OPERATION

User manual

WALL-MOUNTING ELECTRONIC THERMOSTATS

 

Read all instructions carefully

DIMENSIONS

WIRING DIAGRAMS

LEGEND

INSTALLATION

2

Advanced programming

Reset

Setpoint modification

Depleted batteries signal

Error messages

Auxiliary input configuration 

(only battery models)

Backlighting management

Night reduction 

C

O

M

NA

NC

N

L

230V

~

C

O

M

NA

NC

AUXILIARY

INPUT

Thalos 230

Thalos

EST

  

“Room temperature” 

Field

  

“Off” 

Field

  

“Heating activation” 

Field

  

“Cooling activation” 

Field

  

“Night reduction activation” 

Field

  

Key 

   

” Decreases the selected field - active night reduction

  

Key 

   

” Increases the selected field

Thalos Key 230

Thalos Key

Switch off

Normal operation

Note: in heating mode (winter), if the Thalos Key is off, it adjusts the antifreeze 

Toff

 

temperature in order to prevent the system freezing.

Toff

 can have values from 1 to 50° C or be excluded; in this case any minimum 

temperature is guaranteed.

Replace the batteries as soon as possible! 

Dispose of the batteries in 

the appropriate recycling 

containers.

Occurs in case of probe failure.

In this case the adjustment is inhibited and the relay 

contacts remain in COM-NC position.

Occurs for the following values of measured temperature:

t < 0°C

t >50°C

Unhook and re-hook the thermostat from the base (battery models) 

or remove and restore power (230V models).

During the flashing of the backlighting press the keys   and   

until the display shows 

Def

.

Modification of the desired temperature (setpoint), 

 to increase     to decrease

Normal operation

heating on (

   

)

or

3 sec.

3 sec.

19.8

19.9

...

Default values

Heating setpoint 

21 °C

Cooling setpoint 

25 °C

Minimum settable setpoint - 

L0

2 °C

Maximum settable setpoint - 

Xi

50 °C

Operating mode 

 (heating)

Antifreeze temperature

6 °C

Type of command

On /Off

Differential

0.3 °C

Auxiliary input

DIG

Password

- - - (desabled)

3 sec.

3 sec.

press

(only battery models)

“Night reduction” function reduces the 

programmed setpoint by 3 °C.

Press for 3 seconds the key 

 to 

activate (or deactivate, if already active) 

the night reduction.

When the night 

reduction is active, the 

display shows the

symbol  .

Vemer S.p.A.

I - 32032 Feltre (BL) • Via Camp Lonc, 16

Tel +39 0439 80638 • Fax +39 0439 80619
e-mail: [email protected]  -  web site: www.vemer.it 

 

Mod.

 THALOS KEY

Series of wall mounting electronic thermostats for temperature control both in

heating and cooling.

They perform actions of type 1B and are intended for operating in rooms with 

Pollution Degree 2 and Overvoltage Category III (EN60730-1).

• 

 Thalos  Key

 battery powered has an auxiliary input for a temperature probe 

configuration or of an external contact to reduce setpoint of 3 °C.

•  

Thalos Key 230

 AC-powered. 

Code  

Model  

Description

VE718300

 

Thalos Key Bianco 

Battery Thermostat with auxiliary input

VE719100

 

Thalos Key Nero 

Battery Thermostat with auxiliary input

VE720900

 

Thalos Key 230 Bianco  230V Thermostat

VE721700

 

Thalos Key 230 Nero 

230V Thermostat

SAFETY WARNINGS

 

 During product installation and operation it is necessary to observe the 

following instructions:

1)    The instrument must be installed by a qualified person, in strict compliance 

with the connection diagrams.

2)   Do not power or connect the instrument if any part appears to be damaged.

3)    After installation, inaccessibility to the connection terminals without appropriate 

tools must be guaranteed.

4)    The instrument must be installed and activated in compliance with current 

electric systems standards.

5)   Before accessing the connection terminals, verify that the leads are not live.

6)    In the electrical system of the building where the instrument must be installed, 

a switch and a protection device from the overcurrents must be present (for 

Thalos Key 230 models only). 

TECHNICAL SPECIFICATIONS

•   Power supply Thalos Key:  

– 2 alkaline batteries 1.5V (AAA type))

     

– battery life: 12 months

     

– low battery indication

•  Power supply Thalos Key 230:   – 230Vac (-15% ÷ +10%) 50/60Hz 

     

– max absorption: 6 VA / 230Vac

•  Wall mounting or to coverage the in-built three-modules box

•  Terminals Thalos Key:

  – 3 terminals for 1.5 mm

2

 cable section for bistable output relay 5A / 250 Vac

  – 2  terminals for 1.5 mm

2

 cable section for auxiliary input (to connect a 

temperature probe or an external contact to reduce setpoint of 3°C)

•  Terminals Thalos Key 230:

  – 3 terminals for 1.5 mm

2

 cable section for monostable output relay 5A / 250 Vac

  – 2 terminals for 1.5 mm

2

 cable section for power supply

•  Operating mode: summer/winter/off (with antifreeze operating mode) 

•  Password protected lock keypad

•  Type of command:

  – on/off with settable differential (0.1 ÷ 1 °C)

  – P8 proportional with 0.8 °C band (-0.3 ÷ +0.5 °C) and period 8 minutes

  – P15 proportional with 1.5 °C band (-0.7 ÷ +0.8 °C) and period 15 minutes

•  Measurement precision: ±0.5 °C

•  Measurement temperature resolution: 0.1°C

•  Settable setpoint range: 2 °C ÷ 50 °C

•  Operating temperature: 0 °C ÷ +50 °C

•  Storage temperature: -10 °C ÷ +65 °C

•  Operating humidity: 20÷90% non condensing

•  Degree of protection: IP40

•   Insulation: reinforced among accessible parts (frontal) and all other terminals

During normal operation the thermostat displays the measured temperature value and the relay status is identified by the symbol

   

(heating) or by 

the symbol

   

(cooling).

 REFERENCE STANDARDS

Compliance with Community Directives:

2014/35/UE (LVD)

2014/30/UE (EMCD)

is declared in reference to the harmonized standard:

• EN 60730-2-9

Minimum settable setpoint - 

L0

It’s the minimum value settable as setpoint.

Settable values: 2 ÷ 50 °C

Maximum settable setpoint - 

KI

It’s the maximum value settable as setpoint.

Settable values: 

L0

 ÷ 50 °C

Operating mode - 

E-I

 if connected to the boiler (heating)

 if connected to a cooling system

Antifreeze temperature - Toff

Minimum temperature maintained with Thalos Key off

(see box «Switch off»).

Settable values: 1 ÷ 50 °C or --- (excluded function)

Type of command - 

REG

 

- (only in heating)

0

   = on/off with settable differential

P8

   = proportional with band 0.8 °C and period 8 minutes

P15

  = proportional with band 1.5 °C and period 15 minutes

Differential - 

d0.3

 - (only for on/off regulation)

Differential (or hysteresis) for temperature regulation. 

Settable values: 0.1 ÷ 1 °C

Input configuration - Est

 - (only battery models) 

^

_[

 for one temperature probe connection

DIG

 for an external contact connection to reduce setpoint 

(see box “Auxiliary input configuration”)

Password for keypad lock - 

PAS

Set a value between 001 and 999 to activate the keypad lock.

Set 

---

 to disable the lock.

If the keypad lock is active, pressing one key 

LoC

 appears and 

the password is required. If it’s properly inserted the keyboard

is unlocked for the next 30 seconds.

•  Thalos Key series thermostats are designed for wall mounting installation. Alternatively, they can be installed to cover the in-built three-modules box.

•   Install the thermostat at a height of about 1.5 m above the floor, away from direct sunlight, away from doors, windows, heat sources, locations with excess or total lack of 

ventilation.

 

 

Connect the wires to the terminals block 

on back of the base, as shown in the 

“wiring diagrams”

.

  

Fix the base on the wall using the 

screws supplied.

  

For battery-powered models only: insert the 

batteries into the battery compartment on the back 

of the thermostat, respecting the indicated polarity.

  

Attach the thermostat to the base, 

at first mating teeth on the higher 

side.

1

1

2

To enter menu Advanced programming keep simultaneously pressed 

for 5 seconds the keys   and   until 

PR

 will appear.

The items of the menu are displayed in succession. For each item is

displayed an identity breviation and its relative blinking value. 

Use the keys   and   to modify the value. The passage to the next 

parameter occurs after 3 seconds without pressing any key. 

The writing 

END

 will appear when all parameters are set and the 

thermostat returns to normal operation saving the effected modifications.

Models battery powered have a auxiliary input that can be 

configured for connection instead of:

- an external temperature probe

-  an external contact for the set-point temperature reduction.  

Closed external contact allows  setpoint reduction of 3 °C  

than the set one. Display shows the symbol  .

For auxiliary input configuration, see “Advanced programming” on this manual.

• 

Battery models

   In the battery-powered supplied models the display backlighting is normally 

OFF and it is enabled (blue colour) entering menu: setpoint modification, 

advanced programming, pin enter.

• 

Models 230V

   In the 230Vac power supplied models the display backlighting is normally ON.

  Backlighting switching OFF

   If not desired the backlighting function can be disabled (for example in 

bedrooms). Then the thermostat continues its normal operation and the 

backlighting is enabled entering menu: setpoint modification, advanced 

programming, pin enter.