat Timer Pullcord Long cell LHTP PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Lo Carbon SELV Tem...

Страница 2: ...NGE SINCE THE FANS ARE SPECIALLY DESIGNED TO WORK ON 24v DC AND ARE NOT COMPATIBLE WITH OTHER VENT AXIA CONTROLLERS DO NOT CONNECT MORE THAN ONE FAN TO THE CONTROLLER F The controller must not be inst...

Страница 3: ...n overrun timer and optional 3 minute delay on timer or internal humidistat adjustable 60 90 RH SELV Controller The controller can be installed surface or recess mounted using the supplied surface mou...

Страница 4: ...Door Fig 6 6 Feed flexible LV cable from PSU through one of the rear entry points or the side entry point as required And then the door Fig 7 8 7 Fit Chassis to wall with 4 fixing screws carefully ali...

Страница 5: ...Line up key on top of Heat Exchanger with slot in Chassis 10 Fit Heat Exchanger Retaining Clamp with the screws provided Fig 12 11 Close Door and connect 24V Supply as described in section B Wiring Ad...

Страница 6: ...e shut 15 Make good on outside wall with the wall Cover bezel provided ensure the arrow on the bezel is at the top Fix seal to the wall with a suitable sealant Apply sealant in outer groove on rear of...

Страница 7: ...r is suitable for connection to 220 240V 50Hz supply and 24V SELV to the fan The fan is a class ll double insulated product and MUST NOT be earthed 1 Select and follow the appropriate wiring diagram F...

Страница 8: ...utes by altering the adjuster on the control PCB 2 To INCREASE the operating time use a small screwdriver to turn the TIMER adjuster CLOCKWISE 3 To REDUCE the operating time use a small screwdriver to...

Страница 9: ...of dirt or other deposits 1 Remove 2 screws and lift off Cover Plate assembly Fig 21 22 2 Lift where indicated to engage hinges Fig 23 and open Door Fig 24 3 Remove Retaining Plate Carefully slide out...

Страница 10: ...LT HTP LHTP 3 445892 SELV Cover assembly P LP T LT HTP LHTP 4 444377 SELV power supply unit P LP T LT HTP LHTP 5 445889 Pullcord PCB P LP only 6 445890 Timer PCB T LT only 7 445891 HTP PCB HTP LHTP o...

Страница 11: ...0 0 70 Control Factor Control Typology CTRL Typology Control Factor CTRL 1 00 1 00 0 95 0 95 0 65 0 65 Control Typology Manual Control Manual Control Clock Control Clock Control Local Demand Control L...

Страница 12: ...ective the product will be repaired or at the Company s option replaced without charge provided that the product Has been installed and used in accordance with the instructions given with each unit Ha...

Отзывы: