Installation and Wiring Instructions for the 

Lo-Carbon PoziDry Compact Positive Ventilation Unit. 

 

     IMPORTANT: 
     READ THESE INSTRUCTIONS BEFORE COMMENCING THE INSTALLATION 

 
 

SAFETY AND GUIDANCE NOTES 

 
1. DO NOT install this product in areas where the following may be present or occur: 

1.1. Excessive oil or a grease laden atmosphere. 
1.2. Corrosive or flammable gases, liquids or vapours. 
1.3. Ambient temperatures higher than 40°C or less than -5°C. 
1.4. Possible obstructions which would hinder access or removal of the Fan. 
1.5  Relative humidity above 90% 
1.6  Sudden ductwork bends or transformations close to the Unit. 

2. All wiring to be in accordance with the current I.E.E. Regulations, or the appropriate standards of your country and 
MUST be installed by a suitably qualified person. 
3. The fan should be provided with a 3A fused, isolator switch capable of disconnecting all poles, having a contact 
separation of at least 3mm. 
4. Ensure that the mains supply (voltage, frequency, and phase) complies with the fan’s rating label. 
5. The fan should not be used where it is liable to be subjected to direct water spray. 
6. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental 
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning 
use of the appliance by a person responsible for their safety. 
7. Children should be supervised to ensure that they do not play with the appliance. 

 
 

A.

 

INTRODUCTORY NOTES

 

 
The Vent-Axia Lo-CARBON POZIDRY COMPACT is a positive input ventilation unit, designed to be installed in 
apartments taking fresh air from outside and supplying the air, filtered, into the building. 
 
The Lo-Carbon PoziDry Compact has two fully adjustable speed settings; ‘Trickle’ and ‘Normal’. These speeds are 
set on installation, but to aid commissioning there are pre-marked settings to suit the characteristics of the house 
 
The  unit  uses  a  sensor  to  monitor  the  incoming  air  temperature,  automatically  adjusting  the  air  volume  when 
necessary. 
‘Trickle’ speed is automatically selected when the ambient incoming temperature is less than 18°C.

 

‘Normal’ is automatically selected when the ambient incoming temperature is between 18°C and 27°C. 
If the ambient incoming air temperature exceeds 27°C, the unit will automatically switch to standby (no airflow, LED 
displaying one segment). The standby power consumption is 2W. 
 
In the case of the integral heater version, the heater element is automatically activated when necessary and tempers 
the supply air to between 10°C and 20°. This temperature can be set using the adjuster located between the Trickle 
and Normal speed adjusters. 
 
By wiring in a switch on installation it is possible to switch off the heater if its use is not necessary.  See wiring 
section. 
 
The Vent Axia Lo-Carbon PoziDry has the capability to run on Purge setting (maximum speed); this is particularly 
useful for installations where condensation has been a severe problem in order to help dry the property out.  Mould 
will turn to a dry grey powder when dried out and should be vacuumed up. 
 
To enable ‘Purge’ speed, connect a switched live connection to the LS core on the integral mains flying lead.  See 
WIRING on pages 5 and 6 and the notes on page 7. 
 
The unit also incorporates a non-resettable elapsed hours counter. 
 
 
 

Содержание Lo-Carbon PoziDry Compact Series

Страница 1: ...THE ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Lo Carbon PoziDry Compact Positive Pressure Ventilation Unit Stock Ref N Pozidry Compact 444767 With integral heater 444076 Without heater Installatio...

Страница 2: ...t ventilation unit designed to be installed in apartments taking fresh air from outside and supplying the air filtered into the building The Lo Carbon PoziDry Compact has two fully adjustable speed se...

Страница 3: ...d re fix to the other side of the unit in place of the metal front cover Carefully cut out the skinned area on the white plastic cover where the cable gland will now lie Rear entry inlet If rear entry...

Страница 4: ...bles when the terminal cover is replaced The switch cable and cable gland which are not supplied should be rated at 3 amps TO CONNECT A POWER SUPPLY Ensure the local AC power supply is isolated The pr...

Страница 5: ...le controls the heat setting for integral heater version 444767 WARNING THE BLUE POTENTIOMETER DRIVER SUPPLIED WITH THE UNIT MUST BE USED TO ADJUST THE POTENTIOMETERS Turning the potentiometers clockw...

Страница 6: ...er may be gently cleaned with a vacuum cleaner or washed in a soapy water solution and allowed to air dry before re fitting Do not dry the filter in a tumble dryer Spare filters are available from Ven...

Страница 7: ...Multi Speed Multi Speed Type HRS Recuperative Regenerative None None None Thermal Eff NA if none N A N A Max Flow Rate m3 h 122 40 122 40 Max Power Input W Max Flow Rate 49 80 49 80 LWA Sound Power Le...

Страница 8: ...n the event of any part being found to be defective the product will be repaired or at the Company s option replaced without charge provided that the product Has been installed and used in accordance...

Отзывы: