Low battery:

 

       control tension lower than 22 Vdc 

Battery ok:

 

       tension included between 22 Vdc and 28,5 Vdc 

Overcharged battery:  

tension over 28,5 Vdc 

Mains:

 

 

       presence of line tension 230 Vac 

Failure 

:   

       Led of general failure, it activates in case of: 

 

 

       Absence of 230 Vac mains 

 

 

       Faulty fuse 

 

 

       Loss of battery charge 
        Low battery 

                       Overcharged battery 

       Disconnected battery 

                       Battery resistance > 1 ohm 

 

 

 
 
 
 
 
 
 
 

 

 
 
 
 
 

 

The power supply has been certified using YUASA NP 17-12 batteries 

 

Security Instructions 

 

1. 

For mains input and DC o alarms, use separate holes on the bottom of the box to pass the cables. Furthermore, the material of the 
joint pipe/box must have a flammability class V-1 or better  

2. 

The relay contact “GUASTO” and “RETE RIT ” must be connected only to circuits operating with SELV tension. 

3. 

For AC supplying, provide a 6 A protection bi-pole magneto-dynamic switch, easy to access 

4. 

The wires must have a section of 1,5 mm and be equipped with adequate buttonholes where they are subject to pressure contact. 

5. 

The installation of the power supply must be carried out by qualified personnel aware of the security norms EN60950 and concerning power 
supplies CEI-64-8. 

IMPORTANT: In case of mains failure and general anomaly condition, a technical intervention should be carried out within 48 hours to 
avoid the complete discharge of the battery.   

 

INSTALLATION 

 

MECHANICAL MOUNTING 

 
This device has to be mounted on vertical stable walls, suitable to support the power supply, by means of 4 6 mm screws, for spacers and screws on 
the 4 holes on the bottom of the box. The battery must be fixed using the strap given within. 

 

ELECTRICAL CONNECTION 

 
Connect the power supply unit to the mains 230 Vac by use of a differential magneto-thermic bipolar 6 A. switch (minimum distance between contacts 
3 mm) aimed to protect the line against possible short circuit and operator against current leakage.  
 
IMPORTANT: use different cables-passes and pipes for ac supplying input (mains 230 Vac) and dc o alarms (SELV) 

– see pict. 2 

 
The minimum section recommended for ground connection is 1,5 mm. 
For connections refer to pictures 1 and pict. 2. In these pictures the following important steps are shown: 

 

Output Terminals (Power supply unit) 

 

Output terminal board (power supply)  

BAT + 

Positive pole of the battery 

OUT 2 + 

Positive output towards charge 2 

BAT - 

Negative pole of the battery 

OUT 2 - 

Negative output towards charge 2 

OUT1 + 

Positive output towards charge 1 

OUT 3 + 

Positive output towards charge 3 

OUT1 - 

Negative output towards charge 1 

OUT 3 - 

Negative output towards charge 3 

 

Terminal board Alternated Supplying 

 

connection to line (230 Vac)           

 Protection ground connection           N   connection to neutral 

Checks and Adjustments  

 

Controls are shown Below (P1 and P2) are adjusted at factory and 

must in no way be altered by the operator. 

Tampering of these controls automatically means the lost of the warranty. 

 

P1 - Potentiometer for adjustment of the output tension 

P2 - Potentiometer for adjustment of the output current limit.  

 

FRONT PANEL SIGNALS  

 

Indications on the front panel (located on the door of the power supply) 

 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

Mechanical Specifications 

Size in mm. 

width  310 ;   height  373 ;  depth 170 

Weight 

9,5  Kg 

Environmental Specifications 

Operating temperature 

from -5 °C   to +40   °C 

Humidity  

from 5%  to  93%  ±

 2 %

 

cooling 

air cooling 

Installation site 

sheltered from atmospheric agents 

FUSES 

F1 

Fuse of the 230 Vac supplying input (T3,15 AL 250V) 

F5 

Fuse related to output OUT 2 (T3,15 AL 250 V) 

F3 

Battery fuse (T6,3 AL 250 V) 

F6 

Fuse related to output OUT 3 (T3,15 AL 250 V) 

F4 

Fuse related to output OUT 1 (T3,15 AL 250 V) 

F8 

Fuse of protection over-tension (T6,3 AL 250 V) 

   Low battery   Battery OK  Overcharged      Mains      Failure 

       battery 