- 30 -
User Manual Digital Heat Regulators
English
�
During the installation and operation of the instrument, follow the
instructions set out below:
1) The instrument should be installed by a skilled operator.
2) Strictly follow the connection diagrams when installing the instrument.
3) Do not power or connect the instrument if any part of it is damaged.
4) Before touching the terminals, make sure the wires to be connected to
the instrument are not live.
5) The connection cables should be able to resist the maximum operating
temperature (Tmax), obtained from the sum of the maximum ambient
temperature (Ta) + a temperature of 20 °C (Tmax= Ta + 20 °C).
6) The instruments guarantee a main insulation between the low voltage
(250 V) and very low voltage parts.
7) Any outside switches connected to the controls should guarantee a
minimum insulation at operating temperature of 250 V AC, or should be
protected by equivalent insulation.
8) Contacts: all type 1C (CEI 107-70 and variants).
9) The instruments require no maintenance.
�
Series of digital temperature regulators satisfying the simplest requirements in
the field of heat regulation. They can be used as heating or refrigeration regulators
and as maximum/minimum alarms.
�
Three dedicated base models for probe input:
- PTC thermal resistances
(
P
os.
T
emp.
C
oeff.) - Ni100, Pt100
HT
NiPt
- NTC thermal resistances
(
N
egative
T
emperature
C
oefficient)
HT
NTC
- TC thermocouples
- J, K, L, R, S, T, E, N
HT
JK
• For each single model, the probe input can be configured from the keyboard.
• Two probe inputs for the HT
NTC
models, for the measurement of two temperatures
that can be displayed alternatively by the closure or opening of an outer consensus
to be connected to the instrument, or directly from the keyboard for the 72x72 mm
rear panel version (this version has no digital input).
• Available in versions with 1 or 2 relay outputs with exchange contact.
• Heat regulators with 3 digit, seven segment and decimal point display.
• Relay intervention signalling lamp.
• Temperature T2 signalling lamp (only models HT
NTC
-..P7.. and HT
NTC
-..D..)
• Display range: -99 ÷ +999 °C
• Display resolution: 0.1 °C (-9,9 ÷ +99.9 °C) and 1 °C (< -9.9 °C and > +99.9 °C)
• Precision: ±0.5 % of the end of scale value ±1 digit
(at an ambient temperature of 23 °C)
• Sampling time: 0.5s
TECHNICAL SPECIFICATIONS