3. INSTALLATION 

(

CONT

D

)

3.6 I

NSTALLING

 

THE

 D

UCTWORK

 

AND

 R

EGISTERS

 3.6.1 

F

ULLY

 D

UCTED

 S

YSTEM

 (

AS

 

ILLUSTRATED

 

IN

 S

ECTION

 2.1)

 

Stale air exhaust ductwork

 

•  Install the stale air exhaust registers where the contaminants are produced: kitchen, living room, etc. Position the registers as far 

from the stairway as possible and in such a way that the air circulates in all the lived-in spaces in the house.

 

•  If a register is installed in the kitchen, it must be located at least 4 feet (1.2 m) from the range.

 

•  Install the registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install them in the ceiling.

 

•  If possible, measure the velocity of the air flowing through the registers. If the velocity is higher than 400 ft/min (122 m/min), then 

the register type is too small. Replace with a larger one.

 

Fresh air distribution ductwork

 

•  Install the fresh air distribution registers in bedrooms, dining rooms, living room and basement.

 

•  Keep in mind that the fresh air registers must be located as far as possible from the stale air registers.

 

•  Install the registers either in the ceiling or high on the walls with air flow directed towards the ceiling. (The cooler air will then cross 

the upper part of the room and mix with room air, before descending to occupant’s level.)

 

•  If a register must be floor installed, direct the airflow up the wall.

    WARNING

!

Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas 
furnace, a gas water heater or a fireplace.

 3.6.2 

C

ENTRAL

 D

RAW

 P

OINT

 S

YSTEM

 (

AS

 

ILLUSTRATED

 

IN

 S

ECTION

 2.2)

 

Stale air exhaust ductwork

 

Same as for Fully Ducted System, described on point 3.6.1

 

Fresh air distribution ductwork

 

•  There are 2 methods for connecting the unit to the furnace/air handler:

 

Method 1: Supply side connection

 

•  Cut an opening into the furnace supply duct at least 18 inches (0.5 m) from the 

furnace/air handler.

 

•  Connect this opening to the 

Fresh air distribution

 port of the unit (use 

metal 

duct

, see figure at right).

 

•  Make sure the unit duct forms an elbow inside the furnace/air handler ductwork.

 

•  If desired, interlock (synchronize) the furnace/air handler blower operation (see 

Section 5 ELECTRICAL CONNECTION TO FURNACE).

 

Method 2: Return side connection

 

•  Cut an opening into the furnace return duct not less than 10 feet (3.1 m) from the 

furnace/air handler (A+B).

 

•  Connect this opening to the 

Fresh air distribution

 port of the unit (see figure at 

right).

 

NOTE:  For Method 2, it is not essential that the furnace/air handler runs when the 

unit is operation, but we recommend it. If desired, interlock (synchronize) 
the furnace/air handler blower operation (see Section 5 ELECTRICAL 
CONNECTION TO FURNACE).

    WARNING

!

When performing duct connections, always use approved tools and materials. Respect all corresponding laws and 
safety regulations. Please refer to your local building code.

CAUTION

When performing duct connections to the furnace supply duct, this duct must be sized to support the additional 
airflow produced by the unit. Also, the use of metal duct is highly recommended.

VJ0061

M

ETAL

 

DUCT

M

INIMUM

 18"

(0.5 

M

)

B

A

VJ0062

A+B = 

NOT

 

LESS

 

THAN

 10’ (3.1 

M

)

Содержание 60H-V+

Страница 1: ...V These products earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US EPA They meet ENERGY STAR requirements only when used in Canada 21781...

Страница 2: ...prong Do not use an extension cord 8 Do not install in a cooking area or connect directly to any appliances 9 Do not use to exhaust hazardous or explosive materials and vapors 10 When performing inst...

Страница 3: ...IT 10 3 8 INSTALLING TWO EXTERIOR HOODS 11 3 9 CONNECTING THE DRAIN 11 4 CONTROLS 12 15 4 1 UNITS BOOTING SEQUENCE 12 4 2 INTEGRATED CONTROL 12 4 3 SPEED AND DEFROST SETTINGS FOR AVS E15 ECM ERV AVS E...

Страница 4: ...MIN NORMAL DEFROST CYCLE MIN EXTENDED DEFROST CYCLE MIN C F DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OPERATION BETWEEN EACH DEFROST DEFROSTING OP...

Страница 5: ...one level require at least one exhaust register at the highest level See figure at right 2 2 CENTRAL DRAW POINT CONNECTION TO A FORCED AIR SYSTEM Stale air coming from the registers located at the hig...

Страница 6: ...H V ECM HRV units have one front door and one back door while the AVS E15 HRV AVS E10 HRV 90H V and the 60H V units only have one door For these last models the unit door can be relocated on the back...

Страница 7: ...onnect these registers to a main duct which will connect to the unit high speed performance value of 140 cfm What size of duct should I use for the main exhaust duct and for both end branches leading...

Страница 8: ...gas furnace a gas water heater or a fireplace 3 6 2 CENTRAL DRAW POINT SYSTEM AS ILLUSTRATED IN SECTION 2 2 Stale air exhaust ductwork Same as for Fully Ducted System described on point 3 6 1 Fresh ai...

Страница 9: ...on the furnace blower must be in operation when the unit is in operation VJ0063 A B METAL DUCT A B NOT LESS THAN 10 3 1 M MINIMUM 18 0 5 M B A VJ0064 MINIMUM 3 0 9 M A B NOT LESS THAN 10 3 1 M Stale a...

Страница 10: ...the insulation over the joint and tuck in between the inner and outer rings of the double collar 4 Pull down the vapor barrier shaded part in illustrations below over the outer ring to cover it comple...

Страница 11: ...r it is recommended for climates where the outdoor temperature typically remains below 25 C 13 F over a 24 hour period for several days in a row combined with an indoor humidity of 40 or higher VO0258...

Страница 12: ...uence the integrated control LED will light GREEN unit set in normal defrost or amber unit set in extended defrost for 3 seconds and then will shut off for 2 seconds After that the LED will light RED...

Страница 13: ...tegrated control is in CFM setup mode HIGH speed Every 3 seconds the LED will blink RED the number of times corresponding to the chosen speed range See table below NOTE Anytime in setting process if t...

Страница 14: ...tribution panel Use the terminal connector included in the installation kit to perform the electrical connection for main and optional wall controls Check if all wires are correctly inserted in their...

Страница 15: ...the terminals of the furnace interlock standard wiring Only use the low voltage class 2 circuit of the furnace blower control For a furnace connected to a cooling system On some older thermostats ene...

Страница 16: ...L listed CSA Certified line fuse 3A 3AG Type 2 If any of the original wire as supplied must be replaced use the same equivalent wire 3 Field wiring must comply with applicable codes ordinances and reg...

Страница 17: ...ptional see notes 3 4 VE0086A Critical characteristic JU1 1 2 3 MED HI 3 2 1 HI MED JU1 FAN MOTORS SPEED SELECTION NOTES 1 Use specified UL listed CSA Certified line fuse 3A 3AG Type 2 If any of the o...

Страница 18: ...otor J5 1 J5 3 J7 2 J7 1 J4 1 J4 3 J6 2 J6 1 K1 K3 K2 J9 1 J9 2 J9 3 J4 2 J9 4 Exhaust fan motor capacitor Supply fan motor capacitor J8 1 J8 2 J8 4 J8 5 K4 J12 2 J12 1 A1 Damper motor J3 2 J3 1 J2 2...

Страница 19: ...ation at right Be sure to connect the tubes to their appropriate high low fittings If the gauge drops below zero reverse the tubing connections 4 Note the CFM value from balancing chart on unit 5 Repe...

Страница 20: ...207 18207 18207 18207 18207 18207 18207 3 EXHAUST DAMPER SPRING 1 18221 18221 18221 18221 18221 18221 18221 18221 4 MOTOR ASSEMBLY 2 18198 18198 18197 18197 18198 18198 18197 18197 5 BALANCING TOOL 2...

Страница 21: ...he wires are correctly connected Inspect every wire and replace any damaged ones If wires are hidden into walls test the control using a shorter wire 2 There is no outside temperature displayed on Alt...

Страница 22: ...ED LED At power up LED lights up in RED and there is a clicking sound coming from electrical compartment but damper does not move Ice or other things hindering the damper movement J12 unconnected or b...

Страница 23: ...otor capacitor may be defective Tranformer wire s bad connection The transformer or the PCB may be defective Plug exhaust motor to J4 connector and supply motor to J5 connector If supply motor works b...

Страница 24: ...g the button and LED flashes RED after 20 seconds The J4 connector may be misconnected or there may be a bad contact The JU1 jumper may be mispositioned The PCB may be defective The motor may be defec...

Отзывы: