Dafne Wi-Fi Chronothermostat User Manual
During the operating, at the beginning of the regulation period, the device measures
the environment temperature and it compares it with the programmed setpoint;
on the basis of this difference the activation time is calculated (and consequently
the deactivation time). The more the measured temperature is next to the setpoint
value – band, the more the activation time will be predominant in comparison with
the deactivation time; on the contrary, the more the measured temperature is next
to the setpoint value + band, the more the deactivation time will be predominant in
comparison with the activation time).
Once regulation period is passed, the device compares again the environment
temperature with the setpoint and it updates the activation and deactivation times for
the new period.
The result of the proportional regulation is subordinated to the correct selection of the
parameters.
Select the value of the regulation type as follows:
• 10’ for low thermal inertia systems (fan-coil)
• 20’ for medium thermal inertia systems (aluminium radiators)
• 30’ for high thermal inertia systems (cast-iron radiators)
Select the regulation band value as follows:
• broad band (5°C) for systems with high thermal gradient
• narrow band (0.5°C) for systems with low thermal gradient
Attention: the device is default confi gured to operate in on/off with
differential set at 0.3°C. This confi guration is suitable for the most part of
the situations and for this reason it’s advisable to modify it only in particular
situations.
To modify the regulation type, the differential value (on/off regulation), band
and period (proportional regulation) see chapter “Regulation parameters” on
page 35.
Emergency regulation (winter mode only)
The device performs a regulation of emergency if an error occurs during the
reading of the probe or in case of time loss.
In case of
probe error
, if the antifreeze function is not excluded, the device activates
the load for 10 minutes every 4 hours. The display shows the writing
(UU
on
fi eld
(8)
.
To modify the regulation type, the differential value (on/off regulation), band
and period (proportional regulation) see chapter “Regulation parameters” on
page 35.