background image

7.0 Air Flow Balancing 

(cont’d)

4.

Move tubing to the other side of the unit (location B in Figure 20 on page 21) and note reading. 
Adjust the fresh air balancing damper F until the reading at B is approximately the same as the 
reading at A. 

If the reading at B is less than the reading at A then go back and adjust the exhaust balancing 
damper G to equal the fresh air flow.

5.

Remove flow collars and reconnect the duct, then, seal with duct tape. Write the required airflow information on a label and stick it 
near the unit for future reference: (date, maximum speed airflows, your name and phone number and business address).

NOTES:
• Most flow collar kits provide a conversion chart situated on the collar which enables you to convert magnehelic gauge readings to 

equivalent cfm values.

• A difference of ± 10 cfm ( ± 0.015 inches water gauge) between the 2 readings is considered balanced.
• If you are using only one flow collar, then, after completing the first reading, transfer this measuring device to the other side of the 

unit and take the second reading.

Balancing procedure 

(cont’d)

LOW

HIGH

FLOW

LO

VP0004

24

8.0 Maintenance

1)

Motor: The motor is factory lubricated for life. Lubricating the bearings is not recommended.

2)

The heat recovery core must be handled with care. We recommend that it be washed once a year, following the season of most
intense use, in order to insure maximum efficiency of the plastic partitions.
Allow the heat recovery core to soak for 3 hours in a solution of warm water and mild soap. Rinse under a heavy stream of water.

3)

The air filters are washable. Under normal conditions, we recommend that they be washed every 3 months.
Use a vacuum cleaner to remove the heaviest portion of accumulated dust.
Then wash in lukewarm water.

4)

Regularly check the screen on the exterior intake hood and clean when necessary. Also check during very cold weather because
ice may grow on the screen located at the exterior intake hood.

8.1 Regular Maintenance

Annual service should include:

1)

Cleaning filters, heat recovery core and the exterior air intake/exhaust hood.

2)

Cleaning the wheels and the blower blades.

3)

Cleaning the condensation tray with soapy water (make certain that the drain is not clogged).

4)

Running the system and checking the different operating modes.

5)

Measuring and calibrating rates of flow using the procedure descriptions in section 7.0.

8.2 Prolonged Maintenance

WARNING

Risk of electric shock. Before performing any maintenance or servicing, always disconnect the unit from its
power source.

!

CAUTION

Hot water and a strong detergent will damage the heat recovery core.

CAUTION

Even a partial blocking of this air vent could cause the unit to malfunction.

CAUTION

Because the unit is suspended, two people are recommended to remove or install the heat recovery core. Do not
hold the heat recovery core using its plastic extrusions as handles.

Содержание 1.3 HE

Страница 1: ...Installation Manual FOR MODELS VENMAR 1 3 1 8 2 6 HE VENMAR 3055 5585 COMPACT v nEE 1000 2000 3000 HE 10 2004 04435 VB0021...

Страница 2: ...3 Dimensions 12 3 4 Specifications 12 4 0 Typical Installations 13 4 1 Fully Ducted System 13 4 2 Exhaust Ducted System 13 4 3 Simplified 13 5 0 Installation 14 5 1 Locating and Mounting the Unit 14...

Страница 3: ...om 1 10 cfm Bedroom 2 10 cfm Bedroom 3 10 cfm Washroom 1 10 cfm Washroom 2 10 cfm Basement 20 cfm Total 120 cfm high speed ASHRAE Standard 62 2001 Volume of basement 7 360 ft3 Volume of main floor 7 3...

Страница 4: ...0 Service 2 1 3D Drawing for Venmar 1 3 HE Venmar 3055 Compact Venmar 5585 Compact and v nEE 1000 HE 2 1 5 6 6 7 8 9 10 11 12 13 14 15 16 17 25 18 19 19 8 21 23 24 26 27 28 29 30 32 20 31 25 22 3 4 VL...

Страница 5: ...2 00703 00703 00703 00703 17 Lock Nut 10 24 01689 01689 01689 01689 18 Core 13 5 x 13 5 x 13 01817 01403 01403 18 Core 13 5 x 13 5 x 7 875 01402 19 Filter 12 15 16 x 13 1 2 x 3 8 01234 01234 01234 19...

Страница 6: ...6 2 3 3D Drawing for Venmar 1 8 HE Venmar 2 6 HE v nEE 2000 HE and v nEE 3000 HE VL0006 2 3 9 10 11 14 15 16 17 18 8 7 19 4 5 6 12 13 1 3 18 17 6 2 0 Service cont d...

Страница 7: ...00 01277 01277 01277 01277 10 Insulated Triangular Damper 12452 12452 12452 12452 11 Door Assembly 13433 13433 12661 12661 12 Door Latch 00886 00886 00886 00886 13 Door Keeper 00887 00887 00887 00887...

Страница 8: ...agrams of Air Flows 8 VF0010 VF0003 during air exchange during defrost FILTERED AIR TO BUILDING STALE AIR FROM BUILDING Figure 2 VF0002 Figure 1 FILTERED AIR TO BUILDING STALE AIR FROM BUILDING VF0025...

Страница 9: ...95 50 106 109 26 HEATING COOLING Model numbers Venmar 1 8 HE and v nEE 2000 HE Electrical requirements 120 volts 2 5 Amps Exhaust Air Transfer Ratio 0 06 VG0006A VENTILATION PERFORMANCE External Stati...

Страница 10: ...2 89 189 152 71 76 0 03 25 13 56 119 131 67 81 0 20 25 13 55 117 130 67 25 13 Total Recovery Efficiency 35 95 56 119 108 23 35 95 75 160 132 23 HEATING COOLING Model number Venmar 3055 Compact Electri...

Страница 11: ...5 267 128 272 99 211 200 0 8 116 246 118 251 93 198 225 0 9 103 219 105 223 84 179 250 1 0 81 173 83 177 74 157 275 1 1 63 133 64 136 33 70 See NOTE on page 18 Point 5 5 2 External Static Pressure Pas...

Страница 12: ...NMAR 3055 COMPACT VENMAR 1 3 HE VENMAR 1 8 2 6 HE VENMAR 5585 COMPACT V NEE 2000 3000 HE V NEE 1000 HE Weight 70 lb 32 kg 80 lb 36 3 kg 140 lb 63 5 kg Drain diameter 1 2 inch 12 mm 1 2 inch 12 mm 1 2...

Страница 13: ...Fresh air is supplied to the cold air return or the supply duct of the furnace The use of bathroom fans and range hood is required to better exhaust stale air Homes with more than one level require a...

Страница 14: ...source 110 V standard outlet Hang the unit to ceiling joists with the 4 chains and springs See Figure 8 5 1 Locating and Mounting the Unit CAUTION Make sure the unit is level VD0027 a Follow the instr...

Страница 15: ...ble value for a 4 duct is 60 cfm VI0001 end branches main branch 6 140 cfm 5 70 cfm 140 cfm Figure 9 4 42 cfm 6 129 cfm 5 65 cfm 5 64 cfm 6 93 cfm 5 6 7 7 6 6 6 4 4 4 4 7 222 cfm 4 42 cfm 6 84 cfm 6 9...

Страница 16: ...e furnace installation must be done in accordance with all applicable codes and standards Please refer to your local building code Method 2 return side connection Cut an opening into the furnace retur...

Страница 17: ...ecommend it Figure 14 Figure 13 minimum 18 0 5 m VD0174 A B C VD0030 A B C A B C not less than 10 3 1 m 3 0 9 m minimum CAUTION If using Method 2 make sure the furnace blower operation is synchronized...

Страница 18: ...on the insulated ducts does not tear during installation VJ0013 VJ0014 VJ0015 VJ0004 VJ0005 5 5 2 For models Venmar 2 6 HE and v nEE 3000 HE Use the following procedure for connecting the insulated f...

Страница 19: ...iency furnace vent central vacuum vent Gas meter exhaust gas barbecue grill Any exhaust from a combustion source Garbage bin and any other source of contamination Refer to Figure 15 for connecting the...

Страница 20: ...water from being drawn back up into the unit in case of negative pressure Run the tubing to the floor drain or to an alternative drain pipe or pail Be sure there is a slight slope for the run off 12 3...

Страница 21: ...connected to cooling system On some older thermostat energizing the R and G terminals at the furnace has the effect of energizing Y terminal at the thermostat and thereby turning on the cooling syste...

Страница 22: ...is energized 0 0 0 1 1 1 1 0 1 0 1 0 IN OUT OUT OUT IN IN OUT 10 30 10 20 10 15 6 60 6 32 6 20 VE0013A FUNCTION TABLE T T MODE RELAY A A K1 K2 K4 K5 Intermittent Exchange Low Exchange High 0 0 0 1 1 1...

Страница 23: ...fore or after a 90 elbow at least 12 304 mm away from a register Figure 20 NOTE To get the best ventilation performance from Venmar 2 6 HE and v nEE 3000 HE refer to Point 5 5 2 on page 17 23 Balancin...

Страница 24: ...intense use in order to insure maximum efficiency of the plastic partitions Allow the heat recovery core to soak for 3 hours in a solution of warm water and mild soap Rinse under a heavy stream of wat...

Страница 25: ...s an enthalpic recovery core energy recovery core the indicators flashes then the TBI mode is probably activated See section 7 5 every 8 seconds The wires may be in Ensure that the color coded wires h...

Страница 26: ...make sure the unit is adjusted for low speed operation turn all dehumidistats maximum counterclockwise Wait 3 minutes The unit should switch to high speed and the damper at the fresh air intake port...

Отзывы: