About Advanced Features & Operation
29
Deadband Operation
Controls up to two Heat and two Cool stages.
The
1st Stage
of heat or cool is turned on when:
(A)
The temperature spread from the setpoint is equal to or greater
than:
the setpoint plus the 1st stage deadband.
This 1st stage dead-
band is adjustable from 1-6 degrees and the default is two degrees.
The
2nd Stage
of heat or cool is turned on when:
(A)
The 1st Stage has been on for a minimum of two minutes
(default setting).
AND
(B)
The temperature spread from the setpoint is equal to or greater
than:
the setpoint plus the 1st stage deadband, plus the 2nd stage
deadband.
This 2nd stage deadband is adjustable from 0 - 10
degrees.