MA-AL-T272-01-01 Manual TUL272 eng rev1 

 

   Rev.1 Page 3 of 4 

 
ALTERNING POWER SUPPLY TERMINALS 

 

L

   line connection ( 230 Vac)       

 

land protection connection   

N

     neutral connection 

 

Check and adjustments 

 
P1 e P2 check are calibrated from factory and 

must not be modified by operators

.  Tampering of 

these checks will cause guarantee loss.

 

 

FRONT PANEL SIGNALS  

 

 
 
 
 
 

 
 

- Low Battery

:

   

              -

 check tension lower than 22 Vdc 

- Battery OK:

   

 

- tension between 22 Vdc and 29 Vdc 

- Overloaded Battery:

               - tension higher than 29 Vdc 

- Power Supply: 

 

- line tension 230 Vac 

- Failure:

 

 

 

- General failure pilot lamp: light up in case of: 

 

 

 

 

  Low battery 

– Overloaded battery – Tension absence 230 Vac – 

 

 

 

 

  Fuse failure 

– Battery charge loss 

 

 

 

 

 

 

 

 

 

Control circuit connection (placed behind frontal panel)

  

 

See Pict. 2 

 

“Tension absence” Relay – Terminals 10 – 11 – 12 (working with SELV tension) 

 
Output relay for tension absence with programmable delays of activation: 
 
Jumper on 

JP1

  to get a 15 seconds delay 

Jumper on  

J1

 to get a 15 minutes delay 

Jumper on  

J2

 to get a 60 minutes delay 

Jumper on  

J3

 to get a 120 minutes delay 

Jumper on  

J4

 to get a  240 minutes delay

 

 

NOTE

Without any jumper connected, the “Tension absence “ relay will be never activated.  

 

“Failure signaling” relays – Terminals 4 – 5 – 6 (working with SELV tension) 
 
Output relay for failure signaling, activated in case of: 
Low Battery (tension lower than 22 Vdc) 
Overloaded Battery (tension higher than 29 Vdc) 
 

MAINTENANCE 

 
In order to avoid power supply unit malfunctions, periodic and preventive maintenance must be 
executed by qualified staff. Maintenance is recommended each 6 months. During all check 
operations, there is the possibility of alarms, so coordination with control central is suggested. 

 
-  Check connection status of power supply line 230 Vac. 
-  Check connection status of alarm lines and relative screening. 
-  Check connections to battery. They must be not oxidized and well fastened.  
-  Check output tension on load (see Electrical Specifications) 
 