Mithos GSM Programmable Thermostat User Manual
-
T0
antifreeze temperature setting in advanced programming
-
T
temperature in manual operation
• Temperature regulation:
- ON/OFF with differential setting between 0.1°C and 1°C
- PROPORTIONAL with proportional band and regulation period setting
• Weekly programming
• Daily resolution: 1h
• Activation delay setting between 15, 30 and 45 minutes (independent for every hour)
• Measured temperature scale:
– 0°C ÷ +50°C (internal probe)
– -40°C ÷ +60°C (external probe)
• Measured and displayed temperature resolution: 0.1°C
• Temperature regulation range: 2.0°C ÷ +50°C
• Measurement update: every 20 seconds
• Measurement precision: ± 0.5°C
• Winter or summer or manual operation
• Optional display in °F
• Automatic change CET / DST
• Password protected keypad lock for installation in public places
• GSM quad band module (900 - 950 - 1800 - 1900 MHz)
• Integrated gsm antenna
• Possibility to store up 5 numbers with whon to act on the instrument and to receive
alarm
• Wall mounting (or on 503 type box)
• Terminal strips:
- Output: 3 poles 1.5mm
2
for bistable relay
- Input:
2 poles 1.5mm
2
for external probe or digital input
2 poles 1.5mm
2
for connection of the power supply
• Operating temperature: 0 °C ÷ +50 °C
• Operating humidity: 20% ÷ 90% noncondensing
• Storage temperature -10°C ÷ +65°C
• Degree of protection: XXD
The preset temperature values (expressed in °C) are the following:
funct. winter
funct. summer
T1
5.0
OFF
T2
15.0
23.0
T3
18.0
25.0
T
MANUAL
20.0
24.0
Regulation of temperature levels is subjected to the following condition: T1 ≤ T2 ≤T3.
In summer mode, T1 cannot be set and corresponds to the air conditioning OFF.