- 45 -
User Manual Digital Heat Regulators
English
(21) If the parameter is set to “yes”, a mobile average is taken of 8 measurement
values (4 seconds approx.). If “no”, this average is not calculated
[SNS] sensor menu
Notes:
(22) the range of sensors and the default sensor depend on the model.
All the sensors used are listed below:
NiPt thermal resistance
Type of sensor
Display message
Pt100 (*)
PtE (*)
Ni100
nI
* The instrument is set to this parameter by default.
NTC thermal resistances
Type of sensor
Display message
(**)
nt0
(**)
nt1
type 4
nt2 (*)
(**)
CSt
* The instrument is set to this parameter by default.
It corresponds to the use of temperature sensor NTC code VN870200
(see “Red Line” catalogue under the item Heat Regulation-Temperature Probes)
** For the use of sensors other than “type 4” listed above (see note *), it is possible
to select one of the three items “nt0, nt1, CSt”, corresponding to probes
with different temperature/resistance ratios.
To identify the type of sensor to be selected in these cases, we recommend
contacting our Technical Assistance Service directly
Labels of
parameters that
can be modified
Description
Parameter
values
default notes
TY0
Sensor type 0
-
0
16
(22)
TY1
Sensor type 1
-
12
16
(23)
GFA
Cold joint correction enable
-
no
yes
yes
(24)
S01
Display of sensor 0 or 1
-
S0
S1
S0
(23)
min max
unit
- 44 -
User Manual Digital Heat Regulators
English
[ALR] alarm menu
Notes:
(13) This is the status taken on by the outputs in probe alarm condition (see note 11)
(14) This value is added to or subtracted from the set point defined for the maximum
or minimum alarm respectively
(15) If “yes”, the acoustic signal of the key and the buzzer are enabled in alarm
condition. If “no”, both of these are disabled.
(16) If “yes”, the type of alarm is also displayed during its timing.
If “no”, the type of alarm is displayed only at the end of the timing
[DSP] display menu
Notes:
(17) Parameter active only if the operating mode permits
(18) This value is added to the measurement to compensate for imprecision
(19) This is the resolution at which the measurement is displayed:
0.1 if “HI” or 1.0 if “LO”
(20)
Important:
if the measurement unit is modified, the parameters set are not con
verted automatically, but have to be re-calibrated.
Labels of
parameters that
can be modified
Description
Parameter
values
default notes
SUA
Output status in probe
alarm condition
-
0
3
0
(13)
LOA
Minimum alarm shift
degrees 0.1
100
50
(14)
HIA
Maximum alarm shift
degrees 0.1
100
50
(14)
DFA
Alarm differential
degrees 0.1
100
2
TRA
Alarm activation delay time
min
0
200
0
SOU
Buzzer enable
-
no
yes
no
(15)
EAC
Alarm message in timing enable -
no
yes
no
(16)
min max
unit
Labels of
parameters that
can be modified
Description
Parameter
values
default notes
LO1
Lower limit of set-point 1
degrees -99
HI1
-99
HI1
Upper limit of set-point 1
degrees LO1 999
999
LO2
Lower limit of set-point 2
degrees -99
HI2
-99
(17)
HI2
Upper limit of set-point 2
degrees LO2 999
999
(17)
SOF
Probe calibration offset
degrees -50 +50
0.0
(18)
RIS
Resolution displayed
-
HI
LO
HI
(19)
UNI
Temperature measurement
-
C
F
C
(20)
FIL
Measurement filter
-
no
yes
yes
(21)
min max
unit