OPERATION

User Manual

WALL-MOUNTING ELECTRONIC THERMOSTATS

 

Read all instructions carefully

DIMENSIONS

LEGEND

INSTALLATION

2

84

28

84

84

28

84

60

press

or

3 sec.

3 sec.

19.8

19.9

...

3 sec.

Vemer S.p.A.

I - 32032 Feltre (BL) • Via Camp Lonc, 16

Tel +39 0439 80638 • Fax +39 0439 80619
e-mail: [email protected]  -  web site: www.vemer.it 

V3IS00943-010

Mod.

 KLIMA LCD RF

Radofrequency wall-mounting electronic thermostats for temperature control 

both in heating and cooling. It must be combined with a radiofrequency remote 

actuator of Vemer range. 

Code  

Model  

Description

VE768800  

Klima LCD RF 

Radiofrequency wall-mounting thermostat

VE769900

 

Set Klima LCD RF   Configured set Klima LCD RF + RX.16A actuator

SAFETY WARNINGS

 

 During device installation and operation it is necessary to observe the following 

instructions:

1)   The device must be installed by a qualified person, in strict compliance with the 

connection diagrams.

2)   Do not power or connect the device if any part of it is damaged.

3)    The device must be installed and activated in compliance with current electric 

systems standards.

4)   Do not use the device for purposes other than those indicated.

5)    In the event of a malfunction of the device do not perform repair and contact the 

technical assistance. 

6)    The device can be used in environments with overvoltage category III and with 

Polliution Degree 2. 

TECHNICAL SPECIFICATIONS

•  Power Supply:

    - 2 alkaline batteries 1.5V (AAA type)

    - battery life: 12 months

•   Summer/winter/off (with antifreeze) operating mode

•   Password protected lock keypad

•   Regulation type:

  - on / off with settable differential (0.1 ÷ 1 °C)

  - P8 proportional with 0.8 °C band (-0.3 ÷ + 0.5 °C) and period 8 minutes

   - tP proportional with opening modulation (only if associated to valves for 

radiators)

•   Communication with the actuator via 433.92 MHz radiofrequency signal   

•    Maximum radiofrequency power transmitted in the frequency bands in which 

operates the radio equipment: 10 dBm max

•   Maximum distance between thermostat and actuator: 50 meters in free field

•   Measurement precision: ± 0.5 °C 

•   Measurement temperature resolution: 0.1 °C

•   Setpoint range: 2 °C ÷ + 50 °C

•   Operating temperatures: 0 °C  ÷ + 50 °C

•   Storage temperature: -10 °C ÷ +65 °C

•   Operating humidity: 20 ÷ 90% non condensing

•   Protection degree: IP40

•   Insulation: reinforced between accessible parts (frontal) and all other terminals 

During the normal operation the thermostat displays the detected temperature value and the system activation is identified by the symbol

   

(heating) or by the symbol 

 (cooling).

  

“Environment temperature” 

field

  

“Off”

 field

  

“Heating activation”

 field

  

“Cooling activation”

 field

  

“Active night reduction”

 field

  

Key

 “   ”

 

increases the selected field - active night reduction

  

Key

 “   ”

 

decreases the selected field

• Association between the Klima LCD RF and the remote actuator

1.   Activate the configuration of the remote actuator channel (refer to the related 

instructions). The actuator will remain in configuration mode for a set time, 

within which it must receive a configuration signal from Klima LCD RF.

2.    Insert the batteries into the Klima LCD RF, respecting the polarity indicated 

on the device (to access the battery compartment, remove the front shell by 

pressing the tab on the bottom of the device).

  After about 3 seconds, the Klima LCD RF starts the configuration procedure 

(indicated by CNF showed on the display) followed by a short test procedure 

(indicated by TST showed on the display) during which the Klima LCD RF sends 

the on-off-on-off sequence to the actuator.

3.    Once the test phase has elapsed, the remote actuator is ready to receive on and 

off signals from the thermostat.

How to associate another remote actuator:

1.   activate the actuator channel configuration

2.   press simultaneously and for at least 3 seconds the keys “   ” and “   ” to 

access advanced programming

3.   the display shows 

RF

. Wait for 2 seconds without pressing any key

4.   the thermostat sends a configuration signal to the actuator and then activates 

the test phase, which ends when the actuator is associated with the thermostat.

Note: The Set Klima LCD RF is sold already configured.

• Indications for positioning

Install the thermostat at a height of about 1.5 m above the floor, away from direct 

sunlight, away from doors, windows, heat sources, locations with excess or total lack of 

ventilation.

The actuator is usually placed near the boiler to be commanded.

Attention: the maximum distance between the Klima LCD RF and the remote actuator 

is about 50m in free field. This value is reduced if there are obstacles in the middle (for 

example walls in reinforced concrete).

 REFERENCE STANDARDS

EU CONFORMITY DECLARATION

Vemer declares that the device is in compliance with the Community 

Directive 2014/53/EU (RED) with reference to the following standards: 

• ETSI EN 300 220-1 • ETSI EN 300 220-2 • ETSI EN 301 489-1 

• ETSI EN 301 489-3 • EN60730-2-9

The full text of the EU Declaration of Conformity is available at 

www.vemer.it address

Minimum settable setpoint -

 

L0

It’s the minimum value settable as setpoint.

Settable values: 2 ÷ 

hI

Maximum settable setpoint -

 

HI

It’s the maximum value settable as setpoint.

Settable values: 

L0

 ÷ 50 °C

Operating mode - 

E-I

 if connected to the boiler (heating)

 if connected to a cooling system

Antifreeze temperature - Toff 

- (only in heating)

Minimum temperature maintained with instrument off.

Settable values: 1 ÷ 10 °C or --- (excluded function)

Regulation type - 

REG

 

- (only in heating)

0

   = on/off with settable differential

P8

   = proportional with band 0.8 °C and period 8 minutes

P15

  = proportional with band 1.5 °C and period 15 minutes

tP 

  =  (to be used only if associated with radiator valves) the valve opens 

proportionally to the difference between the setpoint and the measured 

temperature

Differential - 

d0.3

 - (only for on/off regulation)

Differential (or hysteresis) for temperature regulation.

Settable values: 0.1 ÷ 1 °C

Password for keypad lock - 

PAS

Set a value between 001 and 999 to activate the keypad lock.

Set “---” to disable the lock.

If the keypad lock is active, pressing one key 

LoC

 appears and the password is 

required. If it’s properly inserted the keyboard is unlocked for the next 30 seconds.

rF communication test - 

RF

To activate the communication test between the thermostat and the actuator, press any 

button. During the test, the thermostat sends the sequence of on and off commands 

with a distance of 3 seconds from each other; the display shows 

tSt

. The test lasts a 

maximum of 10 minutes, but it can be stopped first by pressing any key.

The “Advanced Programming” menu is divided into two parts: configuration of RF transmission (

rF

) and programming of operating parameters (PR). To access the advanced program-

ming, press simultaneously and for at least 3 seconds the keys 

 and 

 until the display shows 

RF

. At this point choose within 2 seconds, if to activate the 

RF

 configuration 

procedure (see ‘How to associate another remote actuator’ in box 4) or access the programming of 

PR

 parameters. If no choice is made within 2 seconds, you automatically access 

the RF configuration.

Note: the passage from a menu to the next occurs after 3 seconds 

without keys pressing. Press simultaneously the keys 

 and 

 for at least 3 seconds to force the exit from the menu.

Note: when the thermostat is in heating mode (winter) and is off, it regulates 

according to the 

Toff

 antifreeze temperature in order to prevent freezing of the 

system.

Toff

 can have values from 1 to 50 °C or be excluded; in this case any minimum 

temperature is guaranteed.

Occurs in case of probe failure.

In this case the thermostat sends the actuator the off 

command and the system remains off until the fault is reset.

Occurs for the following values of measured temperature:

t < 0 °C

t >50 °C

Default values

Heating setpoint 

21 °C

Cooling setpoint 

25 °C

Minimum settable setpoint - 

L0

2 °C

Maximum settable setpoint - 

Xi

50 °C

Operating mode

 (heating)

Antifreeze temperature

6 °C

Regulation type

On /Off

Differential

0.3 °C

Password

- - - (desabled)

Switch off

Reset

Error messages

Setpoint modification

Depleted batteries signal

Replace the batteries as soon as 

possible! Dispose of batteries 

in the appropriate recycling 

containers.

Normal operation

Modification of the desired temperature 

(setpoint),

 to increase   

 to decrease

Normal operation

heating on (

   

)

Advanced programming

Night reduction 

“Night reduction” function reduces the 

programmed setpoint by 3 °C.

Press for 3 seconds the key 

 to 

activate (or deactivate, if already active) 

the night reduction.

When the night 

reduction is 

active, the display

shows the

symbol  .

rF

Pr

Reset to delete the settings you made and 

reload the default values. 

To reset:

1  Remove the batteries and wait until the 

display goes off.

2  Insert the batteries. During the flashing 

press the keys 

 and 

 until the 

display shows 

DEf

.

11-2017

3 sec.

Configuration - 

CNF

Indicates the configuration signal sending

(coupling between Klima LCD RF and actuator) in

progress. Once configured, Klima LCD RF

activates a test cycle.

Note: before starting the configuration

it is necessary to activate the channel 

configuration on the receiver.

Test - 

TST

The test cycle allows you to verify the correct 

configuration between Klima LCD RF and the

actuator. The on-off-on-off sequence is started

and when it is ended the Klima LCD RF

resumes normal operation.