background image

7

4.2 C

ONNECTING

D

UCTS TO THE

U

NIT

Insulated flexible ducts:

Use the following procedure for connecting the insulated flexible ducts to the ports on the
unit (exhaust to outside and fresh air from outside).

a)

Pull back the insulation to expose the flexible duct.

b)

Connect the interior flexible duct to the opening using a duct tie.

c)

Carefully seal the connection with duct tape.

d)

Pull the insulation over the joint and tuck it between the inner and outer rings of double collar.

e)

Pull the vapor barrier over the insulation and over the outer ring of the double collar.

f)

Apply duct tape to the joint making an airtight seal. Avoid compressing the insulation

when you pull the tape tightly around the joint. A compressed insulation loses its R value
and also causes water dripping due to condensation on the exterior surface of the duct.

a)

b)

c)

d), e)

f)

VJ0001

VJ0002

VJ0003

VJ0004

VJ0005

CAUTION

Make sure that the vapor barrier on the insulated ducts does not tear
during installation.

4.3 I

NSTALLING

E

XTERIOR

H

OODS

Choose an appropriate location for installing the exterior hoods:

• A distance of at least 6 feet (1.8 m) one from the other
• A distance of 18 inches (457 mm) from the ground

Make sure the intake hood is at least 6 feet (1.8 m) away from any of the following:

• dryer exhaust, high efficiency furnace vent, central vacuum vent
• gas meter exhaust, gas barbecue-grill
• any exhaust from a combustion source
• garbage bin and any other source of contamination

Refer to Figure 4 for connecting the insulated ducts to the hoods. An “Anti-Gust Intake
Hood” should be installed in regions where a lot of snow is expected to fall.

VD0034

Figure 4

Exhaust hood

Optional duct 

location

Intake
hood

6ӯ

(152 mm)

18” 
(457mm)

18” (457mm)

18” (457mm)

6’ (1.8m)

6’ (1.8m)

Содержание FAE115

Страница 1: ...your installer 04423 07 04 00 Furnace Air Exchanger with Heat Recovery CANADIAN MODELS US MODELS FAE115 vFAE115 uFAE115 FAE115M vFAE115M uFAE115M INSTALLER LEAVE THIS MANUAL TO HOMEOWNER Customer Ser...

Страница 2: ...accident improper maintenance or repairs made by other than Venmar Ventilation Inc or v nEE Canada or c a faulty installation or installation contrary to recommended installation instructions The dur...

Страница 3: ...ting and Mounting the Unit 6 4 2 Connecting Ducts to the Unit 7 4 3 Installing Exterior Hoods 7 4 4 Connecting the Drain 8 5 0 AIR FLOW BALANCING 9 6 0 YOUR UNIT 11 6 1 Unit Description 11 6 2 Heat Re...

Страница 4: ...3 Canada 04455 US 04434 VL0004 2 2 1 1 3 NOTE Unit in normal position Can also be installed upside down FAE115M uFAE115M vFAE115M FAE115 uFAE115 vFAE115 2 0 TECHNICAL DATA 2 1 AIR DISTRIBUTION VF0014...

Страница 5: ...ows cfm Pressure in water gauge VG0031A Stale air Fresh air 0 05 0 15 0 25 110 2 3 DIMENSIONS VK0028 22 562 573 mm 27 250 692 mm 1 500 38 mm 2 225 57 mm 20 000 508 mm 14 500 368 mm 6 000 152 mm NOTE T...

Страница 6: ...6 6 18 Figure 2 4 0 INSTALLATION 4 1 LOCATING AND MOUNTING THE UNIT Choose an appropriate location for the unit So as to provide easy access to the interior cabinet Close to an exterior wall so as to...

Страница 7: ...water dripping due to condensation on the exterior surface of the duct a b c d e f VJ0001 VJ0002 VJ0003 VJ0004 VJ0005 CAUTION Make sure that the vapor barrier on the insulated ducts does not tear duri...

Страница 8: ...op in the tube to prevent the unit from drawing unpleasant odors from the drain source Make sure this loop is situated BELOW the T as shown This will prevent water from being drawn back up into the un...

Страница 9: ...w Collars VP0005 VP0008 A 36 914mm 12 304mm OR B 12 304mm F G Flow collar Seal all the unit ductwork with tape Close all windows and doors Turn off all exhaust devices such as range hoods dryers and b...

Страница 10: ...is less than the reading at A then go back and adjust the exhaust balancing damper G to equal the fresh air flow 5 If the furnace has a low speed option select the low speed option and check if the fr...

Страница 11: ...is heat recovery process is accomplished in such a way that the stale air is never mixed with the fresh air Example in winter VF0015 INSIDE OUTSIDE STALE AIR TO OUTSIDE 25 C 77 F FRESH AIR FROM OUTSID...

Страница 12: ...t turn off your unit and unplug it in the following situation If you owns a FAE115 a uFAE115 or a vFAE115 model this Section doesn t concern your unit Please refer to the next Sections This wall contr...

Страница 13: ...ishwasher is possible but the aluminum frame might tarnish 4 Remove and clean the heat recovery core Let it soak in a mixture of cold or lukewarm water and mild soap dishwashing liquid Rinse thoroughl...

Страница 14: ...plugged in models FAE115M uFAE115M See if the transformer is receiving and vFAE115M only power from the house circuit breaker 2 Condensation on windows Adjust the humidity control knob as Air too hum...

Отзывы: